8. Troubleshooting 
Code 
Name 
ID01 
GridOVP 
ID02 
GridUVP 
ID03 
GridOFP 
ID04 
GridUFP 
ID05 
BatOVP 
ID09 
HW_LLCBus_OVP 
ID10 
HW_Boost_OVP 
ID11 
HwBuckBoostOCP 
ID12 
HwBatOCP 
ID15 
HwAcOCP 
ID17 
HwADFaultIGrid 
ID18 
HwADFaultDCI 
ID19 
HwADFaultVGrid 
ID21 
MChip_Fault 
 
 
description 
The power grid voltage is too high   
The power grid voltage is too low    
The  power  grid  frequency  is  too 
high   
The  power  grid  frequency  is  too 
low   
The battery voltage is too high    
LLCBus  voltage  is  too  high  and  has 
triggered hardware protection 
Boost  voltage  is  too  high  and  has 
triggered hardware protection  
BuckBoost  current  is  too  high  and 
has triggered hardware protection  
The battery current is too high and 
has triggered hardware protection  
The grid current is too high and has 
triggered hardware protection 
The grid current sampling error 
The DCI sampling error 
The grid voltage sampling error 
The master chip fault 
solution 
If  the  alarm  occurs  occasionally,  the  possible cause 
is  that  the  electric  grid  is  abnormal  occasionally. 
ME3000SP  automatically  returns  to  normal 
operating  status  when  the  electric  grid's  back  to 
normal. 
If  the  alarm  occurs  frequently,  check  whether  the 
grid  voltage/frequency  is  within  the  acceptable 
range. If no, contact technical support. If yes, check 
the  AC  circuit  breaker  and  AC  wiring  of  the 
ME3000SP. 
If  the  grid  voltage/frequency  is  within  the 
acceptable range and AC wiring is correct, while the 
alarm  occurs  repeatedly,  contact  technical  support 
to  change  the  grid  over‐voltage,  under‐voltage, 
over‐frequency,  under‐frequency  protection  points 
after  obtaining  approval  from  the  local  electrical 
grid operator. 
If  the  alarm  occurs  occasionally,  the  possible cause 
is during the process of charging. 
If the alarm occurs occasionally, check whether the 
overvoltage  setting  of  the  battery  consistent  with 
the parameter of battery manufacturer and contact 
technical support.  
ID09‐ ID26 are internal faults of ME3000SP, turn OFF 
the "DC & AC switch", wait for 5 minutes, then turn 
ON  the  "DC  switch"  and  turn  ON  the  "AC  switch". 
Check  whether  the  fault  is  rectified.  If  no,  please 
contact technical support. 
 
 
 
37

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ME 3000SP and is the answer not in the manual?

Questions and answers

William John Carter
February 28, 2025

I have no display information on the inverter, just a blank screen

1 comments:
Mr. Anderson
February 28, 2025

The Mass Energy ME 3000SP inverter may not display information due to the following reasons:

1. Power Supply Issue – The inverter may not be turned on, or the DC & AC breakers may be off. Ensure the inverter is powered.
2. Connection Issue – If the CT connection has been changed, the setup procedure must be repeated.
3. Firmware Update Issue – If a firmware update fails, the inverter may not function properly. Ensure the update completes successfully and restart the inverter.
4. Screen Failure – If the LCD screen does not turn on after power is supplied, there might be a hardware malfunction.

Check power connections, restart the inverter, and verify successful firmware updates to resolve the issue.