Oil No
1
2
3
4
Table K - 1: Water Solubility as a Function of the Oil Composition and Temperature
The Hydran M2-X measures the relative saturation of water in the oil, which gives
the following information:
Relative saturation of the oil at the operation temperature
• Temperature at which the water will saturate and condense in the oil
• Estimation of the water percentage in the paper insulation system
For instance, in the calculation of the moisture content in the insulating paper,
the relative saturation is more significant than the absolute water content. The
Hydran M2-X provides directly the relative saturation, thus avoiding inaccuracies
linked with a poorly defined saturation curve.
Page 196
Aromatic Content
(%)
5
8
16
21
Figure K - 1: Water Solubility Curves According to Different Sources
Hydran* M2-X Instruction Manual
Solubility (ppm)
20˚C
40˚C
42.8
97.5
46.8
108
56.2
128.3
75
162
70˚C
279
316
369.2
436
MA-029
Rev. 1.0, 30-Jul-18