GE D30 Instruction Manual page 603

Line distance protection system, ur series
Hide thumbs Also See for D30:
Table of Contents

Advertisement

APPENDIX B
F623
ENUMERATION:
REAL-TIME
SOURCE CONFIGURATION
Enumeration
Item
0
None
1
PP/IRIG-B/PTP/SNTP
2
IRIG-B/PP/PTP/SNTP
3
PP/PTP/IRIG-B/SNTP
F624
ENUMERATION:
REAL-TIME
SOURCE ACTUALS
Enumeration
Item
0
None
1
Port 1 PTP Clock
2
Port 2 PTP Clock
3
Port 3 PTP Clock
4
IRIG-B
5
SNTP
F625
ENUMERATION: PTP STATE
Enumeration
Item
0
Disabled
1
No Signal
2
Calibrating
3
Synchronized
4
Synchronized (No PDelay)
F626
ENUMERATION: NETWORK PORT FOR REMOTE DEVICE
Enumeration
Item
0
None
1
Network Port 1
2
Network Port 2
3
Network Port 3
GE Multilin
CLOCK
SYNCHRONIZING
CLOCK
SYNCHRONZING
D30 Line Distance Protection System
F627
ENUMERATION: REDUNDANCY MODE
Enumeration
Item
0
None
1
Failover
2
PRP
F628
ENUMERATION: SECURITY BYPASS ACCESS
Disables security on local access, remote access, or both.
Enumeration
Item
0
Disabled
1
Local and Remote
2
Local
3
Remote
F629
ENUMERATION: SCADA PROTOCOL
0 = DNP 3.0, 1 = IEC 60870-5-104, 2 = IEC 60870-5-103
F630
ENUMERATION: IEC 103 ASDU TYPE
0 = 3, 1 = 9
F631
ENUMERATION: VIRTUAL INPUTS FOR IEC 103
Enumeration
Item
0
OFF
1
Virtual Input 1
2
Virtual Input 2
3
Virtual Input 3
64
Virtual Input 64
B.4 MEMORY MAPPING
B-105
B

Advertisement

Table of Contents
loading

Table of Contents