Standard Displays - ABB Totalflow microFLO G4 Startup Manual

Flow computer
Table of Contents

Advertisement

Standard Displays

The single tube µFLO
displays. By default, each display item remains on the display for five (5)
seconds. The user has the ability to change this default to zero (item not
displayed) or any value from 1 to 255 seconds. The user is also able to
change the engineering units and data format for display purposes. All
display items and item groups can be programmed by the user and may
be displayed by user-defined parameters.
Description
STATION ID
DATE/TIME
CHARGER
BATTERY VOLTAGE
LITHIUM BACKUP
TUBE # ID
TUBE # ORIFICE DIAMETER
TUBE # SP
TUBE # DP
TUBE # TEMPERATURE
TUBE # FLOW RATE
TUBE # LAST CALC
TUBE # YEST VOL
TUBE # ACCUM VOL
DP HIGH
DP LOW
Visual Alarm and Status Codes
After the µFLO
records, the LCD displays any alarm conditions that have occurred.
Whenever an alarm occurs, the µFLO
period flow record. The status and alarm codes are user-programmable.
This allows the user to program each annunciator to reflect custom
status information for different applications or tube types.
10
G4
comes from the factory with a set of default
MM/DD/YY HH:MM:SS
N.NNN INCHES
NNN.N.IN. H2O
NN.N DEG F
NNNNNN.N SCF/HR
NNNN.N MCF
NNNNNN.NN MCF
G4
completes recording the volume and operational
Station
ID of the unit
Current date and time, 24-hour clock
Input voltage of the charging unit
Battery voltage as supplied by the external unit
Display showing conditions of the lithium battery
Tube
ID of the tube
Size of the orifice plate
Static pressure absolute, PSIA
Differential pressure, inches H2O
Flowing temperature, °F
Current flow rate, programmable SCF, MCF or
MMCF
Last calculated volume
Yesterday's volume, programmable SCF, MCF or
MMCF
Total accumulated volume, programmable SCF,
MCF or MMCF
(Optional) Percentage of the day that the DP
spent in a high status
(Optional) Percentage of the day that the DP
spent in a low status
G4
records it in the appropriate log
Standard Display

Hide quick links: