【Ex.1】 IS.MD=TSV, IS5=OFF
IS1H = 65
IS1 Zone
IS1H = 0
1 SEG
2 SEG
3 SEG
4 SEG
5 SEG
IS4H = 60
IS4 Zone
IS4L = 57
IS3H = 55
1SV = 50 2SV = 50
IS3 Zone
IS3L = 45
IS2H = 35
IS2 Zone
IS2L = 25
1SEG
2SEG
IS1
ON
ON
IS2
OFF
OFF
IS3
ON
ON
IS4
OFF
OFF
IS5
OFF
OFF
• IS1: 1SV(50) is in IS1 Zone(0〜65)  ON
• IS2: 1SV(50) is not in IS2 Zone(25〜35)  OFF
• IS3: 1SV(50) in in IS3 Zone(45〜55)  ON
• IS4: 1SV(50) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
• IS1: 2SV(50) is in IS1 Zone (0〜65)  ON
• IS2: 2SV(50) is not in IS2 Zone (25〜35)  OFF
• IS3: 2SV(50) is in IS3 Zone(45〜55)  ON
• IS4: 2SV(50) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
• IS1: 3SV(70) is not in IS1 Zone(0〜65)  OFF
• IS2: 3SV(70) is not in IS2 Zone(25〜35)  OFF
• IS3: 3SV(70) is not in IS3 Zone(45〜55)  OFF
• IS4: 3SV(70) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
• IS1: 4SV(70) is not in IS1 Zone(0〜65)  OFF
• IS2: 4SV(70) is not in IS2 Zone(25〜35)  OFF
• IS3: 4SV(70) is not in IS3 Zone(45〜55)  OFF
• IS4: 4SV(70) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
• IS1: 5SV(30) is in IS1 Zone(0〜65)  ON
• IS2: 5SV(30) is in IS2 Zone(25〜35)  ON
• IS3: 5SV(30) is not in IS3 Zone(45〜55)  OFF
• IS4: 5SV(30) is not in IS4 Zone(57〜60)  OFF
• IS5: IS5 has no value  OFF
3SV = 70
4SV = 70
3SEG
4SEG
5SEG
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
54
5SV = 30