B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 13 of 61)
ADDR
REGISTER NAME
3751
PTP Domain Number
3752
PTP VLAN Priority
3753
PTP VLAN ID
3754
Undefined (2 items)
PTP Port Configuration (Read/Write Setting) (3 modules)
3756
PTP Port x Function
3757
Port x Path Delay Adder
3758
Port x Path Delay Asymmetry
3759
...Repeated for module number 2
375C
...Repeated for module number 3
B
Real Time Clock Synchronizing Actuals (Read Only)
375F
RTC Sync Source
3760
PTP GrandMaster ID
3764
Real Time Clock Accuracy
3766
PTP Port 1 State (3 items)
3769
RTC Offset
376B
PTP - IRIG-B Delta
Real Time Clock Synchronizing FlexAnalogs (Read Only)
376D
PTP - IRIG-B Delta FlexAnalog
Capacitor control actual values (read only)
3780
Capacitor control 1 discharge time
3781
Capacitor control 2 discharge time
3782
Capacitor control 3 discharge time
3783
Capacitor control 4 discharge time
Field Units (Read/Write Setting) (8 modules)
3800
Field Unit 1 ID
3806
Field Unit 1 Function
3807
Field Unit 1 Type
3808
Field Unit 1 Serial Number
380E
Field Unit 1 Port
380F
...Repeated for Field Unit 2
381E
...Repeated for Filed Unit 3
382D
...Repeated for Filed Unit 4
383C
...Repeated for Filed Unit 5
384B
...Repeated for Filed Unit 6
385A
...Repeated for Filed Unit 7
3869
...Repeated for Filed Unit 8
Field Unit Process Card Ports (Read/Write Setting)
3878
Field Unit 1 Process Card Port
3879
Field Unit 2 Process Card Port
387A
Field Unit3 Process Card Port
387B
Field Unit 4 Process Card Port
387C
Field Unit 5 Process Card Port
387D
Field Unit 6 Process Card Port
387E
Field Unit 7 Process Card Port
387F
Field Unit 8 Process Card Port
Field Unit CT VT Settings (Read/Write Setting) (6 modules)
3890
Remote Phase CT x Origin 1
3891
Remote Phase CT x Origin 2
3892
Remote Ground CT x Origin 1
3893
Remote Ground CT x Origin 2
3894
AC Bank Redundancy Type
3895
Remote Phase CT 1 Primary
B-20
0 to 4095
0 to 60000
-1000 to 1000
0 to 999999999
0 to 999999999
-500000000 to 500000000
-262143 to 262143
0 to 3600
0 to 3600
0 to 3600
0 to 3600
1 to 65000
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
0 to 255
---
1
0 to 7
---
1
---
1
0 to 1
---
1
0 to 1
---
1
ns
1
ns
1
0 to 5
---
1
0 to 100
--
1
ns
1
0 to 4
--
1
ns
1
ns
1
---
1
s
1
s
1
s
1
s
1
0 to 1
---
1
0 to 1
---
1
0 to 3
---
1
0 to1
---
1
1 to 4
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 16
---
1
0 to 16
---
1
0 to 16
---
1
0 to 16
---
1
0 to 2
---
1
---
1
APPENDIX B
FORMAT
DEFAULT
F001
0
F001
4
F001
0
F001
0
F102
0 (Disabled)
F001
0
F002
0
F624
0 (none)
F073
0
F003
0
F625
0 (Disabled)
F004
0
F004
0
F004
0
F001
0
F001
0
F001
0
F001
0
F205
"U1"
F102
0 (Disabled)
F243
0 (CC-05)
F205
"000000000000"
F001
1
F244
6 (H1a)
F244
4 (H2a)
F244
2 (H3a)
F244
0 (H4a)
F244
7 (H1b)
F244
5 (H2b)
F244
3 (H3b)
F244
1 (H4b)
F247
0 (none)
F247
0 (none)
F248
0 (none))
F248
0 (none)
F261
1 (Dependability
Biased)
F001
1
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents