Chapter 14 Fault Codes and Descriptions
Warning
CE01
Comm. Error 1
Fault Name
Fault
ocA
Oc at accel
Fault
ocd
Oc at decel
Fault
ocn
Oc at normal SPD
Fault
ocS
Oc at stop
Fault
GFF
Ground fault
D i s p l ay e r r o r s i g n a l
A b b r e v i a t e e r ro r c o d e
T h e c o d e i s d i sp l a y e d a s s h o w n o n K P C - C E 0 1 .
D i s p l a y e r r o r d e s c r i p t i o n
Fault Descriptions
Over-current during
acceleration
(Output current exceeds
triple rated current during
acceleration.)
Over-current during
deceleration
(Output current exceeds
triple rated current during
deceleration.)
Over-current during
steady state operation
(Output current exceeds
triple rated current during
constant speed.)
Hardware failure in
current detection
Ground fault
Chapter 14 Fault Codes and Descriptions |C2000 Series
Corrective Actions
1. Short-circuit at motor output: Check for possible
poor insulation at the output.
2. Acceleration Time too short: Increase the
Acceleration Time.
3. AC motor drive output power is too small:
Replace the AC motor drive with the next higher
power model.
1. Short-circuit at motor output: Check for possible
poor insulation at the output.
2. Deceleration Time too short: Increase the
Deceleration Time.
3. AC motor drive output power is too small:
Replace the AC motor drive with the next higher
power model.
1. Short-circuit at motor output: Check for possible
poor insulation at the output.
2. Sudden increase in motor loading: Check for
possible motor stall.
3. AC motor drive output power is too small:
Replace the AC motor drive with the next higher
power model.
Return to the factory
When (one of) the output terminal(s) is grounded,
short circuit current is more than 50% of AC motor
drive rated current, the AC motor drive power
module may be damaged.
NOTE: The short circuit protection is provided for
AC motor drive protection, not for protecting the
user.
1. Check the wiring connections between the AC
motor drive and motor for possible short circuits,
also to ground.
2. Check whether the IGBT power module is
damaged.
3. Check for possible poor insulation at the output.
14-1
Need help?
Do you have a question about the C2000 series and is the answer not in the manual?
Questions and answers
the screen show "ICS sensor err cd3" how to solve this error?
To resolve the "ICS sensor err cd3" error on the Delta C2000 series, reboot the power. If the fault code is still displayed on the W-phase error cd3 keypad after rebooting, return the unit to the factory.
This answer is automatically generated
@Mr. Anderson : the vfd I have tried restarting it several times. It still shows the "cd3" error on the display. How do I reset the factor?