base control
Set continuous
operation
Enable network
independent ON-OFF
memory (Auto-Restart)
Page 18
1.4
If pressure drops in relatively small receiver / pressure network volumes must
be avoided at any price, continuous operation can be set as follows:
1. Enter Code 733, as described under parameterization (see page 12)
and the display shows illustration
The shading of the left arrow blinks. This means: automatic power econ-
omy operating mode selection.
2. Press Info key
to change to illustration
back...).
The shading of the right arrow blinks. This means: continuous operation.
3. Press Enter key
ing symbol, and the main display with the selected symbol appears.
Caution!
With activated automatic restart (Auto-Restart) the compressor restarts
automatically after a power failure.
Condition: the network pressure is lower than the set switch-on pressure and
it was switched on beforehand.
Using energy independent memory for remembering ON-OFF:
Normally a compressor always assumes an OFF status directly after an elec-
trical power failure.
Parameterization of the control
left.
to overwrite the non-volatile EEPROM with the blink-
BOGE base control for screw compressors
(press again to toggle
→