GE C60 Instruction Manual page 366

Breaker protection system
Hide thumbs Also See for C60:
Table of Contents

Advertisement

GROUPED ELEMENTS
T = operate time (in seconds)
TDM = Multiplier setting
I = Input Current
I
= Pickup Current setting
pickup
T
= Reset Time in seconds (assuming energy capacity is 100% and
RESET
Definite time curve
The Definite Time curve shape operates as soon as the pickup level is exceeded for a specified period of time. The base
definite time curve delay is in seconds. The curve multiplier of 0.00 to 600.00 makes this delay adjustable from
instantaneous to 600.00 seconds in steps of 10 ms. The definite time curve shapes are defined as follows:
where
T = Operate Time (in seconds)
TDM = Multiplier setting
I = Input Current
I
= Pickup Current setting
pickup
T
= Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
RESET
Recloser curves
5
The C60 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurves settings section
earlier in this chapter for details.
5.7.3.3 Phase time overcurrent (ANSI 51P, IEC PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE TOC1(4)
 PHASE TOC 1
5-198
PHASE TOC1
FUNCTION: Disabled
PHASE TOC1 SIGNAL
SOURCE: SRC 1
PHASE TOC1
INPUT: Phasor
PHASE TOC1
PICKUP: 1.000 pu
PHASE TOC1
CURVE: IEEE Mod Inv
PHASE TOC1
TD MULTIPLIER: 1.00
PHASE TOC1
RESET: Instantaneous
PHASE TOC1 VOLTAGE
RESTRAINT: Disabled
PHASE TOC1 BLOCK A:
Off
PHASE TOC1 BLOCK B:
Off
: Timed)
RESET
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Phasor, RMS
Range: 0.020 to 30.000 pu in steps of 0.001
Range: see Overcurrent Curve Types table
Range: 0.00 to 600.00 in steps of 0.01
Range: Instantaneous, Timed
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Eq. 5-14