CHAPTER 5: SETTINGS
The breaker control element contains the auxiliary logic for status and serves as the interface for opening and closing of a
circuit breaker from protection, autoreclose, SCADA, or through the front panel interface. The breaker control element can
be used to create interlocking functionality. For greater security in determination of the breaker position, both the 52/a and
52/b auxiliary contacts are used with reporting of the discrepancy between them.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
BREAKER 1
SUBSTITUTN: Disabled
BREAKER 1 BYPASS:
Disabled
BREAKER 1 NAME:
Bkr 1
BREAKER 1 MODE:
3-Pole
BREAKER 1 OPEN:
Off
BREAKER 1 BLK OPEN:
Off
BREAKER 1 CLOSE:
Off
BREAKER 1 BLK CLOSE:
Off
BREAKER1 ΦA/3P CLSD:
Off
BREAKER1 ΦA/3P OPND:
Off
BREAKER 1 ΦB CLOSED:
Off
BREAKER 1 ΦB OPENED:
Off
BREAKER 1 ΦC CLOSED:
Off
BREAKER 1 ΦC OPENED:
Off
BREAKER 1 TOPERATE:
70 ms
BREAKER 1 EXT ALARM:
Off
BREAKER 1 ALARM
DELAY:
0.000 s
MANUAL CLOSE RECAL1
TIME:
0.000 s
BREAKER 1 OPEN
SEAL-IN:
0.000 s
BREAKER 1 OUT OF SV:
Off
BREAKER 1 RACKED-IN:
Off
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: up to six alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 65535 s in steps of 1
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
SYSTEM SETUP
5
5-145