Diagnostics
3.2 Error types
3.2
Error types
Analog input module error types
Table 3-1
16
D
9
D
7
D
8
D
6
D
21
D
16
Error types
Error type
10000: Parameter
Module cannot use the
assignment error
parameter for the channel:
Inserted module does not
match the one configured.
Incorrect parameter
assignment.
01001: Error
Internal module error
(diagnostic message at
channel 0 applies to the entire
module)
00111: Upper limit
Value is above the overshoot
exceeded
range.
01000: Lower limit
Value is below the underrange. Correct the module/final
value undershot
00110:
Line to the encoder
Open circuit
interrupted.
10101:
Error on the reference channel
Reference channel
error
Meaning
Correct the configuration (align
actual and set configuration).
Correct the parameter
assignment (wire break
diagnostics only parameterized
for the permitted measuring
ranges).
Replace the module.
Correct the module/final
controlling element tuning.
controlling element tuning.
Correct the process wiring.
Check the reference module
2AI TC HF analog electronic module (6ES7134-4NB01-0AB0)
Manual, 04/2007, A5E01076892-01
Remedy
Need help?
Do you have a question about the 6ES7134-4NB01-0AB0 and is the answer not in the manual?