TROUBLESHOOTING
SYMPTOM
No lights are on.
The unit seems
completely dead.
Red light is
blinking (on initial
power up).
Red light is
blinking (after the
motor has been
previously
running).
Red light is
blinking in this
pattern.
Red light is on
steady.
Green light blinks
and motor is not
running.
Green light is on
steady, but motor
does not start.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
LIGHT
PATTERN
Measure the three line-to-line voltages. If
any of the voltages are below 150 VAC, the
MotorSaver
N / A
to operate its internal electronics. This
may occur on a single-phased system. If
the voltages are correct, call SymCom at
1-800-843-8848 or 1-605-348-5580.
Turn off the three-phase power. Swap any
two leads powering the MotorSaver
L2, or L3). There is a 50-50 chance of
RED
connecting L1, L2, and L3 correctly the fi rst
time. Re-apply the three-phase power.
The incoming lines have been reverse
phased. The MotorSaver
the motor from running backwards. Correct
RED
the phase sequence.
The voltage is unbalanced or
single-phased. Measure the incoming line
voltages and calculate the % unbalance. If
the voltage unbalance does not exceed the
% unbalance reset value, call SymCom at
1-800-843-8848 or 1-605-348-5580.
The voltage is out of tolerance. Measure
the three line-to-line voltages. Calculate
the average of the three voltages. If the
average is 7% above or below the nominal
voltage as selected by the LINE VOLTAGE
ADJUST, the MotorSaver
properly. If the voltage is within ±7% of the
selected line voltage, call SymCom at
1-800-843-8848 or 1-605-348-5580.
The MotorSaver
The MotorSaver
other control devices are allowing the
motor to start. Check control circuit for
loose wires or malfunctioning switches.
SOLUTION
does not have enough power
is functioning
is in restart delay.
is in run mode. Ensure
(L1,
is preventing