CHAPTER 6: ACTUAL VALUES
The C70 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
— Multicast (SSM and ASM) modes of R-GOOSE reception require that the C70 device subscribe to a multicast group
IGMP
over the Internet Group Management Protocol (IGMP) enabled network. R-RxGOOSE## IGMP status On indicates that IGMP
negotiation with a network device (for example a router) was successful. In the case where setting R-RxGOOSE1 DST IP is
configured to a multicast address and this status indicates Off, R-GOOSE reception cannot be successful, and therefore
communication network diagnosis needs to be carried out. This status is relevant to R-GOOSE reception when configured
for SSM or ASM reception modes. It is not relevant for GOOSE or for R-GOOSE in unicast reception mode.

6.3.10 Digital counters

ACTUAL VALUES  STATUS  DIGITAL COUNTERS  DIGITAL COUNTERS Counter 1(8)
 DIGITAL COUNTERS
 Counter 1
The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The

6.3.11 Selector switches

ACTUAL VALUES  STATUS  SELECTOR SWITCHES
 SELECTOR SWITCHES
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.

6.3.12 Time of day timers

ACTUAL VALUES  STATUS  TIME OF DAY TIMERS
 TIME OF DAY TIMERS
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Counter 1
ACCUM:
0
Counter 1 FROZEN:
0
Counter 1 FROZEN:
1970/01/01 00:00:00
Counter 1 MICROS:
0
value refers to the microsecond portion of the time stamp.
COUNTER 1 MICROS
SELECTOR SWITCH 1
POSITION: 0/7
SELECTOR SWITCH 2
POSITION: 0/7
TIME OF DAY TIMER 1:
Off
TIME OF DAY TIMER 2:
Off
Range: YYYY/MM/DD HH:MM:SS
Range: 0 to 4294967295 in steps of 1
Range: Current Position / 7
Range: Current Position / 7
Range: On, Off
Range: On, Off