Setting range
OFF SET
Offset is an amount of energy (in Wh, kWh, or MWh) that can be added to the lifetime total
energy output of the inverter to give it a 'head start.'
Unit
Setting range
Factory setting
CALI.
Preset correction value, so that the data shown on the inverter display corresponds to the
calibrated data shown on the electric meter
Unit
Setting range
Factory setting
IG no.
Unit
Setting range
Factory setting
IMPORTANT! Each inverter must be assigned its own address when connecting several
inverters in a data communications system.
DAT COM
Setting range
OK COM / ERROR COM
Displays data communication available via Solar Net or an error that occurred in data com-
munication
Examples of options:
SIGCD TEST
Function test for the Fronius Signal Card option
OFF SET / CALI.
Wh / kWh / MWh
5-digit + k... / M...
1 kWh = 1000 Wh
1 MWh = 1000000 Wh
0
%
-5.0 - +5.0 in increments of 0.1
0
Number setting (address) of the inverter in
a setup comprising multiple solar inverters
linked together
-
01 - 99 (100th inverter = 00)
1
Indicates status of data transmission, func-
tion test or activates and resets various op-
tion (e.g., Fronius Signal Card, Fronius
Personal Display Card, Fronius Interface
Card, Fronius TAC Card, etc.)
Displays OK COM or ERROR COM;
SIGCD TEST / PDCD RST / IFCD RST / TAC ON