GENERAL
The NOTIFIER NBG-12LX is a state-of-the-art, dual-ac-
tion (i.e., requires two motions to activate the station) pull
station that includes an addressable interface for any
NOTIFIER intelligent control panel. Because the NBG-12LX
is addressable, the control panel can display the exact
location of the activated manual station. This leads fire
personnel quickly to the location of the alarm.
FEATURES
• Maintenance personnel can open station without causing
an alarm condition.
• Built-in bicolor LED, which is visible through the handle of
the station, flashes in normal operation and latches steady
red when in alarm.
• Handle latches in down position and the word "ACTI-
VATED" appears to clearly indicate the station has been
operated.
• Captive screw terminals wire-ready for easy connection
to SLC loop (accepts up to 12 AWG/3.1 mm² wire).
• Semi-flush, mounts to a standard single-gang (2.125"
[5.3975 cm] minimum depth), double-gang, or 4" (10.16
cm) square electrical box.
• Smooth dual-action design.
• Within ADA 5 lb. pull force.
• Highly visible.
• Attractive shape and textured finish.
• Key reset.
• Includes Braille text on station handle.
• Optional trim ring (BG-TR).
• Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
• Up to 99 NBG-12LX stations per loop on classic protocol
systems.
• Up to 159 NBG-12LX stations per loop on FlashScan®
protocol systems.
• Dual-color LED blinks green to indicate normal on
FlashScan® systems.
CONSTRUCTION
Shell, door, and handle are molded of durable LEXAN®
(or polycarbonate equivalent) with a textured finish.
OPERATION
Pushing in, then pulling down on the handle causes it to
latch in the down/activated position. Once latched, the
word "ACTIVATED" (in bright yellow) appears at the top of
the handle, while a portion of the handle protrudes from
FlashScan® and NOTIFIER® are registered trademarks of Hon-
eywell International INC. LEXAN® is a registered trademark of
GE Plastics, a subsidiary of General Electric Company.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
June 13, 2005
NBG
NBG
NBG
NBG
NBG-12LX
Addressable Manual Pull Station
Addressable Manual Pull Station
Addressable Manual Pull Station
Addressable Manual Pull Station
Addressable Manual Pull Station
with FlashScan®
with FlashScan®
with FlashScan®
with FlashScan®
with FlashScan®
Section: Intelligent/Addressable Devices
Patented, U.S. Patent No. D428,351; 6,380,846
U.S. Patent Pending: 09/686,286
S692
U.S. Coast Guard
161.002/23/3
(AFP-200)
BSMI
CI313066760047
The NBG-12LX
Addressable Manual Pull Station
the bottom of the station. To reset the station, simply un-
lock the station with the key and pull the door open. This
action resets the handle; closing the door automatically
resets the switch.
Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow address set-
tings (1 – 159 on FlashScan® systems, 1 – 99 on CLIP
systems).
DN-6726 • H-240
-12LX
-12LX
-12LX
-12LX
California
MEA
State Fire
Marshal
67-02-E
7150-0028:199
93/60141 (E3)
02/6007
DN-6726 • 06/13/05 — Page 1 of 2
Need help?
Do you have a question about the NBG-12LX and is the answer not in the manual?
Questions and answers