6 ACTUAL VALUES
PATH: ACTUAL VALUES
RECORDS
OSCILLOGRAPHY
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-
CYCLES PER RECORD
raphy section of chapter 5 for additional details.
A trigger can be forced here at any time by setting "Yes" to the
menu for information on clearing the oscillography records.
CLEAR RECORDS
PATH: ACTUAL VALUES
RECORDS
BREAKER 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
There is an identical menu for each of the breakers. The
COMMANDS
CLEAR RECORDS
defined as the slowest operating time of breaker poles that were initiated to open.
GE Multilin
OSCILLOGRAPHY
FORCE TRIGGER?
No
NUMBER OF TRIGGERS:
0
AVAILABLE RECORDS:
0
CYCLES PER RECORD:
0.0
LAST CLEARED DATE:
2000/07/14
15:40:16
MAINTENANCE
BREAKER 1(2)
BKR 1 ARCING AMP φA:
0.00 kA2-cyc
BKR 1 ARCING AMP φB:
0.00 kA2-cyc
BKR 1 ARCING AMP φC:
0.00 kA2-cyc
BKR 1 OPERATING TIME
φA:
0 ms
BKR 1 OPERATING TIME
φB:
0 ms
BKR 1 OPERATING TIME
φC:
0 ms
BKR 1 OPERATING
TIME:
0 ms
BKR 1 ARCING AMP
menu for clearing breaker arcing current records. The
D30 Line Distance Protection System
Range: No, Yes
command. Refer to the
FORCE TRIGGER?
6.4.4 BREAKER MAINTENANCE
values are in units of kA
BREAKER OPERATING TIME
6.4 RECORDS
6.4.3 OSCILLOGRAPHY
COMMANDS
6
2
-cycles. Refer to the
is
6-25