5.1.8 Error Codes

The error codes are as follows.
For GT01, GT11 and GT21
Error code
ER00
BCC error
ER01
Format error
ER02
NOT supported error
ER03
Address error
Receive buffer
ER04
overflow
ER05
Requested overflow
ER06
Data error
Data write inhibit
ER07
error
For GT02, GT02L, GT05, GT12, GT32 and GT32-E
Error code
**0000
BCC error
**0001
Format error
**0002
NOT supported error
**0003
Address error
Receive buffer
**0004
overflow
**0005
Requested overflow
**0006
Data error
Data write inhibit
**0007
error
Note) These are the error codes related to communicaiton.

5.1.9 Restrictions

Allowable bytes sent and received
The allowable number of bytes to be sent and received in the GT is up to 512 bytes (including CR).
Therefore, a command or response of which size is more than 513 bytes cannot be sent from the
external device.
Restrictions on transmitting messages
In the two-way 2 mode, a message will not be sent if the following changes occur in the bit device. When
readout is necessary, use the readout command.
Number of displayed screen
BAT bit
Data input in progress flag
BAT LOW flag
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Error name
The value of BCC may be incorrect. Check if there is no
calculation mistake.
A command format may be incorrect. Check if it is correct.
A command used is not supported with the version of the GT.
Upgrade the version of the GT, or use another command.
The address specified does not exist in the GT. Check the
address of the transmitted command.
The sent command exceeds the receivable number of bytes.
Check the number of bytes of the sent command.
The sent readout command exceeds the number of bytes that
can send back. Check the number of the read words.
The communication condition for the GT may be unmatched
with the condition for a destination device. Check the
communication conditions.
A command for the address that writingn is not available was
sent. Check the address of the sent command.
Error name
The value of BCC may be incorrect. Check if there is no
calculation mistake.
A command format may be incorrect. Check if it is correct.
A command used is not supported with the version of the GT.
Upgrade the version of the GT, or use another command.
The address specified does not exist in the GT. Check the
address of the transmitted command.
The sent command exceeds the receivable number of bytes.
Check the number of bytes of the sent command.
The sent readout command exceeds the number of bytes that
can send back. Check the number of the read words.
The communication condition for the GT may be unmatched
with the condition for a destination device. Check the
communication conditions.
A command for the address that writingn is not available was
sent. Check the address of the sent command.
Measures
Measures