Note: this manual corresponds to Color Controls running the latest software. Internet-connected Color Controls will update to the latest version automatically. Check our blog posts for the latest firmware:
(/live/_media/ccgx:ccgx_schematic_diagram.png) For class B EMI compliance, place the provided snap-on ferrite beads around every connection cable. Place the beads as close as possible to the ColorControl.
Summary of Contents for Victron energy Color Control GX
Page 1
Color Control GX manual [Victron Energy] https://www.victronenergy.com/live/ccgx:start (/live/start) Color Control GX manual Note: this manual corresponds to Color Controls running the latest software. Internet-connected Color Controls will update to the latest version automatically. Check our blog posts for the latest firmware: https://www.victronenergy.com/blog/category/firmware-software/...
Page 2
1.1 Power Power the Color Control GX (CCGX) on the Power IN V+ connector. It accepts 8 to 70 V DC. The CCGX will not power itself from the network connections. Use a 1A slow blow fuse. If you power the CCGX from an AC adaptor connected to the AC-out of VE.Bus products (Inverter, Multi or Quattro), then a deadlock will happen after the VE.Bus products are powered down for any reason (after any operational fault or during a black start).
Page 3
The minimal version of the VE.Bus devices connected is 19xx111 or 20xx111, released in 2007. VE.Bus firmware 26xxxxx and 27xxxxx is also supported. 18xxxxx is not. Note that it is not possible to use the Remote on/off (header on the VE.Bus control PCB) in combination with a Color Control GX. The jumper link needs to be in the header, as it is by default.
Measuring the output of a PV Inverter is recommended to provide the user with a total overview of both actual current power balance and energy distribution. Note that these measurements are only used for displaying purposes, and that they are not used, nor necessary, for any algorithms to operate. There are multiple options to display the output of a PV Inverter on the Color Control GX: AC Current Sensor , wired to the analog inputs of a Multi or Quattro (lowest cost, least accurate).
Page 5
1.4.2 Wi-Fi USB dongle Using a Wi-Fi dongle it is possible to connect to WEP, WPA and WPA2 secured networks. There are two supported USB Wi-Fi dongles. Both also available from stock at Victron Energy: CCGX WiFi module simple (Nano USB), small, low cost. Victron part number BPP900100200 Startech USB300WN2X2D , slightly higher cost and also better reception.
Color Control GX manual [Victron Energy] https://www.victronenergy.com/live/ccgx:start Do not enable remote support Possibly set the Logging interval to a very low frequency. Note that state changes (charging → inverting, or bulk→float) and also alarms will cause extra messages to be sent To find out how much traffic you need, in order to purchase the right plan, the best way is really to let the system run for a couple of days and monitor the internet RX and TX counters in your 3G or 4G router.
Page 7
Generator start/stop Configure generator autostart settings and conditions. Generator auto start/stop with Color Control GX (/live/ccgx:generator_start_stop) Tank pump Configure automatic starting and stopping of pump based on tank level. Pump auto start/stop with Color Control GX (/live/ccgx:pump_start_stop) Relay Function Alarm relay Select the relay function.
Page 8
Color Control GX manual [Victron Energy] https://www.victronenergy.com/live/ccgx:start The CCGX can be used in combination with the Victron Remote Management (VRM) portal : The CCGX monitors all products [https://vrm.victronenergy.com/] connected to it and the VRM portal makes the statistics easily accessible.
Page 9
Color Control GX manual [Victron Energy] https://www.victronenergy.com/live/ccgx:start If both a microSD card and a USB flash drive are connected to the CCGX, then data is logged to the one that was inserted first. If one is removed, the CCGX will not try to write to the other, but will create an internal backlog buffer until a new storage medium is inserted and then use that storage medium.
Page 10
Color Control GX manual [Victron Energy] https://www.victronenergy.com/live/ccgx:start 2.4 Select SOC source from the GUI to display on the main Overview screen (Settings → System Setup → Battery monitor) In the image below you can see a range of selectable choices for the SOC values that will be shown in the main Overview screen. Choose the source you want to see on the main Overview screen of your CCGX.
Page 11
3 More information resources CCGX Datasheet [https://www.victronenergy.com/upload/documents/Datasheet-Color-Control-GX-EN.pdf] CCGX - Frequently asked questions (/live/ccgx:ccgx_faq) Generator auto start/stop with Color Control GX (/live/ccgx:generator_start_stop) Manually updating CCGX firmware (/live/ccgx:firmware_updating) CCGX Remote VEConfigure and firmware updates (/live/ccgx:ccgx_ve_power_setup) VRM Portal - Frequently asked questions (/live/vrm_portal:faq)