CHAPTER 5: SETTINGS
Operand type
Operand syntax
ELEMENT:
PUTT OP
PUTT
PUTT TX1
(Permissive
PUTT TX2
underreach transfer
PUTT TX3
trip)
PUTT TX4
PUTT TRIP A
PUTT TRIP B
PUTT TRIP C
PUTT TRIP 3P
ELEMENT:
RESTD GND FT1 PKP
Restricted ground
RESTD GND FT1 OP
fault
RESTD GND FT1 DPO
RESTD GND FT2 to 4
ELEMENT:
SELECTOR 1 POS Y
Selector switch
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 2
ELEMENT:
SETTING GROUP ACT 1
Setting group
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
ELEMENT:
SRC1 50DD OP
Disturbance detector
SRC2 50DD OP
SRC3 50DD OP
SRC4 50DD OP
ELEMENT:
SRC1 VT FF OP
VTFF (Voltage
SRC1 VT FF DPO
transformer fuse
SRC1 VT FF VOL LOSS
failure)
SRC1 VT FF ALARM
SRC1 VT NEU WIRE OPEN
SRC2 VT FUSE FAIL to SRC4
ELEMENT:
STUB BUS OP
Stub bus
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Operand description
Permissive under-reaching transfer trip has operated
Permissive under-reaching transfer trip asserts transmit bit number 1
Permissive under-reaching transfer trip asserts transmit bit number 2
Permissive under-reaching transfer trip asserts transmit bit number 3
Permissive under-reaching transfer trip asserts transmit bit number 4
Permissive under-reaching transfer trip has operated to trip phase A
Permissive under-reaching transfer trip has operated to trip phase B
Permissive under-reaching transfer trip has operated to trip phase C
Permissive under-reaching transfer trip has operated to trip all three phases
Restricted ground fault 1 has picked up
Restricted ground fault 1 has operated
Restricted ground fault 1 has dropped out
Same set of operands as shown for RESTD GND FT1
Selector switch 1 is in Position Y (mutually exclusive operands)
First bit of the 3-bit word encoding position of selector 1
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
Position of selector 1 has been pre-selected but not acknowledged
Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
Same set of operands as shown for SELECTOR 1
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
Source 1 disturbance detector has operated
Source 2 disturbance detector has operated
Source 3 disturbance detector has operated
Source 4 disturbance detector has operated
Source 1 VT fuse failure detector has operated
Source 1 VT fuse failure detector has dropped out
Source 1 has lost voltage signals (V2 below 10% and V1 below 5% of nominal)
Source 1 has triggered a VT fuse failure alarm
Source 1 VT neutral wire open detected. When the VT is connected in Delta,
do not enable this function because there is no neutral wire for Delta
connected VT.
Same set of operands as shown for SRC1 VT FF
Stub bus is operated
FLEXLOGIC
5
5-179