Error Type
Error No.
(FS on, # of
(FS off, # of
FN pulses)
FN pulses)
2
Configuration Errors on Profibus (CHK_CFG telegram)
GFK-1911B
Chapter 6 Diagnostics
Meaning
1
Not all VersaPoint modules
that are present have been
configured.
2
More VersaPoint modules
have been configured than
are present.
3
The first byte of the special
identification format for the
VersaPoint module is faulty.
4
Not enough bytes of the
special identification format
for the last VersaPoint
module have been
configured
5
The sum of the configured
process data for inputs and
outputs of the VersaPoint
station is greater than 184
bytes.
Remedy
Add extra modules to the
configuration.
Remove the extra modules
from your configuration or add
the missing modules.
Determine the exact error
location, using the device-
specific diagnostics in your
control system.
Check the identification
format.
Determine the exact error
location using the device-
specific diagnostics in your
control system.
Combine several VersaPoint
modules in the configuration,
so that the process data is
compressed (resulting in fewer
empty bits).
6
6-5