M- 180.2- AM6000- ENG Do cu ment : 10/1999 Is sue Rev. : Analog Fire Alarm AM-6000 Con trol Panel Installation Manual NO TI FIER ITA LIA A Di vi sion of Pitt way Corporation...
The 220 VAC Power Supply Line Main Power Supply current draw calculation Alarm condition current load Battery capacity calculation APPENDIX: AM-6000 POWER SUPPLY (Refer to note 1) Note 1: Ad ded in this new revision In dex.VP In stal la tion Ma nual Doc.
AM-6000 EXPLODED VIEW CVCV-0117 Power Supply Cable BPS600 Board for 230 V Mains Wiring AVPS 6 Board for 3 A Aux. Power Supply CVCV-0124 Flat Cable complete of transformer DIA 6 Front Board CVCV-0123 Flat Cable BE 600 A Main Board...
55 mm 1 openable hole - 28.0 mm. dia. > bottom side Openable Holes 28.0 mm dia. > 2 bottom side > 2 top side 30 mm Dust preventer door AM-6000-60001.VP Installation Manual Page 2 Doc. M-180.2-AM6000-ENG Rev. B.1 NOTIFIER ITALIA...
- Insert the chassis on the proper hinges ( ). Then push the chassis inward toward the bottom of the cabinet. A click will confirm the correct seat of the chassis ( Page 3 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
Connector for BPS 600 PSU board interconnection Start-up from battery only. (Execute a short circuit between the two PIN) Connector for DIA 6 front board interconnection Connector for LIB 600 expansion board interconnection Page 5 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
RS 485 LIN - (RETURN) ) these two outputs CANNOT operate simultaneously. The operator must select the Type of Connection to NOTE: employ, from the Control Panel Main Programming Menu (refer to AM-6000 Programming Manual). SERIAL PRINTER CONNECTIONS SIGNAL DEFINITION...
Use to drive loads in DC only. Alarm is activated if a detector of line 1-4 is in ALARM condition. Trouble is activated if a detector of line 1-4 is in TROUBLE condition. Page 7 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
Battery-Charger Fuse 3,15 A 230 V Mains Fuse 5 A ATTENZIONE ATTENZIONE 230 V 230 V Auxiliary Power Supply Fuse - 4 A Main Power Supply Fuse - 4A AM-6000-60001.VP Installation Manual Page 8 Doc. M-180.2-AM6000-ENG Rev. B.1 NOTIFIER ITALIA...
Any external device powered by the control panel or by supervised line must be connected to a diode, as showed in the diagram. 47 K End-of-line resistor + 24 V USER Page 9 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
Page 12
Typical LOOP line (style 6) B501 Detector Base To employ with intelligent detectors Separated branches to other Loop device SHIELD - Connector CN1 > BE 600 A BOARD > LIB 600 BOARD AM-6000-60001.VP Installation Manual Page 10 Doc. M-180.2-AM6000-ENG Rev. B.1 NOTIFIER ITALIA...
Program Eprom Connector for earth link. > To the BE 600 A Main Board Interfacing connector to : > BE 600 A Main Board > LIB 600 Expansion Board Page 11 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
Use to drive loads in DC only. Alarm is activated if a detector of line 1-4 is in ALARM condition. Trouble is activated if a detector of line 1-4 is in TROUBLE condition. AM-6000-60001.VP Installation Manual Page 12 Doc. M-180.2-AM6000-ENG Rev.
Auxiliary power supply output Connector for earth link > to the BE 600 A Main Board Interfacing connector to the BE 600 A Main Board LED indicating the aux. power supply operating Page 13 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
99 addressable pull stations, and control and monitor modules. The AM-6000 is able to support a maximum of three LIB-600 boards for a total of 16 lines (4 lines on the main board and 12 on the 3 LIB-600 boards).
(INVALID REPLY from Section 2 Points). This circuit is a variation of an NFPA Style 6 Signaling Line Circuit, therefore no T-Tapping or branching is allowed. The ratings and characteristics are the same as for the Style 6 circuit. AM-6000-60001.VP Installation Manual Page 16 Doc.
The measurement must be made by disconnecting Channels A and B at the control panel, shorting the two leads of Chan- nel A together, and metering the two leads of Channel B. Page 17 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
Page 20
Channel B Channel A SHIELD The total of all branches on Channel B exceed 3000 meters. CANNOT The total of all branches on Channel A exceed 3000 meters. CANNOT AM-6000-60001.VP Installation Manual Page 18 Doc. M-180.2-AM6000-ENG Rev. B.1 NOTIFIER ITALIA...
Page 21
When the detector/module line is connected, the LIB output voltage (terminal 1 - 3) must be 24 VDC without device polling (no Points programmed). A voltage lower than 14 VDC, indicates a polarity inversion on at least one device. Page 19 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
Page 22
NOTE EARTH PLANT The earth plant must be performed according to the CEI and ISPLES rules. The resistance CANNOT exceed 10 Ohm (to be measured at the well with disconnected mains). AM-6000-60001.VP Installation Manual Page 20 Doc. M-180.2-AM6000-ENG Rev. B.1...
For Style 6 field wirings, connect ONLY ONE END of the shield to the negative side of Channel A. Maintain the continuity of the shield wire throughout the loop, BUT DO NOT connect to any devices. Page 21 Installation Manual AM-6000-60001.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
NOTE : for wiring of maximum 15 meters use 232 serial line (terminals 4-5-6) for wiring exceeding 15 meters use 485 serial line with IT-485 interface (terminals 7-11) JUMPER ON RS-485 2-WIRE OPEN LINE ON RS-422 4-WIRE (OUTWARD/RETURN) CLOSED LINE (LOOP) JUMPER AM-6000-60001.VP Installation Manual Page 22 Doc. M-180.2-AM6000-ENG Rev. B.1 NOTIFIER ITALIA...
Number of Multiply Current in Total Current/ Type Devices Amps (each) Type Main Power Supply AVPS-6 ) max 1 0,45 Total amount of current required for 220 VAC circuit Amps Page 23 Installation Manual AM-6000-60003.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
» NOTE: the total of stand-by load obtained in table 2 CANNOT exceed the following values: - 3.0 Amps for Main Power Supply - 3.0 Amps for Auxiliary Power Supply (AVPS-6) AM-6000-60003.VP Installation Manual Page 24 Doc. M-180.2-AM6000-ENG Rev. B.1...
Amps alarm condition » N.B. : If the total load obtained exceeds 3.0 Amps (provided by the power supply), the batteries will supply the current to support alarm conditions. Page 25 Installation Manual AM-6000-60003.VP NOTIFIER ITALIA Rev. B.1 Doc. M-180.2-AM6000-ENG...
Total battery load Alarm time required in Alarm (see Table 3) (for 5/60 minutes enter 0.084) Total current needed Multiply by the derating factor (1.2) Battery capacity in Amps/hour required AM-6000-60003.VP Installation Manual Page 26 Doc. M-180.2-AM6000-ENG Rev. B.1 NOTIFIER ITALIA...
Page 29
AP PEN DIX: AM- 6000 POWER SUP PLY BLOCK DIAGRAM In put and Out put • Mains in put In put vol ta ge 230 Vac with 5A pro tec tion fuse • Mains Tran sfor mer N° 2 39 Vac 3A au xi lia ri es The first au xi lia ry powers the rec ti fi ca tion cir cuit of the main power sup ply with a 4A pro tec tion fuse.
Page 30
• Power sup ply troub le. Any power sup ply troub le ge ne ra te a sy stem troub le and a ge ne ral troub le si gnal; the ge ne ral troub le re lay is de- ac ti va ted and the buz zer so und. •...
Page 31
• Bat te ry char ger fai lu re or over load. It in di ca tes that the bat te ry char ger out put vol ta ge is less than 21 Vdc • Di scon nected bat te ry or bat te ry fuse troub le. A pe rio di cal test is exe cu ted only if the 220 mains is con nected (vol ta ge >= 170 VAC) and the main vol ta ge >= 24,5 VDC.
Page 32
M- 180.2- AM6000- ENG Do cu ment : 10/1999 Is sue Rev. : All rights re ser ved. All spe ci fi ca tions are sub ject to chan ge wit hout no ti ce. De li ve ry ti mes de pend on pro duct avai la bi li ty. NO TI FIER ITA LIA S.r.l.