ABB PQFM Instruction Manual page 224

Power quality filter
Table of Contents

Advertisement

(Voltage group V1)
Unit rating: 100 A
Network voltage: 208 V £ Ue £ 480 V
(Voltage group V1)
Unit rating: 130 A
Network voltage: 208 V £ Ue £ 480 V
(Voltage group V1)
Unit rating: 150 A
Color
Mechanical installation
Cable entry method
CT requirements
Airflow requirements
Network voltage characteristics
Network voltage ratings
Network voltage tolerance
Network frequency
Network frequency tolerance
Maximum rate of frequency variation
Maximum phase jump of network
voltage
Network voltage distortion
Minimum network fault level
Voltage notch limits
224 Technical specifications ç Manual Power Quality Filter PQFM
IP00: 180 kg
IP21: 260 kg
IP00: 180 kg
IP21: 260 kg
IP00: 180 kg
RAL 7035 (light gray)
Floor fixation, lifting lugs provided.
Plate version: bottom or top cable entry
Cubicle version: bottom cable entry, optional top cable
entry cable feed though
Common/top cable entry cubicle on request
3 CTs are required (Class 1.0 or better)
Filter burden: 5 VA for upto 8 units
15 VA burden for up to 30 m of 2.5 mm² cable
5 A secondary rating
CTs must be installed in closed loop configuration
A minimum of 700 m³/h cooling air has to be supplied to
each cubicle.
208 V £ Ue £ 480 V between phases (Voltage group V1)
480 V < Ue £ 690 V between phases (Voltage group V2), CE
versions
480 V < Ue £ 600 V between phases (Voltage group V2),
cULus versions
+/- 10 %
50 Hz or 60 Hz
+/- 5 %
20%/s
30°
Maximum 20% phase to phase
1 MVA
According to IEEE519-1992, dedicated systems category
Notch depth: £ 50%
Notch area: £ 76*U V*µs
Connection requirement:
z
(%) ³ S
/S
* z
load
load
trafo
where: S
:
Notch producing load power
load
(%)
trafo

Advertisement

Table of Contents
loading

Table of Contents