6.2.3.4

Device Address

Note
The address can only be changed from a remote master such as NI-FBUS Configurator or
DeltaV. See Addressing in manual Foundation Fieldbus for Level Instruments
(7ML19985MP01) for further details.
Read only. The unique address of the device on the network.
Values
● In PROGRAM mode, navigate to: Level Meter > Communication (5.) > Device Address (5.2.)
to view the device address.
● Press Mode
6.3

Application examples

Note
In the applications illustrated below, values are for example purposes only.
You can use these examples as setup references. Enter the values in the parameter tables to
select the corresponding functions.
Configure the basic settings using the Quick Start wizard parameters. (These parameters are
inter-related, and changes take effect only after you select FINISH in final step: Wizard
Complete.)
In each example, after performing a Quick Start, navigate to the other required parameters
(either via the handheld programmer or via AMS Device Manager) and enter the appropriate
values.
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 08/2014, A5E32221411-AC
Temporary range during initial commissioning: 248 - 251. Permanent range
after commissioning complete (written to non-volatile memory in the device):
16-247
to return to Measurement mode.
Commissioning
6.3 Application examples