Sharp JW-21MN User Manual page 107

Me-net module
Table of Contents

Advertisement

Address(8)
Connection condition of slave station
- Turn ON the corresponding bit of
007750
to
- 00
007757
At ON: Output error code
At OFF: Do not output error code.
Whether the station number information should
007763
be output or not
007764
Flag area top address on the master
to
station
007767
Stop operation of the JW-21MN
Start operation of the JW-21MN
Writing to EEPROM or operation of the JW-
007777
21MN/stop operation
Writing to EEPROM or operation of the JW-
21MN/start operation
Initialize parameter settings
- For initial values of above addresses, see page 11-5 and 6.
(2) Slave station (01 to 77
Address
(8)
007720
Number of receiving bytes of relay link in save
memory function
007721
007722
Number of receiving bytes of register link in save
memory function
007723
Whether the station number information should
007763
be output or not
16
007764
Top address of flag area on each
to
slave station
007767
Stop operation of the JW-21MN
Start operation of the JW-21MN
Writing to EEPROM or operation of the JW-
007777
21MN / stop operation
Writing to EEPROM or operation of the JW-
21MN / start operation
Initialize parameter settings
- For initial values of above address, see page 11-22.
Set contents
connected station number (01 to
77
) from the list at right.
(8)
of master station (0 bit of
(8)
address 000750)
V2
)
(8)
Set contents
V2
V2
V2
Setting method (value, example)
Bit address
7 6 5 4 3 2 1 0
007750
07 06 05 04 03 02 01 00
007751
17 16 15 14 13 12 11 10
007752
27 26 25 24 23 22 21 20
007753
37 36 35 34 33 32 31 30
007754
47 46 45 44 43 42 41 40
007755
57 56 55 54 53 52 51 50
007756
67 66 65 64 63 62 61 60
007757
77 76 75 74 73 72 71 70
00
(H)
01
(H)
007764
(Octal, word)
007765
00
007766
(H)
007767
00
(H)
01
(H)
80
(H)
81
(H)
08
(H)
Setting method (value, example)
(Octal, byte)
(Octal, byte)
00
(H)
01
(H)
007764
(Octal, word)
007765
00
007766
(H)
007767
00
(H)
01
(H)
80
(H)
81
(H)
08
(H)
16-12
- When connecting slave station 00
to 04
and output error code:
(8)
(Address)
(Bit pattern)
007750 − 00011111
007751 − 00000000
to
to
007757 − 00000000
Do not output
Output
When コ0200, set to 000200
(8)
(Set by file address)
00
: Do not output flag
(H)
80
: Output flag
(H)
If 0 is set, the number of bytes will be
the same as the number of transfer
bytes set in the master station.
If 0 is set, the number of bytes will be
the same as the number of transfer
bytes set in the master station.
Do not output
Output
When コ0600, set to 000600
(8)
(Set by file address)
00
: Do not output flag
(H)
80
: Output flag
(H)
(5 / 5)
(1 / 1)