Air conditioner

Installation manual

AC✴✴✴KN4✴EH
• Thank you for purchasing this Samsung air conditioner.
• Before operating this unit, please read this manual carefully and retain it for future
reference.
360_AC_Indoor_IM_AU_ENG_EN.indb 1
2016-05-13 오후 5:01:31

Advertisement

Table of Contents
loading

Summary of Contents for Samsung AC-Series-KN4*EH

  • Page 1: Air Conditioner

    Air conditioner Installation manual AC✴✴✴KN4✴EH • Thank you for purchasing this Samsung air conditioner. • Before operating this unit, please read this manual carefully and retain it for future reference. 360_AC_Indoor_IM_AU_ENG_EN.indb 1 2016-05-13 오후 5:01:31...
  • Page 2 Contents Safety Information Installation Procedure Step 1 Checking and preparing accessories Step 2 Choosing the installation location Step 3 Optional: Insulating the body of the indoor unit Step 4 Installing the indoor unit Step 5 Purging inert gas from the indoor unit Step 6 Cutting and flaring the pipes Step 7 Connecting the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test...
  • Page 3: Safety Information

    • This manual explains how to install an indoor unit centres or returned to the retailer so that it can be with a split system with two SAMSUNG units. The use disposed of correctly and safely. of other types of units with different control systems may damage the units and invalidate the warranty.
  • Page 4: Installing The Unit

    Safety Information Installing the unit • Always verify that a suitable grounding connection is available. • Verify that the voltage and frequency of the power WARNING supply comply with the specifications and that the installed power is sufficient to ensure the operation of IMPORTANT: When installing the unit, always remember any other domestic appliance connected to the same to connect first the refrigerant tubes, then the electrical...
  • Page 5: Installation Procedure

    Installation Procedure Step 2 Choosing the installation Do not install the air conditioner in following places. • Place where there is mineral oil or arsenic acid. Resin location parts flame and the accessories may drop or water may leak. The capacity of the heat exchanger may reduce or the air conditioner may be out of order.
  • Page 6: Indoor Unit Dimensions

    Installation Procedure Indoor unit dimensions (Unit: mm) Category Square panel Circular panel 1000 1050 Front Ceiling opening dimension 960 (950 - 960) Drain hose Refrigerant connector pipe Large+, Large Wire insert hole Drain hose Refrigerant connector pipe Small Wire insert hole →...
  • Page 7: Spacing Requirements

    AC071KN4PEH AC100KN4PEH AC140KN4PEH Model AC125KN4PEH AC071KN4DEH AC100KN4DEH AC140KN4DEH Chassis Large Large+ Net dimension (W × D × H) 947 × 947 × 365 947 × 947 × 365 947 × 947 × 365 947 × 947 × 365 Net weight 24.0 26.0 26.0...
  • Page 8: Step 3 Optional: Insulating The Body Of The Indoor Unit

    Installation Procedure CAUTION NOTE • A: Reference for the outer circumference of the unit • The indoor unit must be installed according to the (When insulating the body of the indoor unit, use A as specified distances in order to permit accessibility from the reference for its outer circumference.) each side, to guarantee correct operation, maintenance, and repair of the unit.
  • Page 9 2 Perform the following steps to install inspection holes in 4 Install the suspension bolts, depending on the ceiling accordance with the panel type. type. a For the recessed installation of the square panel. • Install an inspection hole to the direction of Ceiling support connection parts of the refrigerant pipe and the drain hose.
  • Page 10: Step 5 Purging Inert Gas From The Indoor Unit

    Installation Procedure 7 Adjust the unit to the appropriate position, taking into Step 6 Cutting and flaring the pipes account the installation area for the front panel. 1 Make sure that you have the required tools available: • Place the pattern sheet on the indoor unit. pipe cutter, reamer, flaring tool, and pipe holder.
  • Page 11: Step 7 Connecting The Assembly Pipes To The Refrigerant Pipes

    5 Check that the flaring is correct, referring to the Outer diameter (mm) Torque (N•m) illustrations below for examples of incorrect flaring. Ø6.35 14 to18 Ø9.52 34 to 42 Ø12.70 49 to 61 Ø15.88 68 to 82 Ø19.05 100 to 120 (1 N•m=10 kgf•cm) Damaged Cracked...
  • Page 12: Step 8 Performing The Gas Leak Test

    Installation Procedure Step 8 Performing the gas leak test CAUTION To identify potential gas leaks on the indoor unit, inspect • Be sure to wrap insulation tightly without any gaps. the connection area of each refrigerant pipe using a leak detector for R-410A.
  • Page 13: Step 10 Installing The Drain Hose And Drain Pipe

    Insulation type (heating/cooling) Standard High humidity Pipe Pipe size Remarks (Less than 30°C, 85%) (Over 30°C, 85%) EPDM, NBR Ø6.35 to Ø9.52 Liquid pipe Ø12.7 to Ø19.05 Ø6.35 The internal Ø9.52 temperature is higher than 120°C. Ø12.70 Gas pipe Ø15.88 Ø19.05 • When installing insulation in the places and 3 Wrap the supplied large sealing pad over the metal...
  • Page 14 Installation Procedure • Install horizontally. CAUTION Check that the indoor unit is level with the ceiling by using the leveller. Be horizontal • Install air ventilation to drain condensation smoothly. Air ventilation Indoor unit Flexible hose • Max. allowable axis gap. Ceiling • If it is necessary to increase the height of the drain pipe, install the drain pipe straight within 300 mm from the...
  • Page 15: Step 11 Performing The Drainage Test

    Step 11 Performing the drainage test CAUTION 1 Do a leak test at the connection part of the flexible hose • Only in the Cool mode, you can check the correct and the drain pipe: operation of the drain pump. a Connect a general hose to the connection part of When the electric cable connection has not been the flexible hose of the indoor unit, and pour in...
  • Page 16 Installation Procedure CAUTION Indoor power supply • Always remember to connect the air conditioner to Power supply Max/Min(V) Indoor power cable the grounding system before performing the electric ±10% 220 to 240V, 50 Hz 0.75 to 1.5 mm², 3 wires connections.
  • Page 17: Step 13 Optional: Extending The Power Cable

    Step 13 Optional: Extending the Method 1 Method 2 power cable 1 Prepare a crimping tool and the following tools. Tools Spec Shape Connection sleeve Connection sleeve Crimping pliers MH-14 4 Using a crimping tool, compress the two points and flip it over and compress another two points in the same location.
  • Page 18 Installation Procedure 7 After tube contraction work is completed, wrap it with Common steps for setting the addresses and options the insulation tape to finish. AR-KH00E remote control (for 360 cassette only) CAUTION • Make sure that the connection parts are not exposed to Entering the Setting the outside.
  • Page 19 SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 On (SEG1 to SEG12) Off (SEG13 to SEG24) SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Take the steps presented in the following table: Steps Remote control display 1 Set the SEG2 and SEG3 values:...
  • Page 20 Installation Procedure Steps Remote control display 4 Press the (Mode) button. Dry and On appear on the remote control display. 5 Set the SEG6 and SEG8 values: a Set the SEG6 value by rotating the Wheel counterclockwise until the value you want to set appears on the remote control display.
  • Page 21 Steps Remote control display b Set the SEG12 value by rotating the Wheel clockwise until the value you want to set appears on the remote control display. SEG12 When you rotate the Wheel, values appear in the following order: 10 Press the (Mode) button.
  • Page 22 Installation Procedure Steps Remote control display 15 Set the SEG18 and SEG20 values: a Set the SEG18 value by rotating the Wheel counterclockwise until the value you want to set appears on the remote control display. SEG18 b Set the SEG20 value by rotating the Wheel clockwise until the value you want to set appears on the remote control display.
  • Page 23 3 Check whether the option values that you have set are NOTE correct by pressing the (Mode) button repeatedly • The remote control display and buttons may vary depending on the model. [SEG2, SEG3] [SEG4, SEG5] [SEG6, SEG8] [SEG9, SEG10] 1 Enter the mode for setting the options: a Remove the batteries from the remote control, [SEG11, SEG12]...
  • Page 24 Installation Procedure SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 On (SEG1 to SEG12) Off (SEG13 to SEG24) SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Take the steps presented in the following table: Steps Remote control display 1 Set the SEG2 and SEG3 values:...
  • Page 25 Steps Remote control display 4 Press the (Mode) button. Dry and On appear on the remote control display. 5 Set the SEG6 and SEG8 values: a Set the SEG6 value by pressing the (Low Fan) button repeatedly until the value you want to set appears on the remote control display. SEG6 b Set the SEG8 value by pressing the (High Fan) button repeatedly until the...
  • Page 26 Installation Procedure Steps Remote control display b Set the SEG12 value by pressing the (High Fan) button repeatedly until the value you want to set appears on the remote control display. SEG12 When you press the (Low Fan) or (High Fan) button, values appear in the following order: 10 Press the (Mode) button.
  • Page 27 Steps Remote control display 14 Press the (Mode) button. Dry and Off appear on the remote control display. 15 Set the SEG18 and SEG20 values: a Set the SEG18 value by pressing the (Low Fan) button repeatedly until the value you want to set appears on the remote control display. SEG18 b Set the SEG20 value by pressing the (High Fan) button repeatedly until the...
  • Page 28 Installation Procedure Steps Remote control display 19 Set the SEG23 and SEG24 values: a Set the SEG23 value by pressing the (Low Fan) button repeatedly until the value you want to set appears on the remote control display. SEG23 b Set the SEG24 value by pressing the (High Fan) button repeatedly until the value you want to set appears on the remote control display.
  • Page 29 2 Set an address for each indoor unit using the remote control, according to your air conditioning system plan, by referring to the following table and by following the steps in Common steps for setting the addresses and options on page 18. • The indoor unit addresses (main and RMC addresses) are set to 0A0000-100000-200000-300000 by default.
  • Page 30: Setting The Installation Options In A Batch

    Installation Procedure Setting the installation options in a batch 2 Set the installation options of indoor units, by referring to the following table and by following the steps in Common steps for setting the addresses and options on Option No. for an indoor unit address: page 18.
  • Page 31 Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Setting the Use of external Maximum filter Function Page output of S-Plasma ion Buzzer control control usage time external control Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details Thermo Use of 1000 Disuse...
  • Page 32: Changing The Addresses And Options Individually

    Installation Procedure Changing the addresses and options individually When you want to change the value of a specific option, refer to the following table and follow the steps in Common steps for setting the addresses and options on page 18. Option SEG1 SEG2...
  • Page 33 For the installation of the circular 4 Rotate the paper compass diametrically to draw a circle on the ceiling. panel Making a circular opening on the ceiling Use a paper compass printed on the indoor unit package. (attached inside to the upper part) 1 Use a bolt or a pin to fix pivot point of the paper compass on center of the ceiling.
  • Page 34: Troubleshooting

    Troubleshooting Indoor unit display indications Condition Ice blue Yellow green Blue Power reset (blinking once every 2 seconds) In the defrost operation (blinking once every 10 seconds) Open or short circuit error of the indoor-temperature sensor Error of the outdoor unit Communication error between the indoor and outdoor units Open or short circuit error of a sensor (evaporator-in, evaporator-out, or discharge sensor) in the indoor unit...
  • Page 35 Memo English 360_AC_Indoor_IM_AU_ENG_EN.indb 35 2016-05-13 오후 5:01:51...