GE D30 series Instruction Manual page 293

Line distance protection system. ur series
Hide thumbs Also See for D30 series:
Table of Contents

Advertisement

5 SETTINGS
NEG SEQ DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit in the forward direc-
tion. Upon
NEG SEQ DIR OC1 TYPE
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
NEG SEQ DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
NEG SEQ DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit in the reverse direc-
tion. Upon
NEG SEQ DIR OC1 TYPE
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
Figure 5–89: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC
GE Multilin
selection, this pickup threshold applies to zero- or negative-sequence current. When
selection, this pickup threshold applies to zero- or negative-sequence current. When
D30 Line Distance Protection System
5.6 GROUPED ELEMENTS
5-173
5

Advertisement

Table of Contents
loading

Table of Contents