Mounting
After enrolling and before mounting permanently, conduct Go/No Go
test (see controller's instructions) to verify adequate signal strength.
Adjust the device location as necessary.
Physically mount the smoke detector in the desired location;
1. Using two supplied screws and anchors, mount the base.
2. Attach the smoke detector to the mounting base with a clockwise
motion.
3. Test each detector as described in the Testing section.
4. Confirm all desired signals have been received by the Central
Station.
NOTE: NFPA 72 recommends the installation of detectors only after
completing construction or any other dust producing activity
Testing
Test communications between the detector and the control panel.
The detector mode has two test buttons; one for smoke testing and
one for CO testing.
The detector may also be functionally tested using canned smoke
and canned CO. If the detector fails any of the test methods, the
detector should be replaced.
NOTE: Testing the detector will activate the alarm and send a signal
to the panel. Before testing, notify the proper authorities to avoid
any false alarms.
Smoke Test
Press and hold the Smoke Test button for 3 to 5 seconds. The
detector will sound and illuminate per Table 2 and send a smoke
alarm signal to the control panel.
Verify that the smoke alarm signal was received at the control
panel.
To functionally test the smoke sensor see Smoke Entry Test section.
CO Test
Press and hold the CO Test button for 3 to 5 seconds to enter a
functional gas test mode. See Functional Gas Test section.
The control panel alarm and all auxiliary functions should be
verified for a complete test of the system.
Smoke Entry Test
1. With the detector in standby mode, spray canned smoke into the
detector. The canned smoke that can be used and is approved
for test include: Home Safeguard Industries 25S, SDi CHEK02
and CHEK06, SDi SOLOA4, and SDi SMOKESABRE.
2. The detector will sound and illuminate per Table 2 and a smoke
alarm signal will be sent to the panel.
3. Verify the smoke alarm signal was received by the control panel.
Smoke Sensitivity Reading
When the Smoke Test button is pressed for 3 to 5 seconds, the
detector will vocally annunciate its smoke sensitivity along with
diagnostic information.
Replace Battery
Caution: The batteries used in this device may present a fire or
chemical burn hazard if mistreated. Do not recharge, disassemble,
heat above 100° C (212° F) or dispose of in fire. Use only
Panasonic CR123A Lithium batteries. Remove old batteries. Wait
10 seconds and then replace with four new batteries. Use of other
batteries may present a risk of fire or explosion. Keep used
batteries away from children. Dispose of used batteries properly.
Panasonic CR123A
0
~ 10
10
45
sec / seg
20
30
.
Table 2: LED Indication & Sounder during Test and Maintenance
MODE
Smoke Alarm
System Test
RealTest™
Functional CO gas
entry test - Waiting
for gas entry
RealTest™
Functional CO gas
entry test -Upon
successful gas entry
Low Battery
Smoke
Maintenance
CO Trouble
CO End of Life -
First 29 days
CO End of Life -
after 30 days
Power Up
Normal (Standby)
Restore Factory Settings
Press and hold both the Smoke and CO test switch
simultaneously for 10 seconds, then release. The green light
will flash rapidly. Press and hold both buttons again for one
second and release. The sensor will begin speaking.
2
Side LED
Status LED
Windows
Sounder
(Top)
Dark
Dark
Temp-3
Blink Red
once a
Dark
Silent
second
Blink Red
Blink blue
Modified
every
every
Temp-4
10 secs
10 secs
Blink Amber
Chirp every
every
Dark
45 seconds
10 secs
after 7 days
Blink Amber
Dark
Silent
every 5 secs
Blink Amber
Dark
Silent
every 5 secs
Blink Amber
Dark
Silent
every 3 secs
Chirp
Blink Amber
Dark
every 45
every 3 secs
Seconds
Blink Green,
Dark
Silent
every 2 secs
Single Blink
Green every
Dark
Silent
10 sec
Speaker
Warning of
alarm signal
transmission.
Voice smoke
warning
Voice
instructions for
testing; warning
of alarm signal
Voice carbon
monoxide
warning
Voice
instructions
when chirp is
hushed by
pressing either
test button
Voice smoke
maintenance
instructions if
either test
button is
pressed
Voice end of life
instructions;
press either test
button
Voice end of life
instructions;
press either test
button
Voice
welcome,
instructions
follow POR for
language
selection,
enrollment,
testing
Silent
Need help?
Do you have a question about the 5800COMBO and is the answer not in the manual?
Questions and answers