APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 20 of 46)
ADDR
REGISTER NAME
Load Encroachment (Read/Write Grouped Setting)
6700
Load Encroachment Function
6701
Load Encroachment Source
6702
Load Encroachment Minimum Voltage
6703
Load Encroachment Reach
6704
Load Encroachment Angle
6705
Load Encroachment Pickup Delay
6706
Load Encroachment Reset Delay
6707
Load Encroachment Block
6708
Load Encroachment Target
6709
Load Encroachment Events
670A
Reserved (6 items)
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase Undervoltage 1 Function
7001
Phase Undervoltage 1 Signal Source
7002
Phase Undervoltage 1 Pickup
7003
Phase Undervoltage 1 Curve
7004
Phase Undervoltage 1 Delay
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7007
Phase Undervoltage 1 Target
7008
Phase Undervoltage 1 Events
7009
Phase Undervoltage 1 Measurement Mode
700A
Reserved (6 items)
7013
...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
7041
Phase Overvoltage 1 Source
7042
Phase Overvoltage 1 Pickup
7043
Phase Overvoltage 1 Delay
7044
Phase Overvoltage 1 Reset Delay
7045
Phase Overvoltage 1 Block
7046
Phase Overvoltage 1 Target
7047
Phase Overvoltage 1 Events
7048
Reserved (8 items)
Distance (Read/Write Grouped Setting)
7060
Distance Signal Source
7061
Memory Duration
7062
Force Self-Polarization
7062
Force Memory Polarization
Phase Distance (Read/Write Grouped Setting) (5 modules)
7070
Phase Distance Zone 1 Function
7071
Phase Distance Zone 1 Current Supervision
7072
Phase Distance Zone 1 Reach
7073
Phase Distance Zone 1 Direction
7074
Phase Distance Zone 1 Comparator Limit
7075
Phase Distance Zone 1 Delay
7076
Phase Distance Zone 1 Block
7077
Phase Distance Zone 1 Target
7078
Phase Distance Zone 1 Events
7079
Phase Distance Zone 1 Shape
707A
Phase Distance Zone 1 RCA
707B
Phase Distance Zone 1 DIR RCA
707C
Phase Distance Zone 1 DIR Comp Limit
GE Multilin
RANGE
0 to 1
0 to 5
0 to 3
0.02 to 250
5 to 50
degrees
0 to 65.535
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 1
0 to 600
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 5
5 to 25
0 to 65535
0 to 65535
0 to 1
0.05 to 30
0.02 to 500
0 to 2
30 to 90
degrees
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 1
30 to 90
degrees
30 to 90
degrees
30 to 90
degrees
D30 Line Distance Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
ohms
0.01
F001
1
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F111
s
0.01
F001
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F186
0 (Phase to Ground)
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F167
cycles
1
F001
---
1
F300
---
1
F300
---
1
F102
pu
0.001
F001
ohms
0.01
F001
---
1
F154
1
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F120
1
F001
1
F001
1
F001
DEFAULT
0 (Disabled)
0 (SRC 1)
250
100
B
30
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0 (Definite Time)
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (SRC 1)
10
0
0
0 (Disabled)
200
200
0 (Forward)
90
0
0
0 (Self-reset)
0 (Disabled)
0 (Mho)
85
85
90
B-27