Table 201. Runtime counter for machines and devices (MDSOPT) main settings
Parameter
Warning value
Alarm value
Initial value
Operating time hour
Operating time mode
Table 202. Three-phase remanent undervoltage supervision (MSVPR)
Characteristic
Operation accuracy
Reset time
Reset ratio
Operate time accuracy in definite time mode
Table 203. Three-phase remanent undervoltage supervision (MSVPR) main settings
Parameter
Start value
Operate delay time
Voltage selection
Num of phases
ABB
Function
MDSOPT
MDSOPT
MDSOPT
MDSOPT
MDSOPT
Function
MSVPR
MSVPR
MSVPR
MSVPR
Value (Range)
0...299999 h
0...299999 h
0...299999 h
0...23 h
1 = Immediate
2 = Timed Warn
3 = Timed Warn Alm
Value
Depending on the frequency of the measured voltage:
20 Hz < f ≤ 70 Hz:
±1.5% of the set value or ±0.002 × U
10 Hz < f ≤ 20 Hz:
±4.0% of the set value or ±0.002 × U
Typically 40 ms
Typically 1.04
±1.0% of the set value or ±20 ms
Value (Range)
0.05...1.20 × U
n
100...300000 ms
1 = phase-to-earth
2 = phase-to-phase
1 = 1 out of 3
2 = 2 out of 3
3 = 3 out of 3
1MRS759144 A
Step
1
1
1
1
-
n
n
Step
0.01
100
-
-
93