FLEXLOGIC
Operand type
ELEMENT:
Trip output
ELEMENT:
Trip bus
FIXED OPERANDS
INPUTS/OUTPUTS:
Contact inputs
INPUTS/OUTPUTS:
Contact outputs,
current
5
(from detector on
form-A output only)
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
INPUTS/OUTPUTS:
Direct inputs
INPUTS/OUTPUTS:
RxGOOSE DPS
INPUTS/OUTPUTS:
RxGOOSE Booleans
INPUTS/OUTPUTS:
Virtual inputs
INPUTS/OUTPUTS:
Virtual outputs
5-196
Operand syntax
TRIP 3-POLE
TRIP 1-POLE
TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP AR INIT 3-POLE
TRIP FORCE 3-POLE
TRIP OUTPUT OP
TRIP Z2PH TMR INIT
TRIP Z2GR TMR INIT
TRIP BUS 1 PKP
TRIP BUS 1 OP
TRIP BUS 2 to 6
Off
On
Cont Ip 1 On
Cont Ip 2 On
↓
Cont Ip 1 Off
Cont Ip 2 Off
↓
Cont Ip 120 On
Cont Ip 120 Off
Cont Op 1
IOn
Cont Op 2
IOn
↓
Cont Op 72
IOn
Cont Op 1 VOn
Cont Op 2
VOn
↓
Cont Op 72
VOn
Cont Op 1
VOff
Cont Op 2
VOff
↓
Cont Op 72
VOff
DIRECT INPUT 1 On
↓
DIRECT INPUT 32 On
RxG DPS 1 BAD
RxG DPS 1 INTERM
RxG DPS 1 OFF
RxG DPS 1 ON
RxG DPS 2 to 5
RxG Bool 1 On
RxG Bool 2 On
RxG Bool 3 On
↓
RxG Bool 256 On
Virt Ip 1 On
Virt Ip 2 On
Virt Ip 3 On
↓
Virt Ip 64 On
Virt Op 1
On
Virt Op 2
On
Virt Op 3
On
↓
Virt Op 96
On
Operand description
Trip all three breaker poles
A single-pole trip-and-reclose operation is initiated
Trip breaker pole A, initiate phase A breaker fail and reclose
Trip breaker pole B, initiate phase B breaker fail and reclose
Trip breaker pole C, initiate phase C breaker fail and reclose
Initiate a three-pole reclose
Three-pole trip must be initiated
Any trip is initiated by the trip output
Phase distance zone 2 timer is initiated by the trip output
Ground distance zone 2 timer is initiated by the trip output
Asserted when the trip bus 1 element picks up
Asserted when the trip bus 1 element operates
Same set of operands as shown for TRIP BUS 1
Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
Flag is set, logic=1
↓
Flag is set, logic=1
Asserted while the RxGOOSE double-point status input is in the bad state
Asserted while the RxGOOSE double-point status input is in the intermediate
state
Asserted while the RxGOOSE double-point status input is off
Asserted while the RxGOOSE double-point status input is on
Same set of operands as per RxG DPS 1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS