13. Local HMI .............. 7 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.
The standard signal configuration can be altered utility substations and industrial power systems, by LHMI (local human-machine interface). in primary and secondary distribution networks. REF601/REJ601 is a member of ABB’s Relion ® Further, the configuration functionality of the product family and part of its 605 series.
● ● = Included Protection functions 255-3 and ANSI C37.112, Normal Inverse (NI), REF601/REJ601 offers three-stage overcurrent Very Inverse (VI), Extremely Inverse (EI), Long- and two-stage earth-fault protection functions. time Inverse (LI) respective Moderate inverse, The transformer inrush detector function is Normal Inverse, Very inverse, Extremely inverse incorporated to prevent unwanted tripping’s due...
Figure 1. Functionality overview for REF601 standard configuration E with current transformer inputs Application The relay additionally offers thermal overload The REF601/REJ601 is a protection relay aimed protection for feeders, cables and transformers, at protection and control of incoming and phase discontinuity (signle phasing) protection outgoing feeders in MV distribution substations.
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Control Recorded data The relay offers control of one circuit breaker The relay stores fault records of analogue values with dedicated push-buttons and guidance on for last five trip events in non-volatile memory.
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A for the operator, engineer and administrator The relay has six output contacts, two power level. There is availability of 2 different password outputs and four signalling outputs.
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A 17. Technical data Table 5. Dimensions Relay type Description Value frame 130.0 mm Width case 121.5 mm frame 160.0 mm Height case 151.5 mm...
Page 9
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 8. Binary input Description Value Rated voltage 24...240 V AC / DC 85...110% of Un for AC and Operating range 70...120% of Un for DC Current drain 2...20 mA...
Page 10
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Table 11. Signal output and IRF output (XK2 : BO3, BO4, BO5, BO6) Description Value Rated voltage 240 V AC/DC Continuous contact carry Make and carry for 3.0 s...
Page 11
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 14. Environmental tests Description Type test value Reference Dry heat test (humidity < 50% ) IEC 60068-2-2 IEC 60068-2-48 Working ...
Page 12
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Table 16. Electromagnetic compatibility tests, continue Description Type test value Reference Power frequency magnetic field immunity IEC 61000-4-8 test: Continuous 100 A/m ...
Page 13
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 18. Mechanical tests Description Type test value Reference Vibration tests IEC 60255-21-1, class I 10...150 Hz, 0.035 mm / 1.0g, Response 1 sweep / axis 10...150 Hz, 2.0 g,...
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A 18. Protection functions Table 23. Low-set phase overcurrent protection, stage 3I> / 51 Parameter Value (Range) Setting range of pick-up current ‘I >’...
Page 15
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 26. Low-set earth-fault protection, stage Io> / 51N Parameter Value (Range) Setting range of pick-up current ‘Io>’ External earth measurement : 0.05...2.0 x In in steps 0.001, infinite Internal earth measurement : 0.5...2.0 x In in steps 0.001, infinite...
Page 16
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Table 28. Transformer inrush detection, 3I2f> / 68 Parameter Value (Range) Inrush threshold value 0.5...25 x In, in steps of 0.01 Ratio Setting 30%...50%, in steps of 5%...
Page 17
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 31. Negative sequence overcurrent protection, I2> / 46 Parameter Value (Range) Start value, ‘I2>” 0.1…1.5 x In, in steps of 0.01 Operate delay time, ‘tI2>’...
Page 18
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Table 34. Counter Parameter Value (Range) Initial value of the counter at the start of IED, ‘Value’ 0…65535, in steps of 1 1…4 (1=BI1, 2=BI2, 3=BI3, 4=BI4)
The REF601/REJ601 have been equipped with With appropriate mounting accessories the in-built press-fit mechanism. Without using any REF601/REJ601 can be mounted on the circuit additional mounting accessories, the breakers type VD4 /HD4. The panel cut-out for REF601/REJ601 can be easily flush mounted on flush mounting: the panel.
Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A 20. Selection and ordering data The relay type and serial number label identifies The serial number and order number label is the protection relay.
Web page helps you find the documents by the document category and You will find the latest relevant information on language. the REF601/REJ601 protection relay on the product page. The Features and Application tabs contain product related information in a compact format.
Page 24
Contact us ABB India Ltd, Distribution Automation Maneja Works Vadodara-390013, India Phone: +91 265 6724402 Fax: +91 265 6724407 ABB Oy, Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone: +358 10 22 11 Fax: +358 10 22 41094 www.abb.com/mediumvoltage...
Need help?
Do you have a question about the REJ601 and is the answer not in the manual?
Questions and answers