5. SETTINGS AND PROCEDURES BEFORE OPERATION

5.4 LED Displays and Indicator Descriptions

A
J71DN91
RUN
L.RUN
MS
NS
A
1SJ71DN91
RUN
L.RUN
MS
NS
This section describes the names of the LEDs at the top of the AJ71DN91 and A1SJ71DN91
front panel and provides indicator descriptions.
LED
Color
Description
Name
RUN
Red
Normal opera-
tion display
L.RUN
Red
Communication
status display
MS
Green
Module status
display
Red
Module status
display
NS
Green
Network status
display
Red
Network status
display
LED Display Status
Lit
Not lit
Flashing
Lit
Not lit
Flashing (periodic)
Flashing (random)
Lit
Flashing
Not used
Lit
Communication enabled with on-line
slave stations
Flashing
Communication not enabled with on-
line slave stations
Lit
Duplicate MAC ID error
Bus-off error occurred
Flashing
There is a connection that has timed
out.
5
5
MELSEC-A
Normal operation
Unit error detected
No power supply
Parameters being loaded
Unit error detected
Parameters being loaded
Communicating
Communication stopped
Preparing for communication
Communication parameter error
DeviceNet interface unit operating
normally
Parameter error