9. IP ADDRESS CONFIGURATION

9.1. PREPARING NET VISION

Once the UPS power is on and NET VISION has been installed in the COM-Slot and connected
to the Network, the Net Vision's IP address must be programmed.

9.2. DEFAULT IP ADDRESS

If a DHCP server is available on the same Network as NET VISION, the NET VISION will request
a valid IP address from the server. If the DHCP server is not available, NET VISION switches to
the following default IP address: 192.168.7.18
IPv6 is not activated by default. The default IP address is set to IPv4 format

9.3. NET VISION ACCESS

When the Net Vision has a valid IP address, open the web browser and enter the IP address set
manually or given by the DHCP server. The IP address can be checked with the NET VISION
Explorer software utility (see NET VISION explorer §).
By default, NET VISION requests the admin account login and password to open web pages.
Login: admin
Password: public

9.4. IP SETTINGS USING NETWORK IF DHCP NOT PRESENT

For the case of NET VISION 5 and 6:
1. You need a computer with Terminal application connected to the same Network as Net Vision.
2. Check the IP address of your terminal
3. Run a terminal session (a DOS session for example)
4. Execute the following command: ROUTE ADD 192.168.7.18 computer.IP.address
5. Test the connection to Net Vision: Ping 192.168.7.18
6. If the NET VISION responds to the ping, open a web session to modify IP parameters.
For the case of NET VISION 7
Even if DHCP is not available, the IP address can be set through the Net Vision Explorer tool.

9.5. IP SETTINGS USING A TERMINAL AND RS232 CONNECTION for NET VISION 5 and 6

1. Connect the RS232/RJ45 PC cable from Net Vision to your computer
2. Open a Terminal session with the parameters assigned to the right COM port:
• 9600 bauds
• Parity none
• 8 bits data
• No control
3. Press 'space' to open the communication.
4. Enter the password: public (default password)

9.6. IP SETTINGS USING A TERMINAL AND USB for NET VISION 7

The USB Gadget Serial driver must be installed. Please refer to the APPENDIX.
Once the device is recognized, open an SSH terminal connection to modify IP settings.
NET-VISION 7 - SOCOMEC