Emergency Lighting Interface LUT-ELI-3PH
Please read this guide before installing.
Contents
Wiring Overview for LUT-ELI-3PH units on:
RadioTouch ............................................................13
GND
12
12
11
11
10
10
System Ratings
• Voltage: 100-347 V 50/60 Hz 30 mA
• Current: 20 A maximum circuit breaker
For use with Lutron
: GRAFIK Eye
®
panels; LCP128
panels; Softswitch128 panels;
TM
EcoSystem
lighting control system; Energi Savr
®
Node
units; Quantum
TM
units, and RadioTouch
Note: This device does not provide emergency power.
An Emergency (Essential) power source must be
provided.
LUT-ELI-3PH Installation Guide
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
S1
CLASS 2 LOW VOLTAGE WIRING
GP, LP, and XP
®
systems; GRAFIK Eye QS
®
lighting controllers.
®
|
Listing
The Emergency Lighting Interface - LUT-ELI-3PH is
Page
UL924 Listed as "Emergency Lighting and Power
Equipment". The interface shall be used with: Lutron
GRAFIK Eye GP, XP, and LP panels; LCP128 panels;
Softswitch128 panels; EcoSystem; Quantum; GRAFIK
Eye QS, RadioTouch controllers, and Energi Savr
Node units.
Description
The LUT-ELI-3PH unit senses the line voltage on
all three phases or a single phase and controls the
emergency signal to the following compatible Lutron
products/systems:
• Circuit Selector for GP, LP, XP panels
• LCP/XPS controller for LCP128, and
Softswitch 128 panels
• EcoSystem Bus Supply
• Quantum Bus Supply
• Grafik Eye QS unit
• RadioTouch controller
• Energi Savr Node unit
When one or more phases of normal power are lost,
the LUT-ELI-3PH unit sends a signal to the affected
device(s), activating the emergency mode. Any lights
controlled by these devices will go to the emergency
light level setting (factory set to 100% intensity). When
normal power is restored, the lights will return to their
previous intensities.
Important Safeguards
• Follow all national and local electrical codes and safety
standards.
• Turn off power before installation.
• Line voltage input to the LUT-ELI-3PH unit must be
from the NORMAL (non-essential) power source.
• Read and follow all safety instructions.
• For indoor use only.
• Equipment should be mounted in locations and
at heights where it will not readily be subjected to
tampering by unauthorized personnel.
• Do not use this equipment for other than intended use.
• All servicing should be performed by qualified service
personnel.
System Limits (per / LUT-ELI-3PH)
• 32 circuit selectors
• 100 RadioTouch Controllers
• 32 EcoSystem bus supplies
• 32 Quantum bus supplies
• 32 Energi Savr Node units
• 32 LCP/XPS Controllers
Installation Guide