B.4 MEMORY MAPPING
value
GOOSE dataset item
143
GGIO3.MX.AnIn15.mag.f
144
GGIO3.MX.AnIn16.mag.f
F237
ENUMERATION: REAL TIME CLOCK MONTH
B
value
month
0
January
1
February
2
March
3
April
4
May
5
June
6
July
7
August
8
September
9
October
10
November
11
December
F238
ENUMERATION: REAL TIME CLOCK DAY
value
day
0
Sunday
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
F239
ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS
TIME START DAY INSTANCE
value
instance
0
First
1
Second
2
Third
3
Fourth
4
Last
F239
ENUMERATION: FAULT REPORT SYSTEM Z0 MAGNITUDE
value
magnitude
0
None
1
I0
2
V0
B-66
F300
UR_UINT16: FLEXLOGIC™ BASE TYPE (6-bit type)
The FlexLogic™ BASE type is 6 bits and is combined with a 9 bit
descriptor and 1 bit for protection element to form a 16 bit value.
The combined bits are of the form: PTTTTTTDDDDDDDDD,
where P bit if set, indicates that the FlexLogic™ type is associated
with a protection element state and T represents bits for the BASE
type, and D represents bits for the descriptor.
The values in square brackets indicate the base type with P prefix
[PTTTTTT] and the values in round brackets indicate the descrip-
tor range.
[0] Off(0) – this is boolean FALSE value
[0] On (1) – this is boolean TRUE value
[2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 64)
[6] VIRTUAL OUTPUTS (1 to 96)
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64)
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64)
[12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64)
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64)
[14] REMOTE INPUTS (1 to 32)
[28] INSERT (via keypad only)
[32] END
[34] NOT (1 INPUT)
[36] 2 INPUT XOR (0)
[38] LATCH SET/RESET (2 inputs)
[40] OR (2 to 16 inputs)
[42] AND (2 to 16 inputs)
[44] NOR (2 to 16 inputs)
[46] NAND (2 to 16 inputs)
[48] TIMER (1 to 32)
[50] ASSIGN VIRTUAL OUTPUT (1 to 96)
[52] SELF-TEST ERROR (see F141 for range)
[56] ACTIVE SETTING GROUP (1 to 6)
[62] MISCELLANEOUS EVENTS (see F146 for range)
[64 to 127] ELEMENT STATES
F400
UR_UINT16: CT/VT BANK SELECTION
bitmask
bank selection
0
Card 1 Contact 1 to 4
1
Card 1 Contact 5 to 8
2
Card 2 Contact 1 to 4
3
Card 2 Contact 5 to 8
4
Card 3 Contact 1 to 4
5
Card 3 Contact 5 to 8
F491
ENUMERATION: ANALOG INPUT MODE
0 = Default Value, 1 = Last Known