5.2.4 Economical operation
Generally the following ap-
plies:
5.3

F800 operation

1
4
3
PR-2013-0105-GB • Subject to modifications • R2-04/2016
The efficiency of the F800 depends largely on the selection of the pool water temper-
ature, the hall air temperature, and the hall humidity.
The higher the room temperature is above the pool water temperature and the higher
the inside air humidity is set, the more economical the dehumidification unit.
The air temperature should be about 2-4 K above the pool water temperature.
The evaporation quantities could double if the pool water temperature is at the same
level or higher than the air temperature!
1:The operating switch with the functions "I" (ON) and "0" (OFF)
2
2:Rotary knob – for adjusting the desired relative hall humidity
3:Malfunction indication (red)
4: Operating indicator (green)
serve simultaneously as "reset" in the event of faults
when the malfunction indicator lights up, please look for the
error in the table on "Troubleshooting" on page 36.
Commissioning and Operation