1 4 | Bosch ZS Series Zone Sensors R1
The following is a description of the available alarm codes on the "Current Alarm
Condition/Code" screen(Rnet tag 1300):
Alarm Code
Description
0
System Normal - No Alarms
1
UPM code for High Pressure on circuit #1 fault
2
UPM code for Low Pressure on circuit #1 fault
3
UPM code for High Pressure on circuit #2 fault
4
UPM code for Low Pressure on circuit #2 fault
5
UPM code for Water Coil Freeze on circuit #1 fault
6
UPM code for High Condensate fault
7
UPM code for Brownout fault
8
UPM code for Air Coil Freeze on circuit #1 fault
9
UPM code for Water Coil Freeze on circuit #2 fault
10
UPM code for Air Coil Freeze on circuit #2 fault
20
FHP560 Input/Output in MANUAL lock position
Wired Sensor Failure for ZS Sensor, DAT Sensor, LWT
30
Sensor, Humidity Sensor or CO2 Sensor
High or Low Leaving Water Temperature (LWT)
40
Condition
50
High or Low Zone Temperature Condition
High or Low Discharge Air Temperature (DAT)
60
Condition
70
Filter or Compressor Runtime Alert
80
High or Low Zone Humidity Condition
90
High Zone CO2 Condition
100
Diff erential Pressure Switch (DPS) Open Condition
Table 13
Data subject to change
If an alarm is generated for any of the below conditions, pressing the info button will
show a Alarm Code Description short "active text" and Rnet tag:
Alarm Display Information
Filter Change Status
Low Zone Temp Alarm
High Zone CO2 Alarm
High Zone Humidity Alarm
Low Zone Humidity Alarm
Compressor1 Runtime Alarm
Compressor2 Runtime Alarm
High Discharge Air Temp Alarm
Low Discharge Air Temp Alarm
Manual I/O Lock Alarm
Wired Sensor Failure Alarm
High Leaving Water Temp Alarm
Low Leaving Water Temp Alarm
High Zone Temp Alarm
DPS Lock Alarm
UPM General High Pressure Alarm
UPM General Low Pressure Alarm
UPM General Freezestat Alarm
UPM Brownout BRN Alarm
UPM Condensate COND Alarm
Table 14
Installation & OperationManual
Rnet Tag Number
Active Text
1027
FILTER
1026
Lo ZTp
1043
HI CO2
1044
HI RH
1045
Lo RH
1050
C1 RT
1051
C2 RT
1028
Hi DAT
1029
Lo DAT
1116
IO OVRD
1115
SEN Conn
1113
Load H2O
1114
Load H2O
1025
Hi ZTp
1117
dPS
1118
HP Fault
1119
LP Fault
1120
Frz stat
1109
Brn Out
1108
Hi Cond
02.2018 | Bosch Thermotechnology Corp.