Troubleshooting

It is recommended to wire the fan and the touchpad remote prior to turning on the power to the
fan. If the fan is not operable, but the touchpad remote is lighting up, cycle power to the fan.
If cycling the power did not resolve this issue, go to the fault code screen (reference page 59) and
check to see if there is a code present.
Fault Code Causes and Possible Solutions
Code
Name
Supply Voltage
1000
High Warning
Supply Voltage
1001
Low Warning
Supply Voltage
1002
High Fault
Supply Voltage
1003
Low Fault
© 2018 MacroAir Technologies
Code
Factory
Description
Type
Setting
The controller
monitors the bus
Warning 425V DC
voltage to verify it's
below the threshold
The controller
monitors the bus
Warning 80V DC
voltage to verify it's
above the threshold
The controller
monitors the bus
Auto-
voltage to verify it's
450V DC
Reset
below the threshold
and will disable the
fan if it is exceeded
The controller
monitors the bus
voltage to verify it's
Halt
40V DC
above the threshold
and will disable the
fan if it is exceeded
Toll Free: 866 668 3247
Symptoms
1. Turn incoming power off for two
minutes, turn back on
Fan Slows
2. Confirm power is within fan's
specifications
Intermittent/
No Operation
3. Check for spikes with power quality
recorder
4. Confirm that motor wiring is correct
1. Turn incoming power off for two
minutes, turn back on
Fan Slow
2. Confirm incoming power is within
fan's specifications
Intermittent/
No Operation
3. Ask if power has gone out recently or
if there have been storms in the area
4. Confirm that motor wiring is correct
1. Turn incoming power off for two
minutes, turn back on
2. Confirm power is within fan's
Intermittent/
specifications
No Operation
3. Check for spikes with power quality
recorder
4. Confirm that motor wiring is correct
1. Turn incoming power off for two
minutes, turn back on
2. Confirm power is within fan's
Intermittent/
specifications
No Operation
3. Ask if power has gone out recently or
if there have been storms in the area
4. Confirm that motor wiring is correct
Fax: 909 890 2313
w w w.macroairfans.com
Troubleshooting Tips
Rev. Date 040218
65