Emi/Ems And Environmental Standard Compliance - ABB MicroSCADA Pro SYS 600C 2.93 Product Manual

Table of Contents

Advertisement

SYS 600C 2.93
6.2
36
MicroSCADA Pro
Product Guide
Temperature
Operating: -30°C ~ +65°C (-22 °F ~ 149°F)
(Maximum continuous CPU burden 50% of lowest/highest operating
temperature)
Storage: -40°C ~ +75°C (-40 °F ~167°F)
MTBF
25 years (+25°C / 77°F)
22 years (+40°C / 104°F)
Relative humidity
5% ~ 95% (+40°C / 104°F) non-condensing
Protection class
IP40

EMI/EMS and environmental standard compliance

The following tables list the EMI/EMS and environmental standard compliance.
Table 6.2: IEC 61850-3 standard compliance
Type test
IEC 61000-4-2-2001
IEC 61000-4-3-2006
IEC 61000-4-4-2004
IEC 61000-4-5-2005
IEC 61000-4-6-2006
IEC 61000-4-8-2001
IEC 61000-4-10-1993
IEC 61000-4-12-1995
IEC 61000-4-16-2002
IEC 61000-4-29-2000
CISPR22-2008
FCC 15
EN55022A
IEC 60255-5
IEC 60255-27
Description
Electrostatic Discharge
Radiated RF Succeptibility
Fast Transient (Burst Immunity)
Surge Immunity
Conducted RF Immunity
Magnetic Field Immunity
Damped Magnetic Immunity
Damped Oscillatory Burst
Conducted RF Immunity
Voltage Dips and Interrupts
Conducted and Radiated
Emissions
Conducted and Radiated
Emissions
Conducted and Radiated
Emissions
Insulation resistance measure-
ment
Protective bonding resistance
1MRS757729
Severity level
Level 4 -±8KV Contact/±15KV
Air
Level 3-18V/m, 6 directions
Level 4- ±4KV 5KHz
Level 4 ±4KV line-to-earth/±2KV
line-to-line
Level 3-10Vrms
Level 5- 100A/m 5min /
1000A/m 1s
Level 4- 30A/m
Level 3-2.5KV common/Differen-
tial 1.25KV for Substation
Level 3-15Hz~150KHz
30% 120ms/ 70% 10ms 100%
3ms (cycle 3)
Class A
Class A
Class A
500VDC, 1min,
999Mohm>100Mohm
25Amps, 1min,
0.021ohm<0.1ohm