Lutron Electronics LUT-ELI-3PH Installation Manual

Lutron Electronics LUT-ELI-3PH Installation Manual

Emergency lighting interface
Hide thumbs Also See for LUT-ELI-3PH:

Advertisement

Emergency Lighting Interface LUT-ELI-3PH
Please read this guide before installing.
Contents
Ratings and model number overview . ...........................1
Mounting the Interface .................................................2
Wiring Overview for LUT-ELI-3PH units on:
RadioTouch Systems ...............................................2
Panel-Based Systems . .............................................4
GRAFIK Eye QS units . ..............................................9
Energi Savr Node units ..........................................10
Control Panel (FACP) .............................................12
RadioTouch ............................................................13
Panel Based Systems ............................................14
Energi Savr Node Installations . ...............................15
EcoSystem or Quantum System ............................16
Grafik Eye QS Installation .......................................17
GND
12
12
11
11
10
10
System Ratings
• Voltage: 100-347 V 50/60 Hz 30 mA
• Current: 20 A maximum circuit breaker
For use with Lutron
: GRAFIK Eye
®
panels; LCP128
panels; Softswitch128 panels;
TM
EcoSystem
lighting control system; Energi Savr
®
Node
units; Quantum
TM
units, and RadioTouch
Note: This device does not provide emergency power.
An Emergency (Essential) power source must be
provided.
LUT-ELI-3PH Installation Guide
bus supplies.......................8
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
S1
CLASS 2 LOW VOLTAGE WIRING
GP, LP, and XP
®
systems; GRAFIK Eye QS
®
lighting controllers.
®
|
Listing
The Emergency Lighting Interface - LUT-ELI-3PH is
Page
UL924 Listed as "Emergency Lighting and Power
Equipment". The interface shall be used with: Lutron
GRAFIK Eye GP, XP, and LP panels; LCP128 panels;
Softswitch128 panels; EcoSystem; Quantum; GRAFIK
Eye QS, RadioTouch controllers, and Energi Savr
Node units.
Description
The LUT-ELI-3PH unit senses the line voltage on
all three phases or a single phase and controls the
emergency signal to the following compatible Lutron
products/systems:
• Circuit Selector for GP, LP, XP panels
• LCP/XPS controller for LCP128, and
Softswitch 128 panels
• EcoSystem Bus Supply
• Quantum Bus Supply
• Grafik Eye QS unit
• RadioTouch controller
• Energi Savr Node unit
When one or more phases of normal power are lost,
the LUT-ELI-3PH unit sends a signal to the affected
device(s), activating the emergency mode. Any lights
controlled by these devices will go to the emergency
light level setting (factory set to 100% intensity). When
normal power is restored, the lights will return to their
previous intensities.
Important Safeguards
• Follow all national and local electrical codes and safety
standards.
• Turn off power before installation.
• Line voltage input to the LUT-ELI-3PH unit must be
from the NORMAL (non-essential) power source.
• Read and follow all safety instructions.
• For indoor use only.
• Equipment should be mounted in locations and
at heights where it will not readily be subjected to
tampering by unauthorized personnel.
• Do not use this equipment for other than intended use.
• All servicing should be performed by qualified service
personnel.
System Limits (per / LUT-ELI-3PH)
• 32 circuit selectors
• 100 RadioTouch Controllers
• 32 EcoSystem bus supplies
• 32 Quantum bus supplies
• 32 Energi Savr Node units
• 32 LCP/XPS Controllers
Installation Guide
Lutron
1
|
®

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LUT-ELI-3PH and is the answer not in the manual?

Questions and answers

Summary of Contents for Lutron Electronics LUT-ELI-3PH

  • Page 1: Table Of Contents

    System Ratings • Do not use this equipment for other than intended use. • Voltage: 100-347 V 50/60 Hz 30 mA • All servicing should be performed by qualified service • Current: 20 A maximum circuit breaker personnel. For use with Lutron : GRAFIK Eye GP, LP, and XP ® ® panels; LCP128 panels; Softswitch128 panels; System Limits (per / LUT-ELI-3PH) EcoSystem lighting control system; Energi Savr • 32 circuit selectors ® Node units; Quantum systems; GRAFIK Eye QS • 100 RadioTouch Controllers ® units, and RadioTouch lighting controllers. • 32 EcoSystem bus supplies ®...
  • Page 2: Mounting The Interface

    ® product or system, which the LUT-ELI-3PH will be Insert NEC Class 2/PELV controlling. Specific wiring to these devices will be wires through knockouts described in the following sections. 8. Reinstall front enclosure cover. Note: Call the Lutron Technical Support Center at (800) 523-9466 for restrictions and wiring requirements for emergency fixtures (fixtures that never turn off or have a battery backup ballast in the fixture). Installing a LUT-ELI-3PH Unit in a RadioTouch System ® Line Voltage Connections Note: Provide proper short-circuit and overcurrent WARNING! Danger of shock. May result protection at the distribution panel. Maximum circuit in serious injury or death. DO NOT WIRE breaker rating of 20 A. WHEN LIVE! Switch off power to all power...
  • Page 3 Emergency Lighting Interface LUT-ELI-3PH Installation Guide Installing a LUT-ELI-3PH Unit in a RadioTouch System (continued) ® Class 2/PELV Connections Test the System ® Note: When wiring for a backup/emergency source of Please perform the following tests to ensure proper power, the RadioTouch Controller (models RTA-RX-F, installation. RTA-RX-F-SC, RTA-RXSW), being used for the backup/ 1. Turn off one of the Normal (Non-Essential) phase(s) emergency lights (Unit A and B) cannot be controlled by breaker(s) that the LUT-ELI-3PH unit is monitoring. an occupancy sensor. Units A and B DIP switch 2 must be in the down position. You should see the following: • All lights controlled by Emergency (Essential) panel...
  • Page 4: Panel-Based Systems

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Installing a LUT-ELI-3PH Unit in a Panel-Based System Line Voltage Connections Note: Provide proper short-circuit and overcurrent WARNING! Danger of shock. May result protection at the distribution panel. Maximum circuit in serious injury or death. DO NOT WIRE breaker rating of 20 A. WHEN LIVE! Switch off power to all power feeds via circuit breaker or isolator before wiring or servicing the LUT-ELI-3PH unit and Panel-Based System. Buttons and LEDs in the unit are used for troubleshooting.
  • Page 5 Emergency Lighting Interface LUT-ELI-3PH Installation Guide Installing a LUT-ELI-3PH Unit in a Panel-Based System (continued) Class 2/PELV: USA Connections ® Wiring Notes Notes • NEC Class 2/PELV wiring link is 500 to 2000 feet • Pull NEC Class 2/PELV wiring for system (152 to 610 m), use Lutron cable GRX-CBL-46L: communications. ® - T wo 12 AWG (2.5 mm ) for control wiring • NEC Class 2/PELV wiring must be daisy-chained. (+V and com) • NEC Class 2/PELV wiring must be run separately from - O ne twisted, shielded pair 22 AWG (0.5 mm...
  • Page 6 Emergency Lighting Interface LUT-ELI-3PH Installation Guide Installing a LUT-ELI-3PH Unit in a Panel-Based System (continued) Class 2/PELV Panel to Panel Wiring Notes ® • Emergency Power: The additional 18 AWG (1.0 mm ) wire • Each NEC Class 2/PELV terminal can accept only is a “sense” line from terminal 12 on the LUT-ELI-3PH. This two 18 AWG (1.0 mm ) wires. Two 12 AWG sense line allows an Emergency (Essential) lighting panel to (2.5 mm ) conductors won't fit. Connect as shown “sense” when Normal (Non-Essential) power is lost. If more below in wiring example B. than one emergency lighting panel needs to sense Normal Connections (Non-Essential) from a specific LUT-ELI-3PH unit, you may LUT-ELI-3PH...
  • Page 7 Emergency Lighting Interface LUT-ELI-3PH Installation Guide Installing a LUT-ELI-3PH Unit in a Panel-Based System (continued) Setting the Circuit Selector Normal/Emergency Circuit Selector in Normal Circuit Selector in (Non-Emergency) Panel Emergency (Essential) Panel Switch (SW6) Position Panels are shipped with SW6 (located at the base of each Circuit Selector) in the middle position. Terminal 5 (sense) 1 2 3 4 1 2 3 4 has no affect on the circuit selector operation. Data A OK Power OK...
  • Page 8: Ecosystem Or Quantum

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Installing a LUT-ELI-3PH Unit in an EcoSystem or Quantum System ® ® Line Voltage and NEC Class 2/PELV Connections ® Note: Provide proper short-circuit and overcurrent WARNING! Danger of shock. May result in serious injury or death. DO NOT WIRE WHEN protection at the distribution panel. Maximum circuit LIVE! Switch off power to all power feeds breaker installation of 20 A.
  • Page 9: Grafik Eye Qs Units

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Installing a LUT-ELI-3PH Unit in a GRAFIK Eye QS Unit ® Class 2/PELV Connections ® WARNING! Danger of shock. May result in Notes serious injury or death. DO NOT WIRE WHEN • Provide proper short-circuit and overcurrent LIVE! Switch off power to all power feeds protection at the distribution panel. Maximum via circuit breaker or isolator before wiring or circuit breaker installation of 20 A. servicing the LUT-ELI-3PH unit and GRAFIK Eye • When normal power loss is detected at the...
  • Page 10: Energi Savr Node Units

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Installing a LUT-ELI-3PH Unit with an Notes: Provide proper short-circuit and overcurrent protection at the distribution panel. Maximum circuit Energi Savr Node Unit(s) breaker installation of 20 A. Class 2/PELV Connections ® • A Lutron PP-120H or PP-277H power pack must be ® WARNING! Danger of shock. May result used to power the LUT-ELI-3PH unit when used with an in serious injury or death. DO NOT WIRE Energi Savr Node unit(s). Both the power pack and the...
  • Page 11: Emergency Power Mode Setup: Lcp Panels

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Emergency Power Mode Setup: LCP128 / Softswitch128 ® with LUT-ELI-3PH This step is only performed if an emergency pattern* is Notes: needed when normal power is lost. All control device • I f UL 924 certification is required, the Lutron ® inputs and time clock events are ignored while in Emergency Lighting Interface (LUT-ELI-3PH) may be emergency power mode. This step will define if the used to meet code. The LUT-ELI-3PH unit senses panel has emergency circuits and how to configure the the normal (non-essential) line voltage on all three emergency pattern. phases (3PH) of normal power. When one or more phases of power are lost, the LUT-ELI-3PH unit will • F or all the emergency (essential) lighting panels, move send a signal to terminal 5 on the LCP128/Soft- the emergency switches to the right position (see switch128 controller(s). When the emergency illustration below).
  • Page 12: Nec Class 2/Pelv Wiring To Fire Alarm Control Panel (Facp)

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Class 2/PELV Wiring to ® Fire Alarm Control Panel (FACP) • The LUT-ELI-3PH unit will have a factory installed • Use only with normally open (terminals 3 and 4) or normally jumper to provide the normally closed input signal closed (terminals 5 and 6) dry contact closure. When the for the supervisory circuit when a normally closed proper contact state is triggered, it must be maintained FACP input is not provided. for the LUT-ELI-3PH unit to go into Emergency Mode. • Consult your Fire Alarm Control Panel’s instruction Once the contact is released, the LUT-ELI-3PH unit will manual before connecting to the LUT-ELI-3PH unit. return the GRAFIK Systems GP, LP, XP panels, XPS, • Do not connect any voltage source to the FACP LCP, RadioTouch controller, EcoSystem Bus Supply, ® ®...
  • Page 13: Troubleshooting Radiotouch

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Troubleshooting RadioTouch ® Symptom Possible Cause Solution Lights are at full LUT-ELI-3PH unit is not connected Connect terminal 2 ‘Occ Sig’ from the RadioTouch intensity and can to Signal on the RadioTouch Controller to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit not be controlled Controller by an addressed One or more of the phases feeding Turn ON all normal power phases to LUT-ELI-3PH unit transmitter the LUT-ELI-3PH unit are off (phase LED on the LUT-ELI-3PH unit will be off) Neutral is not connected on the Connect neutral LUT-ELI-3PH unit (phase LED on the LUT-ELI-3PH unit will be OFF) is not connected on the Connect terminal 4 ‘24V ’ from RadioTouch Controller to LUT-ELI-3PH unit (phase LED on terminal 8 ‘+ V Input’ on the LUT-ELI-3PH unit the LUT-ELI-3PH unit will be OFF) There is a short across FACP and Remove short...
  • Page 14: Panel Based Systems

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Troubleshooting Panel Based Systems Symptom Possible Cause Solution Lights are at Sense wire is not connected from Connect terminal 5 ‘Sense’ from the Circuit selector/ full intensity the Circuit selector/controller to the controller to terminal 12 ‘Sense’ on the LUT-ELI-3PH unit and can not be LUT-ELI-3PH unit controlled by One or more of the phases feeding Turn ON all normal power phases to LUT-ELI-3PH unit the wallstation the LUT-ELI-3PH unit are off (phase (Circuit selector/ LED on the LUT-ELI-3PH unit will controller be OFF) reads “ord”), or Neutral is not connected on the Connect neutral controller reads LUT-ELI-3PH unit (phase LED on Emergency the LUT-ELI-3PH unit will be OFF) Mode 24VFW is not connected on the Connect terminal 2 ‘24VFW’ from the Circuit selector/...
  • Page 15: Energi Savr Node Installations

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Troubleshooting Energi Savr Node Installations Symptom Possible Cause Solution Lights are at full Signal wire is not connected from Connect ‘Emerg’ terminal from the Energi Savr Node unit to intensity. Unit will the LUT-ELI-3PH unit to the Energi terminal 1 ‘Signal’ on the LUT-ELI-3PH unit not respond to Savr Node unit local control or One or more of the phases feeding Turn ON all normal power phases to LUT-ELI-3PH unit input signals. the LUT-ELI-3PH unit are off (phase LED on the LUT-ELI-3PH unit will be OFF) Neutral is not connected on the Connect neutral LUT-ELI-3PH unit (phase LED on the LUT-ELI-3PH unit will be OFF) 24VFW is not connected on the Connect red wire (24 V ) from the PP-120H or PP-277H LUT-ELI-3PH unit (phase LED on unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit...
  • Page 16: Ecosystem Or Quantum System

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Troubleshooting EcoSystem or Quantum System Installations ® ® Symptom Possible Cause Solution Lights are at full Signal wire is not connected from the Connect ‘CCI-EMERG’ terminal from the Ecosystem bus intensity. System supply to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit LUT-ELI-3PH unit to the Ecosystem will not respond bus supply to local control Signal wire is not connected from the Connect ‘EM’ terminal from the Quantum bus supply to or input signals. terminal 1 ‘Signal’ on the LUT-ELI-3PH unit LUT-ELI-3PH unit to the Quantum bus supply One or more of the phases feeding Turn on all normal power phases to LUT-ELI-3PH unit the LUT-ELI-3PH unit are off (phase LED on the LUT-ELI-3PH unit will be OFF) Neutral is not connected on the LUT-...
  • Page 17: Grafik Eye Qs Installation

    Emergency Lighting Interface LUT-ELI-3PH Installation Guide Troubleshooting a GRAFIK Eye QS Installation ® Symptom Possible Cause Solution Lights are at LUT-ELI-3PH unit is not connected Connect the ‘CCI SIG’ terminal from the GRAFIK Eye QS full intensity. to ‘CCI SIG’ on the GRAFIK Eye QS unit to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit System will not unit respond to One or more of the phases feeding Turn on all normal power phases to LUT-ELI-3PH unit local control or the LUT-ELI-3PH unit are off (phase input signals. LED on the LUT-ELI-3PH unit will be off) Neutral is not connected on the Connect neutral LUT-ELI-3PH unit (phase LED on the LUT-ELI-3PH unit will be OFF) 24 V is not connected on the Connect the ‘24 V...
  • Page 18 Emergency Lighting Interface LUT-ELI-3PH Installation Guide NOTES: LUT-ELI-3PH Installation Guide...
  • Page 19 Emergency Lighting Interface LUT-ELI-3PH Installation Guide NOTES: LUT-ELI-3PH Installation Guide...
  • Page 20 Belden is a registered trademark of Belden, Inc., Richmond, Indiana. Liberty Wire & Cable is a registered trademark of Liberty Wire & Cable, Colorado Springs, Colorado. Lutron, EcoSystem, GRAFIK Eye, Quantum, RadioTouch, Softswitch128, and the sunburst logo are registered trademarks and Energi Savr Node and LCP128 are trademarks of Lutron Electronics Co., Inc. Printed in the U.S.A.

Table of Contents