Scaling low limit setting
• Sets scaling low limit value.
• Available only for DC input type
• Input range low limit value to scaling high limit value
(The placement of the decimal point follows the selection)
Decimal point place selection
• Selects decimal point place.
• Available only for DC input
No decimal point:
2 digits after decimal point:
PV filter time constant setting
• Sets PV filter time constant.
(If the value is set too large, it affects control result due to the delay of response)
• 0.0 to 10.0 seconds
OUT1 high limit setting
• Sets the high limit value of OUT1.
• Not available for ON/OFF action
• OUT1 low limit value to 105%
(Setting higher than 100% is effective to DC current output type)
OUT1 low limit setting
• Sets the low limit value of OUT1.
• Not available for ON/OFF action.
• –5% to OUT1 high limit value
(Setting less than 0% is effective to DC current output type)
OUT1 ON/OFF action hysteresis setting
• Sets ON/OFF action hysteresis for OUT1.
• Available only when the control action is ON/OFF action
• 0.1 to 100.0
For DC input, 1 to 1000 (The placement of the decimal point follows the selection)
OUT2 action mode selection
• Selects OUT2 action from air cooling, oil cooling and water cooling.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control (option) is not added.
• Air cooling:
OUT2 high limit setting
• Sets the high limit value of OUT2.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control (option) is not added.
• OUT2 low limit value to 105%
(Setting higher than 100% is effective to DC current output type)
OUT2 low limit setting
• Sets the low limit value of OUT2.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control (option) is not added.
• –5% to OUT2 high limit value
(Setting less than 0% is effective to DC current output type)
Overlap band/Dead band setting
• Sets the overlap band or dead band for OUT1 and OUT2.
+ set value: Dead band
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control (option) is not added.
• –100.0 to 100.0
For DC input, –1000 to 1000 (The placement of the decimal point follows the selection)
OUT2 ON/OFF action hysteresis setting
• Sets ON/OFF action hysteresis for OUT2.
• Available only when Heating/Cooling control (option) is added.
• 0.1 to 100.0
For DC input, 1 to 1000 (The placement of the decimal point follows the selection)
A1 type selection
• Selects an A1 type.
No alarm action
High limit alarm
Low limit alarm
High/Low limits alarm
High/Low limit range alarm:
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
( )
, oil cooling:
, water cooling:
– set value: Overlap band
( )
( ),
:
:
:
:
1 digit after decimal point:
3 digits after decimal point:
Process high alarm
Process low alarm
High limit alarm with standby
Low limit alarm with standby
High/Low limits alarm with standby :
–1999
No decimal point
0.0 seconds
100%
0%
1.0
Air cooling
100%
0%
0.0
1.0
No alarm action
:
:
:
: