Huawei SMU01A User Manual page 23

Table of Contents

Advertisement

SMU01A
User Manual
Main Menu
Issue 06 (2015-10-08)
Second-Level
Third-Level
Menu
Menu
Others
LVD Setting
Communication
Host CommAddr -
Parameter
Host Baudrate
DHCP
Phone Number 1
Account 1
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
3 LCD Description
Fourth-Level
Default
Menu
Value
LVD2Voltage
43.2 V
LVD2Reconnect
51.5 V
Voltage
Battery
Do Nothing
Temperature
Very High
Action
Battery High
45° C
Temperature
Battery Very
53° C
High
Temperature
–5° C
Battery Low
Temperature
Point
–10° C
Battery Very
Low
Temperature
Load HiTemp
Disable
Dis
NOTE
The menu is
displayed only in
ETP48150,
ETP4890, and
ETP4830
systems
LVD1 Enabled
Disable
LVD2 Enabled
Enable
LVD2Mode
By Voltage
LVD2Voltage
43.2 V
LVD2Recon
51.5 V
Volt
0
-
9600 bit/s
Disable
18