Setting
The table below shows the setting elements necessary for the thermal overload protection and
their setting ranges.
Element
Range
THM
2.0 – 10.0 A
(0.40 – 2.00 A)(*)
THMIP
0.0 – 5.0 A
(0.00 – 1.00 A)(*)
TTHM
0.5 - 300.0 min
THMA
50 – 99 %
[THMT]
Off / On
[THMAL]
Off / On
(*) Current values shown in the parenthesis are in the case of a 1 A rating. Other current
values are in the case of a 5 A rating.
Note: THMIP sets a minimum level of previous load current to be used by the thermal element,
and is typically used when testing the element. For the majority of applications, THMIP
should be set to its default value of zero, in which case the previous load current, Ip, is
calculated internally by the thermal model, providing memory of conditions occurring
before an overload.
Step
Default
Remarks
0.1 A
5.0 A
Thermal overload setting.
(0.01 A)
(1.00 A)
(THM = I
0.1 A
0.0 A
Previous load current
(0.01 A)
(0.00 A)
0.1 min
10.0 min
Thermal time constant
1 %
80 %
Thermal alarm setting.
(Percentage of THM setting.)
Off
Thermal OL enable
Off
Thermal alarm enable
 92 
6 F 2 S 0 8 5 0
: allowable overload current)