Toshiba GRL100-701B Instruction Manual page 58

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

ZIC
0.00 - 5.00 A
( 0.00 - 1.00 A
Vn
100 - 120
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
Setting of phase selection element
Phase selection is required only for faults on the protected line. Therefore, impedance reach
setting UVCZ is set to 120% of the positive-sequence impedance of the protected line. Impedance
angle setting UVC θ is set the same as the protected line angle.
Undervoltage setting UVCV is set higher than the estimated maximum fault voltage at the fault
point for a single-phase earth fault.
0.01 A
0.0 0
0.01 A
0.00 A) (*)
1 V
110 V
 57 
6 F 2 S 0 8 5 0
Charging current setting
Rated line voltage