Figure 31. Install the Bezel
3.
Push the bezel into place until it attaches to the expansion enclosure.
4.
Release the latches on the front on the bezel.
5.
If the bezel has key lock, lock the bezel with the key.

Pre-Replacement Procedures

Perform the procedures described in this chapter before replacing a component of the SCv360 expansion enclosure.

Send Diagnostic Data Using Dell SupportAssist

Before replacing components, use Dell SupportAssist to send diagnostic data to Dell Technical Support.
1.
Use Dell Storage Manager to connect to the Storage Center.
2.
In the Summary tab, click Send SupportAssist Information Now, which is located under SupportAssist Actions in the Status
pane.
The Send SupportAssist Information Now dialog box opens.
3.
Select Storage Center Configuration and Detailed Logs.
4.
Click OK.

Change the Operation Mode of the Storage Center to Maintenance

Change the operation mode of the Storage Center to Maintenance before replacing components.
1.
Use Dell Storage Manager to connect to the Storage Center.
2.
In the Summary tab, click Edit Settings. The Edit Storage Center Settings dialog box opens.
3.
Click the General tab.
4.
In the Operation Mode field select Maintenance. Selecting Maintenance isolates alerts from those that would occur during
normal operation.
5.
Click OK.
34
Replacing SCv360 Expansion Enclosure Components