Page 1
Operation and Maintenance Manual St. Joseph’s Hospital and Medical Center BNI Medical Education Suite 350 W. Thomas Rd Phoenix, AZ 85013 Fire Alarm System Modification...
Page 2
Operation and Maintenance Manual St. Joseph’s Hospital and Medical Center BNI Medical Education Suite 350 W. Thomas Rd Phoenix, AZ 85013 Fire Alarm System Modification AFE Job #14408 1. Fire Alarm System 1.1. Data Sheets 1.2. Drawings 2. Warranty SYSTEM INSTALLED BY American Fire Equipment Sales and Service Corporation 3107 West Virginia Avenue Phoenix, Arizona 85009...
Page 3
Fire emergency detection and evacuation are extremely critical to life safety, and the NFS2-3030 is ideally suited for these applications. The NFS2-3030 is part of the ONYX® Series of products from NOTIFIER. The NFS2-3030 is ideal for virtually any application because it features a modular design that is configured per project requirements.
Page 4
Modules ...etc. CPU2-3030D display or CPU2-3030ND NFS2-3030 Shown in CAB-C4 with display PRN Series DVC audio in CA-1 in second tier Printer NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD2-80/LCD-80 in terminal mode, but not both at the same time.
Page 5
The architecture of the At the heart of the NFS2-3030 is a set of detection devices and NFS2-3030 software is such that each point entry carries its device protocol —...
AA-30: Audio Amplifier, 30 watts. Switch-mode power. AUXILIARY POWER SUPPLIES AND BATTERIES Includes amplifier and audio input supervision, backup input, AMPS-24(E): One required for each NFS2-3030. Addressable and automatic switchover, power supply, cables. See DN- power supply and battery charger with two 24 VDC outputs.
Page 7
Microprocessor- 6720. controlled, field-programmable from IBM®-compatible PCs FMM-101: FlashScan miniature monitor module. See DN- (requires optional programming kit). Mounts on a CHS-4 series chassis within NFS2-3030. 6720. FMM-4-20: FlashScan 4-20 mA protocol monitor module. See COMPATIBLE INTELLIGENT DEVICES DN-60411.
The left side accommodates one DVC mounted on SEISKIT-PS/2/4: Seismic mounting kit for the FCPS-24S6/S8 a half-chassis and one NFS2-3030 or NCA-2 mounted on a and CAB-PS1. Includes battery bracket for two 7 AH or 12 AH half-chassis. The right side houses a microphone/handset batteries.
Page 9
only, or IP primary with cellular backup. Connects to the primary and secondary ports of a DACT. Replaces IPGSM-COM. See DH-60695. NOTE: For other options including compatibility with retrofit equip- ment, refer to the panel's installation manual, the SLC manual, and the Device Compatibility Document.
We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 8 of 8 — DN-7070:H • 12/19/2011...
Page 11
dn-6823:a • C-25 XPIQ Quad Intelligent Audio Transponder Voice Control Systems General The XPIQ Quad Intelligent Audio Transponder is for distrib- uted multichannel voice evacuation systems, playing up to four simultaneous messages. It is an integrated audio amplification and distribution subsystem controlled by an FACP (Fire Alarm Control Panel) via the SLC (Signaling Line Circuit).
Page 12
• Maximum voltage drop @ 2 A on NAC output: 0.5 VDC. XPIQ-AIB4/AIB1 AUDIO INPUT BOARD • NAC output current: 2.0 A. (4 CHANNEL/1 CHANNEL) • Nominal FFT handset DC resistance: 1.2 K ohms. • All screw terminal blocks accept wire up to 12 AWG (3.31 •...
• AC Fail; yellow LED turns on when AC is lost (all other non- essential LEDs will turn off to conserve batteries). Specifications of these and all Notifier products are available • Battery Trouble; yellow LED turns on for low or no battery from Notifier.
We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 4 of 4 — dn-6823:a • 02/27/09...
Page 15
10 amps of power for general purposes, excluding NAC appli- cations. The ACPS-610(E) is compatible with NOTIFIER intelligent fire alarm control panels using CLIP and FlashScan® protocol. Features • Certified for seismic applications when used with the appro- priate seismic mounting kit.
We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 — DN-60244:C3 • 4/23/2012...
Fire Alarm Control Panels (FACPs). FlashScan® (U.S. Patent 5,539,389) is a communication proto- – B200SR(A): 6.875" (17.46 cm) diameter. col developed by Notifier that greatly increases the speed of – B224RB(A): 6.2" (15.748 cm) diameter. communication between analog intelligent devices. Intelligent –...
Page 18
We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 — DN-6935:D • 12/08/2011...
Page 19
Addressable Devices General Intelligent FlashScan® and CLIP mounting bases and kits pro- vide a variety of ways to install NOTIFIER detectors in any application. Intelligent detectors can be mounted in either flanged or flangeless bases depending on junction box selec- tion (see Junction Box Selection Guide).
Page 20
We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 — DN-60054:E • 7/22/2011...
Indoor Selectable- Output Speaker Strobes and Dual Voltage Evacuation Speakers for Wall Applications The SpectrAlert ® Advance selectable output speaker strobes and dual-voltage evacuation speakers can reduce ground faults and enable faster installation. Features The SpectrAlert Advance Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and •...
Page 22
SpectrAlert Advance Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General SpectrAlert Advance speaker and speaker strobes shall mount to a 4 × 4 × 21⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync•Circuit™...
Page 23
UL Current Draw Data UL Max. Strobe Current Draw (mA RMS) 8 to 17 .5 Volts 16 to 33 Volts Candela Standard Candela Range 15/75 High Candela Range Sound Output UL Reverberant (dBA @ 10 ft.) ½ W ¼ W Wall-Mount SP Series Wall-Mount SPV Series Wall-Mount SPS Series...
Surface Mounting Wall-Mount Speaker Strobe with SPBBS Back Ordering Information for SpectrAlert ® Advance Speakers and Speaker Strobes Wall Mount White Description Speaker only SPWV SPRV Speaker only, High dB SPSW* SPSR* Speaker Strobe, Standard cd SPSW-ALERT — Speaker Strobe, Standard cd, Amber Lens SPSW-CLR-ALERT —...
Page 25
PROJECT INFORMATION SCOPE OF WORK NAME: 1) MODIFY THE EXISTING BUILDING FIRE ALARM SYSTEM FOR THE ST JOESPH'S HOSPITAL AND ST. JOSEPH'S HOSPITAL AND MEDICAL CENTER MEDICAL CENTER - 1NST BNI MEDICAL EDUCATION SUITE. 1NST BNI MEDICAL EDUCATIONAL SUITE ADDRESS: 2) AMERICAN FIRE EQUIPMENT SHALL PROVIDE ALL SYSTEM DRAWINGS, EQUIPMENT, WIRING, 350 WEST THOMAS ROAD RACEWAYS, LABOR, PERMITS AND TESTING FOR ALL LIFE SAFETY DEVICES.
Page 26
SHAFT SHAFT T1020 T1020 DETECTOR SPACING WOMEN WOMEN T1016 900 SQ. FT. T1016 DETECTOR SPACING 900 SQ. FT. T1015 T1015 STARBUCKS STARBUCKS STORAGE STORAGE T1039 T1039 DETECTOR SPACING DETECTOR SPACING DETECTOR SPACING 900 SQ. FT. 900 SQ. FT. 900 SQ. FT. DETECTOR SPACING OFFICE OFFICE...
Page 27
12 VOLT BATTERY 12 VOLT BATTERY 12 VOLT BATTERY 12 VOLT BATTERY (SEE BATTERY CALCULATIONS FOR (SEE BATTERY CALCULATIONS FOR (SEE BATTERY CALCULATIONS FOR (SEE BATTERY CALCULATIONS FOR ACTUALLY BATTERY SIZES) ACTUALLY BATTERY SIZES) ACTUALLY BATTERY SIZES) ACTUALLY BATTERY SIZES)
Page 29
TWO YEAR STANDARD WARRANTY Contractor: JFK Electric 1439 W. San Anglo St Gilbert, AZ 85233 Job Name: St. Joseph’s Hospital and Medical Center – BNI Medical Education Suites 350 W. Thomas Rd. Phoenix, AZ 85013 Warranty Effective Dates: 2/26/15 through 2/26/17 American Fire Equipment Sales &...