Operating Instructions Capacitive rod electrode for continuous level measurement VEGACAL 62 For connection to a signal conditioning instrument Document ID: 30317...
How to proceed if a repair is necessary ................24 Dismount Dismounting steps......................25 Disposal ......................... 25 Supplement Technical data ........................ 26 Dimensions ........................30 Industrial property rights ....................34 VEGACAL 62 • For connection to a signal conditioning instrument...
Page 3
• 27720 - VEGADIS 61 • 30531 - Electronics module VEGACAL series 60 • 34296 - Protective cover • 31088 - Flanges according to DIN-EN-ASME-JIS Editing status: 2017-04-06 VEGACAL 62 • For connection to a signal conditioning instrument...
This arrow indicates a single action. Sequence of actions Numbers set in front indicate successive steps in a procedure. Battery disposal This symbol indicates special information about the disposal of bat- teries and accumulators. VEGACAL 62 • For connection to a signal conditioning instrument...
For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi- trary conversions or modifications are explicitly forbidden. For safety VEGACAL 62 • For connection to a signal conditioning instrument...
That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" VEGACAL 62 • For connection to a signal conditioning instrument...
• Housing with electronics • Housing lid Fig. 1: VEGACAL 62, rod version with plastic housing Housing lid Housing with electronics 3 Process fitting Type label The type label contains the most important data for identification and use of the instrument: VEGACAL 62 • For connection to a signal conditioning instrument...
Principle of operation Application area VEGACAL 62 is a level sensor for continuous level measurement in all areas of industry. The partly insulated probe is designed for measurement of bulk solids and can be also used in non-conductive liquids such as for example oil.
The supply voltage range can differ depending on the instrument version. The data for power supply are specified in chapter "Technical data". Adjustment VEGACAL 62 measurement signals can be evaluated with the follow- ing: • With a VEGAMET signal conditioning instrument The measuring range must be selected on the electronics module of the probe.
You will find additional information in the supplementary instructions manual "Protective cover" (Document-ID 34296). Flanges Screwed flanges are available in different versions according to the following standards: DIN 2501, EN 1092-1, BS 10, ASME B 16.5, JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual "Flanges according to DIN-EN-ASME-JIS". VEGACAL 62 • For connection to a signal conditioning instrument...
(e.g. through cleaning processes) or on cooled or heated vessels. To maintain the housing protection, make sure that the housing lid is closed during operation and locked, if necessary. Make sure that the degree of contamination specified in chapter "Technical data" meets the existing ambient conditions. VEGACAL 62 • For connection to a signal conditioning instrument...
Page 12
Use a concentric tube in non-conductive products or linearize the meas. signal. If condensate forms on the vessel top, the run-off liquid can cause Condensation bridging and hence measurement errors. For this reason, use a screening tube or a longer insulation. The length depends on the amount of condensate and the drain-off be- haviour of the product. VEGACAL 62 • For connection to a signal conditioning instrument...
For this reason, mount the instrument at a position in the vessel where no disturbances, e.g. from filling openings, agitators, etc., can occur. This applies particularly to instrument versions with a longer probe. VEGACAL 62 • For connection to a signal conditioning instrument...
Page 14
4 Mounting Fig. 6: Inflowing medium VEGACAL 62 • For connection to a signal conditioning instrument...
The data for power supply are specified in chapter "Technical data". Provide a reliable separation between the supply circuit and the mains circuits according to DIN VDE 0106 part 101. The VEGA power supply units VEGATRENN 149AEx, VEGASTAB 690, VEGADIS 371 as well as all VEGAMETs meet this requirement.
10. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 11. Screw the housing lid back on The electrical connection is finished. VEGACAL 62 • For connection to a signal conditioning instrument...
Stainless steel (precision casting) Stainless steel (electro-polished) Filter element for air pressure compensation of all material versions. Blind plug with version IP 66/IP 68, 1 bar for Aluminium and stainless steel VEGACAL 62 • For connection to a signal conditioning instrument...
Wiring plan - version IP 66/IP 68, 1 bar Wire assignment, con- nection cable Fig. 11: Wire assignment, connection cable Brown (+) and blue (-) to power supply or to the processing system Shielding VEGACAL 62 • For connection to a signal conditioning instrument...
• range 1 (sensitive): 0 … 120 pF • range 2 (standard): 0 … 600 pF • range 3 (less sensitive): 0 … 3000 pF VEGACAL 62 • For connection to a signal conditioning instrument...
(see operating instructions manual of the signal conditioning instrument: "Adjustment with medium") When connecting to an analogue input card of a PLC, take note of the operating instructions manual of the input card. The vessel must be as VEGACAL 62 • For connection to a signal conditioning instrument...
Page 21
If the indication exceeds 100 % and cannot be reset, you have to set the range selection switch of the probe to the next higher stage. In both cases you have to repeat the adjustment. VEGACAL 62 • For connection to a signal conditioning instrument...
24 hour service hotline Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550. The hotline is manned 7 days a week round-the-clock. Since we offer this service worldwide, the support is only available in the English language. The service is free, only standard call charges are incurred.
CL-E60ZX (without approvals) Shortening the electrode The probe (rod) can be shortened by any length. 1. Shorten the rod with a cut-off wheel or metal saw at the lower end. Make sure the length is correct before shortening. 2. Carry out a fresh adjustment VEGACAL 62 • For connection to a signal conditioning instrument...
Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Please contact the agency serving you to get the address for the return shipment. You can find the agency on our home page www.vega.com. VEGACAL 62 • For connection to a signal conditioning instrument...
Correct disposal avoids negative effects on humans and the environ- ment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal. VEGACAL 62 • For connection to a signal conditioning instrument...
100 Nm (73 lbf ft) Torque for NPT cable glands and Conduit tubes Ʋ Plastic housing max. 10 Nm (7.376 lbf ft) Ʋ Aluminium/Stainless steel housing max. 50 Nm (36.88 lbf ft) VEGACAL 62 • For connection to a signal conditioning instrument...
Page 27
Process temperature VEGACAL 62 of -50 … +150 °C (-58 … +302 °F) 316L Process temperature (thread or flange -50 … +200 °C (-58 … +392 °F) temperature) with temperature adapter (option) Only in conjunction with PTFE insulation. VEGACAL 62 • For connection to a signal conditioning instrument...
Page 28
– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT Voltage supply Operating voltage Ʋ Non-Ex instrument 12 … 36 V DC Ʋ Ex ia instrument 12 … 30 V DC Depending on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF. VEGACAL 62 • For connection to a signal conditioning instrument...
Page 29
IP 66/IP 68 (0.2 bar) Type 6P casting) IP 68 (1 bar) Type 6P Double chamber IP 66/IP 67 Type 4X IP 66/IP 68 (0.2 bar) Type 6P IP 68 (1 bar) Type 6P VEGACAL 62 • For connection to a signal conditioning instrument...
Approvals Instruments with approvals can have different technical specifications depending on the version. For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded under www.vega.com "Instrument search (serial number)" as well as in the general download area. Dimensions Housing in protection IP 66/IP 67 and IP 66/IP 68; 0.2 bar...
Page 31
Aluminium - single chamber G ¾, G 1, G 1½ ø 16 mm (0.63") 12 mm (0.47") Fig. 18: VEGACAL 62, threaded version G1 (ISO 228 T1) Sensor length, see chapter "Technical data" VEGACAL 62 • For connection to a signal conditioning instrument...
Page 32
Fig. 19: Temperature adapter ø 16 mm (0.63") ø 27 mm (1.06") Fig. 20: VEGACAL 62, screening tube, for example against strong condensation Length of the screening tube, see chapter "Technical data" VEGACAL 62 • For connection to a signal conditioning instrument...
Page 33
9 Supplement ø 27 mm (1.06") Fig. 21: VEGACAL 62, concentric tube, for example with small dielectric constant or for linearization Concentric tube length, see chapter "Technical data" VEGACAL 62 • For connection to a signal conditioning instrument...
Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.