Page 2
TABLE OF CONTENTS TABLE OF CONTENTS: 10000008586/00 - February 2015 GENERAL INFORMATION .............................. 3 Use of this manual .............................. 3 Validity of this manual ............................3 Use of pictograms .............................. 3 Identification label ...............................
Figure 2: operation of the ChargeMaster FEATURES SWITCHING ON / STAND-BY The Mastervolt ChargeMaster is a fully automatic battery The ChargeMaster is activated by holding the POWER charger. This means that under normal circumstances it switch pressed for approx. 5 seconds. The POWER switch may stay switched on with the AC power and batteries will illuminate green.
OPERATION Load bar Yellow LED “A” = on Yellow LED “V” = on Actual stage of the three step charge algorithm. Charge voltage Charge current 100% >14V >28V 13-14V 26-28V 12-13V 24-26V 11-12V 22-24V 10.5-11V, 21-22V, Blinking: Blinking: 20-21V 10-10,5V Selected battery bank Red LED: see section 2.7 (1, 2 or 3).
OPERATION THREE STEP CHARGE ALGORITHM 2.4.1 Temperature compensated charging By installing the battery temperature sensor the charge See Figure 4. Battery charging is accomplished in three voltages automatically adapted deviating automatic stages: BULK, ABSORPTION and FLOAT. temperatures. The first step of the three step charge system is the BULK phase, in which the output current of the charger is 100%, and the greater part of the capacity of the battery is rapidly charged.
If a fault communication between the different Mastervolt system condition occurs, a load bar segment on the display devices such as the inverter, battery charger, generator, illuminates red. The LED position indicates the failure batteries and many more.
INSTALLATION 3 INSTALLATION During installation commissioning Although the ChargeMaster fully complies with all ChargeMaster, the important safety instructions are applicable EMC limits, it may still cause harmful applicable at all times. interference to radio communication equipment. If such interference appears, it is recommended to increase the separation between the ChargeMaster and the UNPACKING equipment, to relocate the receiving antenna or to...
The minimum required battery capacity for negative post of the battery bank or the ground side of a Mastervolt gel batteries (MVG series) is as follows: current shunt. Do not use the chassis frame as the negative conductor. Tighten securely. The positive battery...
Page 11
INSTALLATION 3.7.2 Connection example AC Input DC fuse Battery fuse Battery Battery fuse fuse Temperature sensor BATTERY BATTERY BATTERY BANK 1 BANK 2 BANK 3 This schematic is to illustrate the general placement of the ChargeMaster in a circuit. It is not meant to provide detailed wiring instructions for any particular electrical installation.
INSTALLATION INSTALLATION STEP BY STEP Fix the enclosure to the wall by fastening two screws at the lower side of the enclosure as well. Mark the position of the four mounting spots by using the mounting bracket. Then fix the mounting bracket to the wall.
Page 13
INSTALLATION If required, change DIP-settings. See section Mount the isolation caps of the DC terminals back into position 4.1 for adjustment. Mind the + and – markings! Use a small screw driver for adjustment of the DIP-switches. Attach the battery temperature sensor to the casing of battery bank 1.
When placing this fuse, a spark can occur, Always use the original packing for transportation. Contact caused by the capacitors used in the your local Mastervolt Service Centre for further details if ChargeMaster. This is particularly dangerous you want to return the apparatus for repair.
SETTINGS 4 SETTINGS Adjustment of the settings of the ChargeMaster can be 4.1.4 DIP switch 4: CEC Energy saving mode made in two different ways: By means of DIP-switches; see section 4.1; Energy saving mode disabled (factory setting) Via the MasterBus network;...
SETTINGS MASTERBUS FUNCTIONS The equalizing mode can only be started when the Adjustment of the settings of the ChargeMaster can be ChargeMaster is in operation and in Float mode. The made via the MasterBus network (by means of a remote equalize mode can only be started by means of MasterBus control panel or an interface connected to a PC with (see section 4.3.4).
Page 17
SETTINGS Value Meaning Factory setting Adjustable range Lowest DC volt Lowest detected DC voltage output 2 (read only) Highest DC Volt Highest detected DC voltage output 2 (read only) Battery 3 Lowest DC volt Lowest detected DC voltage output 3 (read only) Highest DC Volt Highest detected DC voltage output 3...
Page 18
SETTINGS Value Meaning Factory setting Adjustable. range DC High off Lower threshold level to stop the Output high alarm 15.50/31.00V 0-16.00/0-32.00V DC Low on Lower threshold level to trigger the Output low alarm 10.00/20.00V 0-16.00/0-32.00V DC Low off Upper threshold level to stop the Output low alarm 11.00/22.00V 0-16.00/0-32.00V Alarm Delay...
Page 19
SETTINGS Value Meaning Factory setting Adjustable. range Events Event x source Disabled (See List of event Event-based command Event by the ChargeMaster that should result in an sources, section action by another device on the MasterBus network. 4.3.6) Event x target (See Device list) Event-based command Selection of device on the MasterBus network that...
If you cannot solve a problem with the aid of this chapter, contact your local Mastervolt Service Centre. Make sure you have the following information present if you have to contact your local Mastervolt Service Center to solve a problem: ...
* standard included with the delivery of the ChargeMaster Mastervolt can offer a wide range of products for your electrical installation, including an extended program of components for your MasterBus network, both AGM and gel batteries, shore power connections, DC distribution kits and many more.
Need help?
Do you have a question about the CHARGEMASTER 12/35-3 and is the answer not in the manual?
Questions and answers