Page 1
UDC3500 Universal Digital Controller Product Manual 51-52-25-120 March 2007 Honeywell Process Solutions Industrial Measurement and Control...
Page 2
Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose.
Page 3
This document provides descriptions and procedures for the Installation, Configuration, Operation, and Troubleshooting of your UDC3500 Controller. Contacts World Wide Web The following lists Honeywell’s World Wide Web sites that will be of interest to our customers. Honeywell Organization WWW Address (URL) Corporate http://www.honeywell.com...
Page 4
Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. 3/07 UDC3500 Universal Digital Controller Product Manual...
3.14 Output Set Up Group.......................106 3.15 Input 1 Set Up Group ......................117 3.16 Input 2 Set Up Group ......................121 3.17 Input 3 Set Up Group ......................124 3.18 Input 4 Set Up Group ......................127 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 6
4.10.6 ACCUTUNE Error Codes ....................212 4.11 Fuzzy Overshoot Suppression ....................213 4.12 Using Two Sets of Tuning Constants..................214 4.13 Input Math Algorithms......................216 4.14 Logic Gate Operation ......................218 4.15 Digital Input Option (Remote Switching) ................221 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 7
Restore Input Factory Calibration....................293 OUTPUT CALIBRATION................... 295 Overview.............................295 First Current Output Calibration ....................296 Second Current Output Calibration.....................298 Third Current Output Calibration ....................300 Position Proportional and Three Position Step Output Calibration ..........302 Restore Factory Output Calibration ....................305 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 8
CODES........................347 10.1 Overview ..........................347 10.2 Reading Control Data......................350 10.3 Read Software Options Status ....................351 10.4 Miscellaneous Read Onlys ......................352 10.4.1 Register Addresses for Read Onlys ................352 10.4.2 SetPoint Program Read Only Information..............352 3/07 UDC3500 Universal Digital Controller Product Manual viii...
Page 9
FURTHER INFORMATION................436 11.1 Modbus RTU Serial Communications ..................436 11.2 Modbus Messaging on Ethernet TCP/IP .................436 11.3 How to Apply Digital Instrumentation in Severe Electrical Noise Environments....436 INDEX ........................437 SALES AND SERVICE..................442 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 10
Table 4-5 Control Mode Definitions ___________________________________________________ 201 Table 4-6 Changing Control Modes ____________________________________________________ 202 Table 4-7 Procedure for Changing the Local Setpoints _____________________________________ 203 Table 4-8 Procedure for Switching Between Setpoints _____________________________________ 203 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 11
Table 6-5 Set Up Wiring Procedure for the Third Current Output ____________________________ 300 Table 6-6 Third Current Output Calibration Procedure _____________________________________ 301 Table 6-7 Position Proportional and Three Position Step Output Calibration Procedure ___________ 303 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 12
Table 10-21 Set-up Group – Input 1____________________________________________________ 401 Table 10-22 Set-up Group – Input 2____________________________________________________ 403 Table 10-23 Set-up Group – Input 3____________________________________________________ 405 Table 10-24 Set-up Group – Input 4____________________________________________________ 407 Table 10-25 Set-up Group – Input 5____________________________________________________ 409 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 13
Table 10-32 Set-up Group – Time Event ________________________________________________ 430 Table 10-33 Set-up Group – Display ___________________________________________________ 432 Table 10-34 Set-up Group – Clock ____________________________________________________ 433 Table 10-35 Modbus RTU Data Layer Status Exception Codes ______________________________ 435 xiii UDC3500 Universal Digital Controller Product Manual 3/07...
Page 14
Figures Figure 1-1 UDC3500 Operator Interface __________________________________________________ 6 Figure 1-2 Screen capture of Process Instrument Explorer running on a Pocket PC _________________ 8 Figure 1-3 Depiction of infrared communications ___________________________________________ 9 Figure 2-1 Model Number Interpretation _________________________________________________ 18 Figure 2-2 Mounting Dimensions (not to scale)____________________________________________ 20...
Page 15
Figure 6-2 Wiring Connections for Calibrating the Second Current Output _____________________ 298 Figure 6-3 Wiring Connections for Calibrating Third Current Output _________________________ 300 Figure 8-1 UDC3500 Exploded View __________________________________________________ 335 Figure 10-1 Software Option Status Information __________________________________________ 351 UDC3500 Universal Digital Controller Product Manual...
1.1 Overview Function The UDC3500 is a microprocessor-based stand-alone controller. It combines a high degree of functionality and operating simplicity in a 1/4 DIN size controller. This instrument is an ideal controller for regulating temperature and other process variables in numerous heating and cooling applications, as well as in metal working, food, pharmaceuticals, semiconductor, testing and environmental work.
Page 18
Introduction Analog Inputs The UDC3500 has three universal analog inputs with a typical accuracy of ±0.10% of full-scale input and a typical resolution of 16 bits. These can be configured to act as one Universal and four High Level Inputs for a total of five analog inputs. All analog inputs are sampled six times per second (every 166 ms).
Page 19
Also, two of these digital inputs can allow one of six additional selections to be combined with one of the above selections. Outputs Output Types - The UDC3500 may have up to seven of the following outputs: • Current Outputs (4-20 or 0-20 mA) • Electromechanical Relays (5 amps) •...
Page 20
• Diagnostic Alarm Communications A communications link is provided between the UDC3500 and a host computer or PLC via the RS422/485 Modbus® RTU or Ethernet TCP/IP * communications option. An infrared communication link is also available allowing a non-intrusive configuration of the instrument.
Page 21
Fast Tune will tune the process in such a way that the temp is reached faster, a slight overshoot will be allowed. Slowtune will minimize overshoot, but it will take more time for the process temperature to reach the target setpoint. 3/07 UDC3500 Universal Digital Controller Product Manual...
It can be enabled or disabled depending on the application or the control criteria. * The Second Current Output option is mutually exclusive with the Ethernet Communications option. † Characterizers are mutually exclusive with Setpoint Program #4. 1.2 Operator Interface Figure 1-1 UDC3500 Operator Interface UDC3500 Universal Digital Controller Product Manual 3/07...
Decreases setpoint or output value. Decreases Increases the configuration values or the configuration values or changes functions in changes functions in Configuration Configuration mode groups. mode groups. Infrared transceiver NEMA4X and IP66 screw attachment (each corner) 3/07 UDC3500 Universal Digital Controller Product Manual...
• Create/edit configurations live, just connect software to the controller via a communications port. • Create/edit configurations offline and download to controller later via a communications port. • Communication types available on every UDC3500: Infrared (standard) RS 485 (optional) Ethernet (optional) •...
You can now communicate. After 4 minutes, the port will be shut down again. Each controller may also be assigned a different communications address. Figure 1-3 Depiction of infrared communications 3/07 UDC3500 Universal Digital Controller Product Manual...
WARNING If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. UDC3500 Universal Digital Controller Product Manual 3/07...
2 Installation 2.1 Overview Introduction Installation of the UDC3500 consists of mounting and wiring the controller according to the instructions given in this section. Read the pre-installation information, check the model number interpretation (Subsection 2.3) and become familiar with your model selections, then proceed with installation.
Page 28
Figure 2-24 Optional Electromechanical Relay Outputs Figure 2-25 Transmitter Power for 4-20 mA — 2 wire Transmitter Using Open Collector Output Figure 2-26 Transmitter Power for 4-20 mA — 2 Wire Transmitter Using Second Current Output UDC3500 Universal Digital Controller Product Manual 3/07...
• Check that the model number shown on the inside of the case agrees with what you have ordered. 2.2 Condensed Specifications Honeywell recommends that you review and adhere to the operating limits listed in Table 2-1 when you install your controller. Table 2-1 Condensed Specifications...
Page 31
When applying power to more than one instrument, make sure that sufficient power is supplied. Otherwise, the instruments may not start up normally due to voltage drop from the inrush current. Weight 3 lbs. (1.3 kg) 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 32
60 ± 0.2 59 to 61 58 to 62 * The maximum moisture rating only applies up to 40 °C (104 °F). For higher temperatures, the RH specification is derated to maintain constant moisture content. UDC3500 Universal Digital Controller Product Manual 3/07...
_ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ KEY NUMBER - UDC3500 Single & Dual Loop Controller Description Selection Availability Digital Controller for use with 90 to 264Vac Power + Current Output #1...
English Manual (Hard Copy) French Manual (Hard Copy) Manuals German Manual (Hard Copy) Italian Manual (Hard Copy) Spanish Manual (Hard Copy) None Certificate Certificate of Conformance (F3391) TABLE VI None Figure 2-1 Model Number Interpretation UDC3500 Universal Digital Controller Product Manual 3/07...
Table 2-3 Alarm Relay Contact Information Unit Alarm Relay Variable NOT in Alarm State Variable in Alarm State Power Wiring Relay Indicators Relay Indicators Contact Contact N.O. Open Open N.C. Closed Closed N.O. Closed Open N.C. Open Closed 3/07 UDC3500 Universal Digital Controller Product Manual...
Mounting Notes Before mounting the controller, refer to the nameplate on the outside of the case and make a note of the model number. It will help later when selecting the proper wiring configuration. UDC3500 Universal Digital Controller Product Manual 3/07...
(Figure 2-3). Push the point of the screw through the center piercing the elastomeric material and then tighten screws to 5 lb-in (56 N•cm). 3/07 UDC3500 Universal Digital Controller Product Manual...
Vac, 42.4 Vpeak, or 60 Vdc) wiring per Permissible Wiring Bundling, Table 2-5. Electrical Noise Precautions Electrical noise is composed of unabated electrical signals, which produce undesirable effects in measurements and control circuits. UDC3500 Universal Digital Controller Product Manual 3/07...
• 4-20 mA output signal wiring Digital input signals • Low voltage alarm relay output wiring • Low voltage wiring to solid state type control circuits • Low voltage wiring to open collector type control circuits 3/07 UDC3500 Universal Digital Controller Product Manual...
Relay 3), enable Alarm 3 (which also uses Relay 3) and configure a Logic Gate to use Relay 3, then the instrument will use Relay #3 to perform the Time Simplex output and ignore the Alarm and Logic Gate functions. UDC3500 Universal Digital Controller Product Manual 3/07...
Type, But it may be used for the Second Loop Output Type. Refer to the selection made in Table 2-7. Any current output not used as a Control Output for either loop may be used as an Auxiliary Output. 3/07 UDC3500 Universal Digital Controller Product Manual...
*** Current Duplex 50% is available only on Loop 1 or Loop 2, it cannot be used on both loops. If the Second Current Output is not present, then the Third Current Output is used as Loop 1 COOL output. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 43
Digital Inputs Terminals. See Figure 2-23. Optional Relays Terminals (Relays 3, 4 and 5). See Figure 2-24. Optional Interface Second Current Output Terminals. See Figure 2-13. RS-485 Communications Terminals. See Figure 2-20. Ethernet Communications Terminals. See Figure 2-22. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 44
Applying 90-264 Vac to an instrument rated for 24 Vac/dc will severely damage the instrument and is a fire and smoke hazard. damage the instrument and is a fire and smoke hazard. Figure 2-5 Mains Power Supply UDC3500 Universal Digital Controller Product Manual 3/07...
Page 45
The millivolt values for the Thermocouple Differential Input are for a pair of J thermocouples at an ambient temperature mean of 450°F / 232°C. Cold Junction Compensation is not required for this input type. Figure 2-6 Input 1 Connections 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 46
The millivolt values for the Thermocouple Differential Input are for a pair of J thermocouples at an ambient temperature mean of 450°F / 232°C. Cold Junction Compensation is not required for this input type. Figure 2-7 Input 2 Connections UDC3500 Universal Digital Controller Product Manual 3/07...
Page 47
450°F / 232°C. Cold Junction Compensation is not required for this input type. Input 3 is used to measure the Slidewire Input for Position Proportional Control. Figure 2-8 Input 3 Connections 3/07 UDC3500 Universal Digital Controller Product Manual...
These items must be installed prior to start up when the controller is wired. For 0-20 mA applications, the resistor should be located at the transmitter terminals if Burnout detection is desired. Figure 2-9 HLAI Inputs 2 and 4 Connections See Figure 2-11 for Jumper Positions. UDC3500 Universal Digital Controller Product Manual 3/07...
Thermocouple, RTD, Volt, Millivolt, Input becomes HLAI Inputs 2 & 4 Input Types Milliamp, Radiamatic and Input becomes HLAI Inputs 3 & 5 Available (Input 3 only) Slidewire Figure 2-11 Optional Analog Input Jumper Positions 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 50
The Second Current Output is mutually exclusive with Ethernet Communications. Figure 2-13 Second Current Output See Table 2-6 and Table 2-7 for other information about output types. UDC3500 Universal Digital Controller Product Manual 3/07...
Solid State relays are rated at 1 Amp at 25°C and derated linearly to 0.5 Amp at 55°C. Customer should size fuse accordingly. Use Fast Blo fuses only. Figure 2-15 Output #2 – Solid State Relay Output See Table 2-6 and Table 2-7 for other information about output types. 3/07 UDC3500 Universal Digital Controller Product Manual...
Current Output Output Load 0-20 or 4-20 mA 0 - 1000 ohms – Figure 2-17 Output #2 – Third Current Output See Table 2-6 and Table 2-7 for other information about output types. UDC3500 Universal Digital Controller Product Manual 3/07...
Figure 2-19 Output #2 – Dual Relay Output for Position Proportional or Three Position Step Control See Table 2-6 and Table 2-7 for other information about output types. See Figure 2-8 for Slidewire connections. 3/07 UDC3500 Universal Digital Controller Product Manual...
Route the long wire on the Ethernet Adaptor Board over to Terminal #4 on your instrument. The RJ-45 connector on the Ethernet Adaptor Board will allow you to use a UDC3500 Universal Digital Controller Product Manual 3/07...
Ethernet Adaptor Board, then Figure 2-22 and Table 2-8 show the connections for a UDC to a MDI Compliant Hub or Switch utilizing a straight-through cable or for connecting a UDC to a PC utilizing a crossover cable. 3/07 UDC3500 Universal Digital Controller Product Manual...
UDC Terminal UDC Signal Name RJ45 Socket Pin # Switch Signal Name Position 4 Shield Shield Shield Position 24 RXD- TXD- Position 25 RXD+ TXD+ Position 26 TXD- RXD- Position 27 TXD+ RXD+ UDC3500 Universal Digital Controller Product Manual 3/07...
Use only Category 5 (STP CAT5) shielded twisted-pair Ethernet cables. Digital Input #1 Digital Input #2 Digital Input #3 Digital Input #4 Connect shield to ground at one end only. Figure 2-23 Digital Inputs 3/07 UDC3500 Universal Digital Controller Product Manual...
If necessary, install a zener diode here to reduce voltage at the transmitter. A 1N4733 will reduce the voltage at the transmitter to approximately 25 Vdc. Figure 2-25 Transmitter Power for 4-20 mA — 2 wire Transmitter Using Open Collector Output UDC3500 Universal Digital Controller Product Manual 3/07...
If necessary, install a zener diode here to reduce voltage at the transmitter. A 1N4733 will reduce the voltage at the transmitter to approximately 25 Vdc. Figure 2-26 Transmitter Power for 4-20 mA — 2 Wire Transmitter Using Second Current Output 3/07 UDC3500 Universal Digital Controller Product Manual...
3.13 Logic Gates Set Up Group 3.14 Output Set Up Group 3.15 Input 1 Set Up Group 3.16 Input 2 Set Up Group 3.17 Input 3 Set Up Group 3.18 Input 4 Set Up Group UDC3500 Universal Digital Controller Product Manual 3/07...
Page 61
3.26 Maintenance Set Up Group 3.27 Display Set Up Group 3.28 Read Maintenance Set Up Group 3.29 Time Events Set Up Group 3.30 P.I.E. Tool Ethernet and Email Configuration Screens 3.31 Configuration Record Sheet 3/07 UDC3500 Universal Digital Controller Product Manual...
Segment 20 SP PROG4 PROGRAM4 STRT SEG END SEG RAMPUNIT RECYCLES HOTSTART SEG x PID* SEGxRAMP SEGxRATE* * x = 1 to 20. Program SEGx SP* SEGxTIME* SOAKxDEV concludes after Segment 20 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 63
FILTER 3 BURNOUT3 EMISSIV3 INPUT4 IN4 TYPE XMITTER4 IN4 HIGH IN4 LOW RATIO 4 BIAS IN4 FILTER 4 BURNOUT4 INPUT5 IN5 TYPE XMITTER5 IN5 HIGH IN5 LOW RATIO 5 BIAS IN5 FILTER 5 BURNOUT5 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 64
HRS:MIN3 COUNTS 1 COUNTS 2 MAINTNCE COUNTS 3 TIME EVENT 1 TIME 1 HOUR 1 MINUTE 1 MONTH 1 DAY 1 EVENT 2 TIME 2 EVENT HOUR 2 MINUTE2 MONTH 2 DAY 2 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 65
Configuration Set Up Group Function Prompts CALIB USED FOR FIELD CALIBRATION STATUS VERSION FAILSAFE TESTS 3/07 UDC3500 Universal Digital Controller Product Manual...
If you do not press any keys for 30 seconds, the controller times out and reverts to the mode and associated display used prior to entry into Set Up mode. UDC3500 Universal Digital Controller Product Manual 3/07...
RATE action, in minutes, affects the controller’s output whenever the deviation is changing; and affects it more when the deviation is changing faster. Also defined as “HEAT” Rate on Duplex models for variations of Heat/Cool applications. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 68
PID sets are enabled. GAIN 3 RATE3MIN 0.00 to 10.00 minutes RATE 3 MINUTES parameter is the same as previously described. This prompt appears only when four PID sets are enabled. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 69
This configuration should be copied and kept in a secure location. NOTE: The Security Code is for keyboard entry only and is not available via communications. ATTENTION Can only be changed if LOCKOUT selection is NONE. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 70
ATTENTION Can only be viewed if LOCKOUT is configured for NONE. SP SEL SETPOINT SELECT KEY LOCKOUT—Allows you to disable the Setpoint Select key DISABLE DISABLE ENABLE ENABLE ATTENTION Can only be viewed if LOCKOUT is configured for NONE. UDC3500 Universal Digital Controller Product Manual 3/07...
RATE action, in minutes, affects the controller’s output whenever the deviation is changing; and affects it more when the deviation is changing faster. Also defined as “HEAT” Rate on Duplex models for variations of Heat/Cool applications. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 72
PID sets are enabled. GAIN 7 RATE7MIN 0.00 to 10.00 minutes RATE 7 MINUTES parameter is the same as previously described. This prompt appears only when four PID sets are enabled. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 73
PID constants. CYC6 SEC—Electromechanical relays CYC6 SX3—Solid state relays ATTENTION Cycle times are in either second or 1/3-second increments depending upon the configuration of RLY TYPE in the Output Algorithm Set Up group. 3/07 UDC3500 Universal Digital Controller Product Manual...
Please note that the configurations used in SP Program #1 for Program End, Program State, Power Up and Key Reset affect all other SP Programs. For this reason, Program #1 must always be enabled in order to enable Programs #2, 3 and/or 4. UDC3500 Universal Digital Controller Product Manual 3/07...
SP Rate operates on any LSP when both DISABLE DISABLE SETPOINT RATE—Disables the setpoint SP Ramp and SP rate option. Programming are not ENABLE ENABLE SETPOINT RATE—Allows the SP rate active. feature. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 76
RAMPUNIT—Engineering Units for Ramp Segments TIME in hours: minutes TIME RATE in Engineering units per minute EU/MIN RATE in Engineering units per hour EU/HR RECYCLES 0 to 100 recycles Number of Program Recycles UDC3500 Universal Digital Controller Product Manual 3/07...
Page 77
Ramp segment is skipped and the program will restart at the beginning of the first Soak segment in the program. ATTENTION Selection affects all enabled SP Programs. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 78
Section 3.20 (Control 1) and Section 3.21 (Control 2). Selections are same as Same as above SEG3RAMP or SEG3RATE above. SEG3 PID SEG4 SP SEG4TIME SOAK4DEV SEG4 PID SEG5RAMP or SEG5RATE SEG5 PID SEG6 SP SEG6TIME UDC3500 Universal Digital Controller Product Manual 3/07...
RATE in Engineering units per minute EU/MIN RATE in Engineering units per hour EU/HR ATTENTION Normally the same as Program #1 when linking programs. RECYCLES 0 to 100 recycles Number of Program Recycles UDC3500 Universal Digital Controller Product Manual 3/07...
Page 81
SEG3RAMP or Selections are same as Same as above above. SEG3RATE SEG3 PID SEG4 SP SEG4TIME SOAK4DEV SEG4 PID SEG5RAMP or SEG5RATE SEG5 PID SEG6 SP SEG6TIME SOAK6DEV SEG6 PID SEG7RAMP or SEG7RATE 3/07 UDC3500 Universal Digital Controller Product Manual...
Number of Program Recycles ATTENTION Not used when linking programs HOTSTART DISABLE HOT START—This feature allows the SP Program ENABLE to start at the current PV value rather than the current Setpoint value. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 84
Program 3 MUST be used. SEG4 SP SEG4TIME SOAK4DEV SEG4 PID SEG5RAMP or SEG5RATE SEG5 PID SEG6 SP SEG6TIME SOAK6DEV SEG6 PID SEG7RAMP or SEG7RATE SEG7 PID SEG8 SP SEG8TIME SOAK8DEV SEG8 PID UDC3500 Universal Digital Controller Product Manual 3/07...
RAMPUNIT—Engineering Units for Ramp Segments TIME in hours: minutes TIME RATE in Engineering units per minute EU/MIN RATE in Engineering units per hour EU/HR ATTENTION Normally the same as Program #3 when linking programs. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 87
Control 2 Setup Group is set to 4 KEYBD. Selections are same as Same as above SEG3RAMP or SEG3RATE above. SEG3 PID SEG4 SP SEG4TIME SOAK4DEV SEG4 PID SEG5RAMP or SEG5RATE SEG5 PID SEG6 SP SEG6TIME SOAK6DEV SEG6 PID SEG7RAMP or 3/07 UDC3500 Universal Digital Controller Product Manual...
Duplex Tuning is used when a Duplex Control Algorithm is configured. To perform a Duplex Tune, Two Local Setpoints must be configured per the Control Group in Section 3.20. See Section 4.10 for additional information. 3/07 UDC3500 Universal Digital Controller Product Manual...
This method should only be used after the process has lined out (stabilized). ATTENTION When SP Tune is active (T displayed) the Tuning Group parameters cannot be changed. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 91
For example, if the SP range is 0 to 2400 and Setpoint change is set to 5%, then a re-tuning process will take place whenever the SP is changed by 120 or more. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 92
CRITERA2 TUNING CRITERIA (SETPOINT ADAPTIVE) FOR LOOP 2—This prompt appears only when SP or SP+PV has been selected for Loop 2. Same selections as for Same selections as for Loop 1. Loop 1. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 93
PV has increased by more than 4% but Deadtime was not determined. AT ERR 2 Same as Loop 1. ACCUTUNE ERROR STATUS FOR LOOP 2 (Read Only) 3/07 UDC3500 Universal Digital Controller Product Manual...
(hysteresis) of the on and off states of each output. Both Deadband and Hysteresis are separately adjustable. With no relay action the controller will read 50 %. ATTENTION Other prompts affected: OUT HYST and DEADBAND UDC3500 Universal Digital Controller Product Manual 3/07...
Page 95
If you select PD with Manual Reset you can also configure the following variations: • PD (Two Mode) control, • P (Single Mode) control. Set Rate (D) to 0. ATTENTION Other prompts affected: MAN RSET in the Tuning Set Up group 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 96
(loop 2) is used to adjust the remote setpoint of the secondary loop (loop 1). The output of the secondary loop is used to control the final control element. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 97
0 to 99 hours: 59 minutes or from 59 minutes: 59 seconds depending upon Period configuration). START START—Select whether the timer starts with the ALARM 2 keyboard (via the key) or via Alarm 2. Run/Hold 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 98
Alg1 = [(Input A x Ratio A + Bias A) + (K x Input B x Ratio B + Bias B)] / (1 + K)] + Alg1Bias UDC3500 Universal Digital Controller Product Manual 3/07...
Page 99
This selection specifies the PV or SP as the higher of Input A or Input B. The following formula applies: Alg1 = higher of (Input A x Ratio A + Bias A) or (Input B x Ratio B + Bias B) 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 100
Carbon/Oxygen/Dewpoint Notes. CARB C CARBON POTENTIAL C—Make this selection if you have an A.A.C.C. type Zirconium Oxide sensor. This algorithm requires a temperature range within the region of 1500 to 1900°F. See Carbon/Oxygen/Dewpoint Notes. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 101
If the Ratio for Input 2 is set to 0.0, then a constant value may be used for the Input 2 value via the Input 2 Bias setting. When Input 2 Ratio is set to 0.0, the Input 2 low range and Sooting diagnostic messages are disabled. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 102
LOOP 1 OUTPUT—Should not be used for Three Position Step Control applications LP2OUT LOOP 2 OUTPUT—Should not be used for Three Position Step Control applications IN AL1 INPUT ALGORITHM 1 IN AL2 INPUT ALGORITHM 2 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 103
Hydrogen content that is applicable. 590.0 to 760.0 (mm Hg) ATM PRES ATMOSPHERIC PRESSURE COMPENSATION— Used only when Relative Humidity is selected. Enter the value of the atmospheric pressure of the process. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 104
–999. To 9999. Floating CALCULATED VARIABLE LOW SCALING (in engineering units) FACTOR FOR INPUT ALGORITHM 2—Does not apply to Feedforward algorithms. Range is used for either PV or RSP, depending upon Algorithm application. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 105
IN AL1 INPUT ALGORITHM 1 IN AL2 INPUT ALGORITHM 2 ALG2BIAS -999 to 9999 floating (in INPUT ALGORITHM 2 BIAS—Does not apply to engineering units) selections: FFWR2, FFWM2, HI SEL or LO SEL. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 106
This is because input values outside of this range will not calculate valid %RH values. If the calculated %RH value falls below zero, the “RH LOW” diagnostic message will appear on the lower display. UDC3500 Universal Digital Controller Product Manual 3/07...
DP value by "90" to normalize the equation. (IN3 + 14.7) SCFM x 650 (IN2 + 460) Rearranging terms: (IN3 + 14.7) SCFM x 650 Example continued (IN2 + 460) on next page Constant = K Variable 22049 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 108
170 F + 460 50 psi + 14.7 170 F + 460 20 psi + 14.7 110 F + 460 50 psi + 14.7 110 F + 460 20 psi + 14.7 22050 UDC3500 Universal Digital Controller Product Manual 3/07...
Xn Input values are the Output from the control algorithm, and the Yn Output is the final control element action. This application is useful for non- linear control elements or Process Variable. A simple example is shown in Figure 3-2. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 110
Y6 VALUE 0.00 to 99.99 % Y6 INPUT VALUE (Y AXIS) Y7 VALUE 0.00 to 99.99 % Y7 INPUT VALUE (Y AXIS) Y8 VALUE 0.00 to 99.99 % Y8 INPUT VALUE (Y AXIS) UDC3500 Universal Digital Controller Product Manual 3/07...
Page 111
X14 INPUT VALUE (X AXIS) X15VALUE 0.00 to 99.99 % X15 INPUT VALUE (X AXIS) X16VALUE 0.00 to 99.99 % X16 INPUT VALUE (X AXIS) X17VALUE 0.00 to 99.99 % X17 INPUT VALUE (X AXIS) 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 112
E6 = 1 x 10 6 = 1,000,000 TOT SCR TOTALIZER RESET SECURITY LOCK—Allows the totalizer to be reset. UNLOCK UNLOCK—Allows the totalizer value to be reset. LOCK LOCK—Prevents the totalizer value from being reset. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 113
POLYNOMIAL COEFFICIENT C2 C3 X 10 –3 –9.999 to 9.999 POLYNOMIAL COEFFICIENT C3 C4 X 10 –5 –9.999 to 9.999 POLYNOMIAL COEFFICIENT C4 C5 X 10 –7 –9.999 to 9.999 POLYNOMIAL COEFFICIENT C5 3/07 UDC3500 Universal Digital Controller Product Manual...
ENABLE—Enables Logic Gates Function. ATTENTION For each Logic Gate, make a selection for: Gate Type GATEnTYP Input A Source GATEnINA Input B Source GATEnINB Output Use GATEnOUT where n = 1, 2, 3, 4 or 5 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 116
AND—With this gate, if Input A AND Input B are ON, then the Output will be ON; so that any single Input change will not cause the Output to change unless the other Input is already ON. INPUT A OUTPUT (Y) INPUT B UDC3500 Universal Digital Controller Product Manual 3/07...
Page 117
X NOR EXCLUSIVE NOR)—The EXCLUSIVE NOR is an inverted EXCLUSIVE OR. If Input A and Input B are ON or OFF, the Output will be ON. INPUT A OUTPUT (Y) XNOR INPUT B 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 118
Input A will be for any of the 5 Gates you want to configure. The following selections apply if the Gate Type is OR, NOR, AND, NAND, X OR, or X NOR. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 119
2 Loops are configured. –999.0 to +9999 GATE(n) K GATE (n) K CONSTANT—This selection only (n) = 1, 2, 3, 4, or 5 appears if CONST K is configured for GATE(n)INA. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 120
Local or Remote Setpoint – Loop 2 LR SPL2 * 0 = Local 1 = Remote Disable or Enable Adaptive Tune – Loop 2 ADAPT 2 * 0 = Disable 1 = Enable UDC3500 Universal Digital Controller Product Manual 3/07...
Page 121
0 = Local 1 = Remote ADAPT 2 * Disable or Enable Adaptive Tune – Loop 2 0 = Disable 1 = Enable * These prompts appear only when 2 Loops are configured. 3/07 UDC3500 Universal Digital Controller Product Manual...
50 %. TIME TIME SIMPLEX—This output algorithm uses Relay1 for Time Proportional Control. Time Proportional Output has a resolution of 3.33 milliseconds with an adjustable Cycle Time (see Section 3.4). UDC3500 Universal Digital Controller Product Manual 3/07...
Page 123
% to 100 % and time is active for 0 % to 50 %. Relay controls COOL, current controls HEAT. ATTENTION Other prompts affected: OUT RNG OUT RNG CURRENT DUPLEX RANGE ALGORITHM—Used with Output Algorithm selections CUR D, CUR TI, or TI CUR. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 124
4-20 mA output or 0-20 mA output 0-20mA operation without the need for recalibration of the controller. ATTENTION Changing the Current Output Range will result in the loss of Field Calibration values and will restore Factory Calibration values. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 125
ATTENTION Some of these configurations may not be available on Loop 2 if Loop 1 uses the available outputs. See Table 2-6 and Table 2-7 for information about output types and how they are used for each Loop. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 126
% to 100 % and time is active for 0 % to 50 %. Relay controls COOL, current controls HEAT. ATTENTION Other prompts affected: OUT2 RNG OUT2 RNG CURRENT DUPLEX RANGE ALGORITHM—Used with Output Algorithm selections CUR D, CUR TI, or TI CUR. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 127
OUT2 ALG Parameter is configured for ATTENTION Changing the Current Output Range CURRENT, CUR D, will result in the loss of Field Calibration values and CUR TI, or TI CUR. will restore Factory Calibration values. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 128
INPUT 3—Same as Input 1. ATTENTION Do not configure Input 3 when input 3 is used for slidewire or slidewire emulation. INPUT 4 INPUT 4—Same as Input 1. INPUT 5 INPUT 5—Same as Input 1. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 129
Deviation Display = –150 °F, which is –150 / 2000 = –7.5% of the Deviation Range, so Second Current Output = 50% – 7.5% = 42.5% which is 0.425 X 16 mA + 4 mA = 10.8 mA 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 130
(such as PID A). When using one of the characterizers, OUTPUT 2 is the output value for Loop 2 after it passes through the characterizer. CB OUTL2 is the control block output before it passes through the characterizer. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 131
LOCAL SETPOINT ONE FOR LOOP 2—Output represents Loop 2 Local Setpoint 1 regardless of active setpoint. RSP LP2 REMOTE SETPOINT FOR LOOP 2—Represents the configured Loop 2 RSP regardless of the active SetPoint for Loop 2. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 132
For Output, this is a value in percent and can be any value between –5 % and +105 %. However, keep in mind that relay output types can only be scaled 0 % to 100 %. UDC3500 Universal Digital Controller Product Manual 3/07...
0-1 V—0 to 1 Volts 0-5 V 0-5 V—0 to 5 Volts 1-5 V 1-5 V—1 to 5 Volts 0-10 V 0-10 V—0 to 10 Volts -1-1 V -1-1 V— -1 to +1 Volts 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 134
12 mA = 125 Liters/Minute 20 mA = 250 Liters/Minute ATTENTION If Input 1 is selected as the PV Source, then the range of the control Setpoint will be limited by the range of units selected here. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 135
5V type that uses a dropping resistor), the dropping resistor must be remotely located (across the transmitter terminals). Otherwise, the input at the instrument terminals will always be 0 (i.e., within the normal operating range) when the sensor opens. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 136
Radiamatic input signal that is the ratio of the actual energy emitted from the target to the energy that would be emitted if the target were a perfect radiator. Available only for Radiamatic inputs. UDC3500 Universal Digital Controller Product Manual 3/07...
0-1 V—0 to 1 Volts 0-5 V 0-5 V—0 to 5 Volts 1-5 V 1-5 V—1 to 5 Volts 0-10 V 0-10 V—0 to 10 Volts -1-1 V -1-1 V— -1 to +1 Volts 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 138
No filter = 0 provided for Input 2 to smooth the input signal. You can configure the first order lag time constant from 1 to 120 seconds. If you do not want filtering, enter 0. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 139
Radiamatic input signal that is the ratio of the actual energy emitted from the target to the energy that would be emitted if the target were a perfect radiator. Available only for Radiamatic inputs. 3/07 UDC3500 Universal Digital Controller Product Manual...
0-1 V—0 to 1 Volts 0-5 V 0-5 V—0 to 5 Volts 1-5 V 1-5 V—1 to 5 Volts 0-10 V 0-10 V—0 to 10 Volts -1-1 V -1-1 V— -1 to +1 Volts UDC3500 Universal Digital Controller Product Manual 3/07...
Page 141
No filter = 0 provided for Input 3 to smooth the input signal. You can configure the first order lag time constant from 1 to 120 seconds. If you do not want filtering, enter 0. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 142
Radiamatic input signal that is the ratio of the actual energy emitted from the target to the energy that would be emitted if the target were a perfect radiator. Available only for Radiamatic inputs. UDC3500 Universal Digital Controller Product Manual 3/07...
INPUT 4 HIGH RANGE VALUE—This value in (in engineering units) engineering units is displayed for all inputs but can only be changed for inputs configured for linear or square root transmitter characterization. See the example in IN1 HI. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 144
UPSCALE BURNOUT—Forces the Input 4 signal to the full-scale value when the sensor fails. Diagnostic message IN4 FAIL intermittently flashed on the lower display. The controller remains in Automatic control mode and adjusts the controller output signal accordingly. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 145
Burnout current. (For this selection, no burnout signal is sent to the sensor.) ATTENTION The Thermocouple Health feature is disabled when NO FS is configured. 3/07 UDC3500 Universal Digital Controller Product Manual...
INPUT 5 HIGH RANGE VALUE—This value in (in engineering units) engineering units is displayed for all inputs but can only be changed for inputs configured for linear or square root transmitter characterization. See the example in IN1 HI. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 147
UPSCALE BURNOUT—Forces the Input 5 signal to the full-scale value when the sensor fails. Diagnostic message IN5 FAIL intermittently flashed on the lower display. The controller remains in Automatic control mode and adjusts the controller output signal accordingly. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 148
Burnout current. (For this selection, no burnout signal is sent to the sensor.) ATTENTION The Thermocouple Health feature is disabled when NO FS is configured. UDC3500 Universal Digital Controller Product Manual 3/07...
Digital Inputs. Press the key until you see PID SET1 Lower/Display or PID SET2 then press to switch between sets. Configure the values for: Gain, Rate, Reset Gain #2, Rate #2, Reset #2 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 150
Similarly, the controller switches between the other PID sets based upon the values configured for SW VAL 2 and SW VAL 3. ATTENTION Other prompts affected: SW VALUE, SW VAL 2 and SW VAL 3. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 151
Similarly, the controller switches between the other PID sets based upon the values configured for SW VAL 2 and SW VAL 3. ATTENTION Other prompts affected: SW VALUE, SW VAL 2 and SW VAL 3. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 152
FOUR LOCAL SETPOINTS—This selection lets you switch between four local setpoints using the SP/Select RSP SRC REMOTE SETPOINT SOURCE—This selection determines what your remote setpoint source will be when toggled by the key or Digital Input. SP/Select UDC3500 Universal Digital Controller Product Manual 3/07...
Page 153
MANUAL, LSP—At power-up, the controller will use manual mode with the local setpoint displayed. A LSP AUTOMATIC MODE, LAST LSP—At power-up, the controller will use automatic mode with the last local setpoint used before power down displayed. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 154
ACTION CONTROL OUTPUT DIRECTION—Select direct or reverse output action. DIRECT DIRECT ACTING CONTROL—The controller’s output increases as the process variable increases. REVERSE REVERSE ACTING CONTROL—The controller’s output decreases as the process variable increases. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 155
(positive value) or both outputs operate (negative value). –5.0 to 25.0 % Time Duplex 0.0 to 25.0 % On-Off Duplex 0.5 to 5.0 % Position Proportional and Three Position Step 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 156
(NOTE 1) PBorGAIN PROPORTIONAL BAND UNITS—Select one of the (selection is used for following for the Proportional (P) term of the PID both loops) algorithm: UDC3500 Universal Digital Controller Product Manual 3/07...
Page 157
Math A, Math B, Math C or Math D; then the SP HiLIM and SP LoLIM values can be set anywhere between –999 and 9999 and are not limited to the CALC HI and CALC LOW values 3/07 UDC3500 Universal Digital Controller Product Manual...
Digital Inputs. Press key until you see PID SET3 or Lower/Display PID SET4 then press or to switch between UDC3500 Universal Digital Controller Product Manual 3/07...
Page 159
Similarly, the controller switches between the other PID sets based upon the values configured for SW VAL 2 and SW VAL 3. ATTENTION Other prompts affected: SW VALUE, SW VAL 2 and SW VAL 3. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 160
Similarly, the controller switches between the other PID sets based upon the values configured for SW VAL 2 and SW VAL 3. ATTENTION Other prompts affected: SW VALUE, SW VAL 2 and SW VAL 3. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 161
INPUT 4—Remote Setpoint using Input 4. INPUT 3 INPUT 5—Remote Setpoint using Input 5. INPUT 4 INPUT ALGORITHM 1—Remote Setpoint using INPUT 5 Input Algorithm 1. IN AL1 INPUT ALGORITHM 2—Remote Setpoint using Input Algorithm 2. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 162
Local Setpoint used before power down displayed. A RSP AUTOMATIC MODE, LAST RSP—At power-up, the controller will use automatic mode with the last Remote Setpoint used before power down displayed. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 163
HIGH OUTPUT LIMIT—This is the highest value of output beyond which you do not want the controller automatic output to exceed. 0 % to 100 % For relay output types. –5 % to 105 % For current output types 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 164
Math A, Math B, Math C or Math D, then the SP HiLIM and SP LoLIM values can be set anywhere between –999 and 9999 and are not limited to the CALC HI and CALC LOW values. UDC3500 Universal Digital Controller Product Manual 3/07...
Second Current Output or Third Current Output to be a specific selection with desired scaling. The UDC3500 has three current outputs, two of which are configured in this Set Up Group. The UDC3500 has four digital inputs. Loop assignments are made in this Set Up Group.
Page 166
Deviation Display = –150 °F, which is –150 / 2000 = –7.5% of the Deviation Range, so Second Current Output = 50% – 7.5% = 42.5% which is 0.425 X 16 mA + 4 mA = 10.8 mA UDC3500 Universal Digital Controller Product Manual 3/07...
Page 167
(such as PID A). When using one of the characterizers, OUTPUT 2 is the output value for Loop 2 after it passes through the characterizer. CB OUTL2 is the control block output before it passes through the characterizer. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 168
LOCAL SETPOINT ONE FOR LOOP 2—Output represents Loop 2 Local Setpoint 1 regardless of active setpoint. RSP LP2 REMOTE SETPOINT FOR LOOP 2—Represents the configured Loop 2 RSP regardless of the active SetPoint for Loop 2. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 169
4-20mA output or 0-20mA 0-20mA output operation without the need for recalibration of the instrument. ATTENTION Changing the Current Output Range will result in the loss of Field Calibration values and will restore Factory Calibration values. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 170
TO 3SP puts the controller into local setpoint 3. TO LOCAL SETPOINT FOUR—Contact closure TO 4SP puts the controller into local setpoint 4. TO DIRECT ACTION—Contact closure selects TO DIR direct controller action. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 171
Program. Upper left character blinks “R”. Reopening the contact has no effect. This selection applies to either loop. ATTENTION When multiple SP Programs are enabled, this configuration is affected by the “SPP A” and “SPP B” configurations below. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 172
Digital Inputs assigned to Loop 2 will also use the AUTO OUT value in the Control Setup Group. ATTENTION Does not apply to Three Position Step Control. TIMER—Contact closure starts timer, if enabled. TIMER Reopening the switch has no effect. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 173
LOOP DISPLAY—Contact closure displays the loop D L1/2 not currently being displayed. Opening contact returns to the original loop display. EXTERNAL RESET FEEDBACK—Contact closure RST FB allows Input 2 to override the internal reset value. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 174
PV is frozen at last value. When switch opens, PV resumes normal operation after 2 seconds. Digital Input SOFTWARE OPTIONS DIGITAL INPUTS—The prompts for following Digital Input selections appear only when the Healthwatch Software Option is installed. Software Options UDC3500 Universal Digital Controller Product Manual 3/07...
Page 175
PLUS DIRECT ACTION—Contact closure selects +TO DIR direct controller action. PLUS SETPOINT 2—Contact closure puts the +TO SP2 controller to Local Setpoint 2. PLUS DISABLE ADAPTIVE TUNE—Contact +DIS AT closure disables Accutune process. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 176
TO RUN, TO HOLD, RERUN, or To BEGIN will control the setpoint program regardless of the loop to which the Digital Input is assigned. UDC3500 Universal Digital Controller Product Manual 3/07...
ATTENTION If there are no IR communications transactions for four minutes, then the IR port automatically shuts down. It can be re-enabled at any time by pressing any key on the front panel. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 178
LEVEL—Determines the mode of local control you want when the controller is shed from the communications link. LAST—SAME MODE LAST The controller will return to the same mode (manual or automatic) that it had before shed. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 179
–20.0 to 20.0 CSP2RATO LOOP 2 COMPUTER SETPOINT RATIO— Computer setpoint ratio for Loop 2. –999. to 9999. CSP2BIAS LOOP 2 COMPUTER SETPOINT BIAS—Computer (engineering units) setpoint bias in Engineering Units for Loop 2. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 180
Loopback test at a time, as the instrument running the Loopback test transmits on the RS-485 bus. The host computer should not be transmitting on the link while the Loopback test is active. UDC3500 Universal Digital Controller Product Manual 3/07...
Configuration 3.24 Alarms Set Up Group Introduction The UDC3500 has four alarms and eight alarm setpoints. Each alarm has its own hysteresis configuration. An alarm is an indication that an event that you have configured (for example—Process Variable) has exceeded one or more alarm limits. There are up to four alarms available.
Page 183
Totalizer Scale Factor: *E4 = 1 x 10 = 10,000 Alarm Type: Totalizer Alarm SP: 400 Alarm High / Low: HIGH Alarm will activate when the Totalizer Value exceeds 400 x 10 = 4,000,000. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 184
Alarm Type is configured for Event On/Off: A1S1 EV ALARM 1 SEGMENT EVENT 1—Select whether you want the alarm type chosen in prompt A1S1TYPE to alarm the beginning or end of a segment in setpoint Ramp/Soak programming. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 185
Same as A1S1 VAL ALARM 2 SETPOINT 1 VALUE—Same as A1S1 VAL. HIGH A2S1 H L ALARM 2 SETPOINT 1 STATE—Same as A1S1 H L. A2S1 EV BEGIN ALARM 2 SEGMENT EVENT 1—Same as A1S1 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 186
(OR condition). See Section 3.29. ATTENTION Not applicable with Relay Duplex or Position Proportional output types unless using Dual Relay PWA. Same as A1S1 VAL A3S2 VAL ALARM 3 SETPOINT 2 VALUE—Same as A1S1 VAL. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 187
ALARM HYSTERESIS FOR ALARM 4—Same as 0.0 to 100.0 % of span or ALHYST4 ALHYST1. full output as appropriate ALM OUT1 LATCHING ALARM OUTPUT 1—Alarm output 1 can be configured to be Latching or Non-latching. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 188
ENABLE message will appear on the lower display whenever an alarm is active. This message can be disabled by pressing the RUN/HOLD key, similar to other diagnostic messages. See Section 7.5 for messages. UDC3500 Universal Digital Controller Product Manual 3/07...
+10.7 seconds per month. Each negative increment represents a clock change of –5.35 seconds per month. These values correspond to a total adjustment range of between +5.5 and –2.75 minutes per month. 3/07 UDC3500 Universal Digital Controller Product Manual...
DIGITAL INPUT 2—Cumulative time Digital Input 2 was closed DIGIN3 DIGITAL INPUT3—Cumulative time Digital Input 3 was closed DIGIN4 DIGITAL INPUT 4—Cumulative time Digital Input 4 was closed MANUAL2 LOOP 2 MANUAL—Cumulative time Loop 2 was in Manual. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 191
GUAR SK GUARANTEED SOAK—Number of times unit has been in guaranteed soak. PWRCYC POWER CYCLE—Number of times unit’s power has cycled off and on. PVRANGE LOOP 1 PV RANGE—Number of times Loop 1’s PV 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 192
COUNTER 1 will be reset COUNT 1 COUNTER 2 will be reset COUNT 2 COUNTER 3 will be reset COUNT 3 ALL COUNTERS will be reset ALL CNT ALL T+C ALL TIMERS AND COUNTERS will be reset UDC3500 Universal Digital Controller Product Manual 3/07...
DEG C DEG C—Degrees Centigrade – Degrees C Annunciator lighted NONE NONE—No temperature annunciators lighted. Upper and Lower Displays will show temperature in Degrees Fahrenheit when inputs are configured for Thermocouple or RTD types. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 194
DISABLE—Disable Diagnostic Messages IDNUMBER 0 to 255 IDENTIFICATION NUMBER—This configuration is used only for uniquely identifying a particular controller over a communications network. The value selected has no effect on how the controller operates. UDC3500 Universal Digital Controller Product Manual 3/07...
Shows the value of Counter 1. COUNTS 1 for output relays 1 to 5) COUNTS 2 Same as COUNTS 1 Shows the value of Counter 2. Same as COUNTS 1 Shows the value of Counter 3. COUNTS 3 3/07 UDC3500 Universal Digital Controller Product Manual...
DAY—Day of Month or Week 1 to 31 When “CALENDR” is configured: Day of the month (NOTE 5) 1 to 7 When “DAYofWK” is configured: Day of the week (Sunday = 1, Saturday = 7) (NOTE 4) UDC3500 Universal Digital Controller Product Manual 3/07...
Page 197
NOTE 5: The range of DAY 1 or DAY 2 is restricted based upon the MONTH 1 or MONTH 2 selection. For example, a selection of APRIL for the MONTH 1 configuration will restrict the DAY 1 configuration to a range of 1 to 30. NOTE 6: Only operates on SP Program #1. 3/07 UDC3500 Universal Digital Controller Product Manual...
These settings can be changed via the Ethernet Configuration Screen as shown in Figure 3-3. See Section 4.32 – Configuring your Ethernet Connection for more information. Figure 3-3 Ethernet Configuration Screen UDC3500 Universal Digital Controller Product Manual 3/07...
Email server, then the SMTP IP Address may generally be found by opening a DOS shell and typing: ping smtp.[your domain name and extension, i.e., “yourisp.com”] 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 200
Real Time Clock option will send Email time-stamped with the current time in the controller. If the SMTP address on your network is changed, such as can happen when a server is replaced, then you must reconfigure the Email SMTP IP address in this instrument to match. UDC3500 Universal Digital Controller Product Manual 3/07...
For SP Program #1 record sheet – see Figure 4-8 PROGRAM2 DISABLE PROGRAM2 For SP Program #2 record sheet – see Figure 4-9 PROGRAM3 PROGRAM3 DISABLE For SP Program #3 record sheet – see Figure 4-10 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 202
ALG 1 INB ALG1 INC PCO SEL DISABLE PCT CO 0.200 PCT H2 ATM PRESS 780.0 ALG1 BIAS INALG2 NONE MATH K2 CALC HI CALC LOW ALG2 INA ALG2 INB ALG2 INC ALG2 BIAS UDC3500 Universal Digital Controller Product Manual 3/07...
Page 203
Y17 VALUE TOTALIZE DISABLE ΣXXXXXXX TOT SCALE TOT SCR UNLOCK Σ RESET? TOT RATE SECOND POLYNOM DISABLE C0 VALUE C1 VALUE C2 X 10 C2 X 10 C2 X 10 C2 X 10 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 204
RATIO 1 1.00 BIAS IN1 FILTER 1 BURNOUT1 NONE EMISSIV1 0.00 IN2 TYPE 0-10mV INPUT 2 XMITTER2 LINEAR IN2 HIGH 1000 IN2 LOW RATIO 2 1.00 BIAS IN2 FILTER 2 BURNOUT2 NONE EMISSIV2 0.00 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 205
REVERSE OUT RATE DISABLE PCT/M UP PCT/M DN OUTHiLIM OUTLoLIM I Hi LIM I Lo LIM DROPOFF DEADBAND OUT HYST FAILMODE NO LATCH FAILSAFE SW FAIL MAN OUT AUTO OUT PBorGAIN GAIN MINorRPM 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 206
NONE Com ADDR ComSTATE DISABLE IR ENABLE DISABLE BAUD 19200 TX DELAY WSFLOAT FP B SHEDENAB DISABLE SHEDTIME SHEDMODE LAST SHEDSP TO LSP UNITS PERCENT CSP RATO CSP BIAS CSP2RATO CSP2BIAS LOOPBACK DISABLE UDC3500 Universal Digital Controller Product Manual 3/07...
Page 207
“ “ “ SET CLK? “ “ “ “ ADJUST TIME 1 DISABLE MAINTNCE TIME 2 DISABLE TIME 3 DISABLE COUNT 1 DISABLE COUNT 2 DISABLE COUNT 3 DISABLE PASSWORD RES TYPE NONE 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 208
ETHERNET AND EMAIL IP Address 10.0.0.2 (Accessible via PIE Subnet Mask 255.255.255.0 Tool) Default Gateway 0.0.0.0 SMTP Address (for Outgoing) 0.0.0.0 To Email 1 From Email 1 To Email 2 From Email 2 UDC3500 Universal Digital Controller Product Manual 3/07...
4.21 Alarm Setpoints 4.22 Three Position Step Control Algorithm 4.23 Setting a Failsafe Output Value for Restart after a Power Loss 4.24 Setting Failsafe Mode 4.25 Carbon Potential, Oxygen and Dewpoint Algorithms 4.26 Healthwatch 3/07 UDC3500 Universal Digital Controller Product Manual...
NONE. Thereafter, that selected number must be used to change the lockout level from something other than NONE. Write the number on the Configuration Record Sheet in the configuration ATTENTION section so you will have a permanent record. UDC3500 Universal Digital Controller Product Manual 3/07...
Timer, Tuning, and SP Ramp are Read only. No other parameters are viewable. See Subsection 3.4 - Tuning Parameters Set Up Group prompts to select one of the above. Security Code (see Subsection 4.3) 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 212
When a key is pressed and the prompt “Key Error” appears in the lower display, it will be for one of the following reasons: • Parameter not available or locked out • Not in setup mode, press key first SET UP • Individual key locked out. UDC3500 Universal Digital Controller Product Manual 3/07...
I—Cascade control (when Loop 1 is displayed) C—Computer setpoint active O—Output override active H—Setpoint Ramp or Setpoint Program in HOLD mode R—Setpoint Ramp or Setpoint Program in RUN mode H and R alternating—Guaranteed Soak in operation 3/07 UDC3500 Universal Digital Controller Product Manual...
Digital Input Selections “PROG LO” and “PROG HI” override the keyboard and force the Program selection per their status (open or closed). When running linked programs, the Setpoint Program Number can be incremented/decremented when in the “HOLD” mode. UDC3500 Universal Digital Controller Product Manual 3/07...
LOWER DISPLAY key. If the underlying condition has not been corrected, then the next time the instrument is powered-down/powered-up, the diagnostic message will return. 3/07 UDC3500 Universal Digital Controller Product Manual...
Refer to Tuning Set Up group to ensure that the selections for Pb or GAIN, RATE T, and I MIN, or I RPM have been entered. Use Accutune to tune the controller; see the procedure in this section. UDC3500 Universal Digital Controller Product Manual 3/07...
In Automatic cascade mode, there are two control loops, with one loop’s output acting as the AUTOMATIC setpoint for the second control loop. There is only one physical output in this mode. CASCADE 3/07 UDC3500 Universal Digital Controller Product Manual...
If LSP tracking is not configured, the local setpoint will not be altered when the transfer is made. 4.8 Setpoints Introduction You can configure the following setpoints for the UDC3500 controller. • One to four Local Setpoints • One to four Local Setpoints plus one Remote Setpoint Refer to Subsection 3.20 –...
• you attempt to change the setpoint while a setpoint ramp is enabled, or • if you attempt to change the setpoint with the setpoint select function key disabled. Appears to the left of the active setpoint 3/07 UDC3500 Universal Digital Controller Product Manual...
Alarm 1 relay. At “TIME-OUT: • Alarm 1 is active • The clock character has stopped moving • The Time display shows either 00:00 or the time-out period depending on the configuration selection UDC3500 Universal Digital Controller Product Manual 3/07...
If the controller determines that the process has appreciable dead time, it will automatically default to use Dahlin Tuning, which produces very conservative tuning constants. The SLOW selection may be useful for TPSC and 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 222
Tuning group, and begins PID control with the correct tuning parameters. This works with any process, including integrating type processes, and allows retuning at a fixed setpoint. UDC3500 Universal Digital Controller Product Manual 3/07...
“NO TUNE” prompt. ATTENTION The Accutune process may be aborted at any time by changing the lower display back to “NoTUNE” or by switching the controller into Manual Mode. 3/07 UDC3500 Universal Digital Controller Product Manual...
PID SET 2. Configuration Check for Duplex See Subsection 3.10 – Accutune Set Up Group for details. Make sure: • TUNE has been enabled • DUPLEX has been configured to Manual, Automatic or Disabled UDC3500 Universal Digital Controller Product Manual 3/07...
Tuning in operation Lower Upper display will show a “T” as Display long as ACCUTUNE process is operating. When process completes, tuning parameters are calculated and lower display will show “NO TUNE” prompt. 3/07 UDC3500 Universal Digital Controller Product Manual...
Tuning in operation Lower Upper display will show a “T” as Display long as ACCUTUNE process is operating. When process completes, tuning parameters are calculated and lower display will show “NO TUNE” prompt. UDC3500 Universal Digital Controller Product Manual 3/07...
Tuning in operation Upper display will show a “T” as Lower Display long as ACCUTUNE process is operating. When process completes, tuning parameters are calculated and lower display will show “NO TUNE” prompt. 3/07 UDC3500 Universal Digital Controller Product Manual...
Output insufficient to get to SP value. ATTENTION This error will cause the controller to switch from Automatic to Manual Mode. The output is then set to the value present at the beginning of UDC3500 Universal Digital Controller Product Manual 3/07...
Enabled or Disabled as required by the application to work with the Accutune algorithm. Fuzzy Tune should not be enabled for processes that have an appreciable amount of deadtime. Configuration To configure this item, refer to Section 3 – Configuration: 3/07 UDC3500 Universal Digital Controller Product Manual...
To select the type of function. Available selections are: Function 1 ONLY—1 set of constants 2KEYBD—2 sets, keyboard selectable 2PV SW—2 sets, auto switch at PV value 2SP SW—2 sets, auto switch at SP value UDC3500 Universal Digital Controller Product Manual 3/07...
Upper Display = (the PV value) Lower Display = PIDS X (X= 1 or 2) To change PID SET 1 to PID SET2 or Vice Versa. You can use Accutune on each set. To accept changes. Lower Display 3/07 UDC3500 Universal Digital Controller Product Manual...
Relative Humidity Summer Hi Select Lo Select √ Multiply Divide √ Multiply Multiply Divide Multiply Feedforward Multiplier Carbon Potential (several types) Oxygen Dewpoint The formulas for these selections are given in Section 3.11. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 233
Alarm on totalizer value The alarm type configuration includes an Alarm on Totalizer value. This allows an alarm setpoint value to be used to cause an alarm when exceeded. The alarm setpoint represents 3/07 UDC3500 Universal Digital Controller Product Manual...
Local/Remote Setpoint, then pushing the key or Man/Auto key, respectively, will result in a key error SP Select diagnostic display. However, the key is permitted during Man/Auto communications when the Host computer has mode control. UDC3500 Universal Digital Controller Product Manual 3/07...
Suspends setpoint program or setpoint ramp operation. Contact open runs the ramp/program from the Hold point unless the Ramp/Program was not previously started via the key. Run/Hold This selection applies to either loop. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 238
Allows Output 2 to override Output 1. blinks Puts the controller into Remote Setpoint. When contact opens, TO RSP SP annunciator blinks the controller returns to former operation, local or remote Lower display shows setpoint. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 239
Reset Healthwatch Counter 2 to zero. REST C2 Reset Healthwatch Counter 3 to zero. REST C3 R ALL C Reset all Healthwatch Counters to zero. R ALLTC Reset all Healthwatch Timers and Counters to zero. 3/07 UDC3500 Universal Digital Controller Product Manual...
Action Disabled means that the digital input or digital combination parameter is configured but the action cannot occur when the digital input is active because the selected parameter is disabled. UDC3500 Universal Digital Controller Product Manual 3/07...
DIG IN1 = ToPID2 action will occur. DIG1 COM = +ToSP2 PID SETS = 2KEYBD LSP’S =TWO Instrument is correctly configured for both actions and thus will perform as desired when DIG IN1 is active. 3/07 UDC3500 Universal Digital Controller Product Manual...
Input 1 is typically the PV of some upper controller and Input 2 is typically that controller’s output. If the upper control fails, the upper device or some watchdog opens the digital input switch and UDC3500 back-up PID A control is active. When the upper control reactivates, the digital input switch is closed and the Auto/Manual Station becomes a repeater station and allows the upper control output signal to pass through.
Page 244
Until you see: Func Loop 1/2 Algorithm Upper Display = (available selections) Lower Display = CONT ALG To select: Select PID A PID A— PID A This is defining the back-up control algorithm. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 245
• In the ALGORTHM set up list, do not select CONT ALG as PID B, ON-OFF, or 3PSTEP. • In the Display menu when PIDSET # is displayed, DO NOT change the selection. 3/07 UDC3500 Universal Digital Controller Product Manual...
Current output on Loop 2 requires that either Second Current Output or Third Current Output be installed. • Loop 2 relay output is always dedicated to relay outputs 3 and 4. • No Three Position Step output on Loop 2. UDC3500 Universal Digital Controller Product Manual 3/07...
The following rules apply for internal Cascade control: • Loop 2 is the primary (external) loop. • Loop 1 is the secondary (internal or slave) loop. • Loop 1 Remote Setpoint is fixed as the Loop 2 output. 3/07 UDC3500 Universal Digital Controller Product Manual...
This tracking is done in the direction opposite to the Override Select configuration; i.e., for High Select, the unselected output tracks within 5 % of the lower output, and vice versa for Low Select. UDC3500 Universal Digital Controller Product Manual 3/07...
RSP appears in the lower display then release the key to select remote SP Select setpoint. Switching between automatic and manual mode on either loop will not affect the internal Cascade indication. UDC3500 Universal Digital Controller Product Manual 3/07...
Output 1 and Output 2 (Lo Select) to appear at Output 1 terminals to drive the final control element. Refer to Section 5.12 for Override rules and block diagram. Override prompts appear under the Algorithm Set Up group, function prompt OUT OVRD. 3/07 UDC3500 Universal Digital Controller Product Manual...
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - A4S2 VAL = Alarm 4, Setpoint 2 Value NOTES: With Three position step control, alarms set for “output” will not function. MANUAL, RSP, and F’SAFE selections do not have setpoint values. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 253
Event (A1S1 EV) is configured for END, then this alarm will deactivate when the Setpoint Program reaches the end of Segment 5. ATTENTION Some other alarm configuration must first turn the alarm on before this configuration can turn it off. 3/07 UDC3500 Universal Digital Controller Product Manual...
POS XX.X. The TPSC algorithm does not use this value; it is only used for display purposes. The slidewire must be calibrated for this display to operate correctly. See Section 6.5. UDC3500 Universal Digital Controller Product Manual 3/07...
Lower Display = F’SAFE Select a value To select a failsafe output value in the upper display Return to Normal Lower At power up, the output will go to the value set. Display Display 3/07 UDC3500 Universal Digital Controller Product Manual...
Instruments with Two Loops may use Loop 1 to control the Carbon/Oxygen/Dewpoint of the oven while Loop 2 may use the temperature measured by Input 2 to control the temperature of the oven. For this application, PV Source in the Control Set Up Group UDC3500 Universal Digital Controller Product Manual 3/07...
Page 257
The controller computes the atmosphere’s actual carbon potential from these inputs and compares the computed value with the desired setpoint. An on-off or PID control algorithm determines the controller output necessary to keep the actual carbon potential at the setpoint. 3/07 UDC3500 Universal Digital Controller Product Manual...
K, R or S thermocouple input. All calculations are performed by the Controller with Percent Oxygen shown as the PV display. The actual reading of each analog input is available for viewing on the lower display. UDC3500 Universal Digital Controller Product Manual 3/07...
1 to 255 minutes. (Subsection 4.29) • SP PROG – a ramp/soak profile in a 20-segment program. (Subsection 4.30) This section explains the operation of each selection and configuration reference where necessary. 3/07 UDC3500 Universal Digital Controller Product Manual...
When you have configured a SETPOINT RAMP, the ramp will occur between the current local setpoint and a final local setpoint over a time interval of from 1 to 255 minutes. You can RUN or HOLD the ramp at any time. UDC3500 Universal Digital Controller Product Manual 3/07...
The ramp is placed in hold at the beginning. Configure the mode at Set Up Group “CONTROL”, function prompt “PWR MODE”. See Subsection 3.20 – CONTROL SETUP GROUP Prompts. 3/07 UDC3500 Universal Digital Controller Product Manual...
Refer to the example in Figure 4-7. For each SP Program, draw a Ramp/Soak Profile on the worksheets provided and fill in the information for each segment. This will give you a record of how the programs were developed. Operation Refer to Table 4-36 Run/Monitor the program. UDC3500 Universal Digital Controller Product Manual 3/07...
Soak segment in the program, then the first Ramp segment is skipped and the program will restart at the beginning of the first Soak segment in the 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 264
This selection of time or rate is made at prompt “RAMPUNIT”. Set this prompt before entering any Ramp values. ATTENTION Entering “0” implies an immediate step change in setpoint to the next soak. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 265
The decimal location used here corresponds decimal configuration chosen in the Display Set up group. 3/07 UDC3500 Universal Digital Controller Product Manual...
0 hr:30 min. Soak SP SG11RAMP Ramp Time 3 hr:30 min. SEG2 SP SEG2TIME Soak Time 1 hr:30 min. SG12 SP Soak SP SEG3RAMP Ramp Time 1 hr. SG12TIME Soak Time 0 hr:30 min. UDC3500 Universal Digital Controller Product Manual 3/07...
Lower Display = XXRAHH.MM for Ramps or = Display segment number XXSKHH.MM for Soaks until you see and time Time remaining in the SEGMENT in hours and minutes. XX = The segment number, 1 to 12. Continued 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 276
Opening the contact will cause the Controller to revert to its original state. Setpoint Program Event Alarms See the example in Section 0 for help in configuring Alarm Events based upon segments in the Setpoint Program. UDC3500 Universal Digital Controller Product Manual 3/07...
OP status for that output is always “OK.” The “Alarms” and “Digital Inputs” buttons allow you to see the current status of each alarm setpoint and digital input. Figure 4-12 Loop Data Maintenance Screen 3/07 UDC3500 Universal Digital Controller Product Manual...
“Alarm Off” column indicates that the alarm has never been inactive. See Section 3.24 for other information about configuring Alarms. Figure 4-13 Alarm Details Maintenance Screen UDC3500 Universal Digital Controller Product Manual 3/07...
Digital Input is disabled. Highlighted Digital Inputs are currently active. An asterisk (*) indicates that the alarm has changed state since the last communications transaction. Figure 4-14 Digital Inputs Details Maintenance Screen 3/07 UDC3500 Universal Digital Controller Product Manual...
Real Time Clock Option, then pressing the “Diagnostics” button will show the time and dates that the problem occurred and when it was cleared. Figure 4-15 Status Data Maintenance Screen UDC3500 Universal Digital Controller Product Manual 3/07...
“Cleared” column indicates that the problem still exists. Essentially, this screen shows the same diagnostic messages as available on the controller via the lower display window. See Section 7 for other information about Troubleshooting and Diagnostics. Figure 4-16 Diagnostic History Maintenance Screen 3/07 UDC3500 Universal Digital Controller Product Manual...
Ethernet or via Infrared communications. Not all diagnostic messages are available via Ethernet Communications. For example, if the Ethernet cable is unplugged, then the instrument cannot send up the “EUNPLGED” diagnostic message via Ethernet. Figure 4-17 Ethernet Status Maintenance Screen UDC3500 Universal Digital Controller Product Manual 3/07...
“Save” button. See Section 3.26 for other information about Healthwatch. The Reset button calls up a menu allowing individual timers and counters to be reset back to zero. See next page. Figure 4-18 Healthwatch Data Maintenance Screen 3/07 UDC3500 Universal Digital Controller Product Manual...
Healthwatch Reset screen allows you to reset the various Timers and Counters back to zero. The Password is configured as part of the Maintenance Set Up Group. See Section 3.26. Figure 4-19 Healthwatch Data Reset Screen UDC3500 Universal Digital Controller Product Manual 3/07...
Totalizer. The Reset button sets the Totalizer Value back to zero. See Section 3.12 for other information about the Totalizer option. Figure 4-20 Totalizer Maintenance Screen 3/07 UDC3500 Universal Digital Controller Product Manual...
Ethernet Software in the instrument was last modified. Instruments with the Real Time Clock option will send Email time-stamped with the current time in the controller. Figure 4-21 Real Time Clock Maintenance Screen UDC3500 Universal Digital Controller Product Manual 3/07...
3, then configure your Communications Type as “Infrared” and your IR address to 3 as shown below. Select “PC COMM Setup”, then select “Infrared”. Figure 4-22 IR Communications Address 3/07 UDC3500 Universal Digital Controller Product Manual...
Once the upload is complete, click on the “Ethernet & Email” Group. Configure your Ethernet and Email parameters per Section 3.30. Once you have changed the Ethernet settings and downloaded them to your controller, you will now be able to communicate with it via Ethernet. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 289
Once you have made an Ethernet connection between your PC and the controller, then change the Local Area Network (LAN) settings on your PC to be as follows: IP Address: 10.0.0.3 Subnet Mask: 255.255.255.0 Default Gateway: 10.0.0.1 3/07 UDC3500 Universal Digital Controller Product Manual...
Open your P.I.E. Tool program and select “PC Comm Setup”. . Now configure your “Communication Type” to Ethernet and your Ethernet address to 10.0.0.2 as shown in Figure 4-24. Figure 4-24 Ethernet Communications Address UDC3500 Universal Digital Controller Product Manual 3/07...
On some PCs and LANs, it is possible to simply allow the PC to get these settings automatically via the DHCP server. Contact your Information Technologies (IT) representative to see if this is available on your PC. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 292
Monitoring and Operating the Controller UDC3500 Universal Digital Controller Product Manual 3/07...
The following topics are covered in this section. TOPIC See Page 5.1 Overview 5.2 Minimum and Maximum Range Values 5.3 Preliminary Information 5.4 Input Set Up Wiring 5.5 Input Calibration Procedure 5.6 Restore Input Factory Calibration 3/07 UDC3500 Universal Digital Controller Product Manual...
–18 to 1300 –0.461 mV 47.513 mV NIC H NIC L 0 to 1472 –18 to 800 -0.461 mV 28.455 mV PLAT H 32 to 2516 0 to 1380 0.000 mV 54.798 mV UDC3500 Universal Digital Controller Product Manual 3/07...
Page 295
Field Calibration of the input, with the range value limits being –4 mV to +16 mV for the zero and span values. See Table 5-7. ** The range values for Radiamatic Type RI are customer configurable within the limits shown. 3/07 UDC3500 Universal Digital Controller Product Manual...
A calibrating device with at least ± 0.02 % accuracy for use as a Inputs (T/C Source) signal source such as a millivolt source. • Thermocouple extension wire that corresponds with the type of thermocouple that will be used with controller input. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 297
• Two insulated copper leads for connecting the calibrator to the controller. • Place current source at zero before switching ON. • Do not switch current sources OFF/ON while connected to the instrument. 3/07 UDC3500 Universal Digital Controller Product Manual...
Connect the thermocouple extension wires to the terminals for the input to be calibrated. See Figure 5-3. Input 3 C/J S e ns ors Input 2 Thermocouple Input 1 Source Thermocouple Extension Wire Figure 5-3 Wiring Connections for Thermocouple Inputs Using a Thermocouple Source 3/07 UDC3500 Universal Digital Controller Product Manual...
Table 5-1. Determine the proper zero and span resistance settings prior to attaching the Decade Box to the instrument. For best accuracy, measure with the DMM connected to the wire ends rather than directly to the Decade Box. UDC3500 Universal Digital Controller Product Manual 3/07...
(this can be rounded off to –1.54 millivolts without significant loss of accuracy). • The span calibration voltage is thus 17.188 minus 12.568 millivolts or +4.62 millivolts. • Use –1.54 millivolts for the Zero calibration value and +4.62 millivolts for the Span calibration value. UDC3500 Universal Digital Controller Product Manual 3/07...
Following calibration, turn off the current source prior to disconnecting it from the instrument. Input 3 250 ohms 250 ohms Input 2 Milliampere Input 1 Source 250 ohms Figure 5-7 Wiring Connections for Milliampere Inputs UDC3500 Universal Digital Controller Product Manual 3/07...
Terminals for Input 3 are 29 (+) and 30 (-) Terminals for Input 4 are 31 (+) and 33 (-) Terminals for Input 5 are 28 (+) and 30 (-) Figure 5-8 Wiring Connections for Dual High Level Voltage Inputs 3/07 UDC3500 Universal Digital Controller Product Manual...
Terminals for Input 3 are 29 (+) and 30 (-) Terminals for Input 4 are 31 (+) and 33 (-) Terminals for Input 5 are 28 (+) and 30 (-) Figure 5-9 Wiring Connections for Dual High Level Milliampere Inputs UDC3500 Universal Digital Controller Product Manual 3/07...
0 % range value for your particular input sensor. See Table 5-1 for Voltage, Degrees, or Resistance equivalents for 0 % range values. • Wait 15 seconds, then go to the next step. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 308
Input Bias setting. See Section 3.15 (Input 1), Section 3.16 (Input 2) or Section 3.17 (Input 3). Exit the Func The controller stores the calibration constants and exits the Loop 1/2 Calibration Mode calibration mode. then Lower Display UDC3500 Universal Digital Controller Product Manual 3/07...
Scroll through Func returns to: Loop 1/2 Functions Upper Display = the new selection Lower Display = INn TYPE n = 1 to 5 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 310
Normal operating mode. Return to Normal Lower Display Operation The factory calibration will be restored. If the problem is not corrected, contact the Honeywell Technical Assistance Center at 1- 800-423-9883 USA and Canada UDC3500 Universal Digital Controller Product Manual 3/07...
6.6 Restore Factory Output Calibration WARNING—SHOCK HAZARD OUTPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION. 3/07 UDC3500 Universal Digital Controller Product Manual...
Tag and disconnect the field wiring, at the rear of the controller, from terminals 5 (+) and 6 (–). See Figure 6-1. Connect a milliammeter across these terminals. Milliammeter L2/N Curre nt Output 1 Figure 6-1 Wiring Connections for Calibrating the First Current Output UDC3500 Universal Digital Controller Product Manual 3/07...
Normally, this will be the setting that produces 20 mA. Exit the Func The controller stores the span value. Loop 1/2 Calibration Mode Lower To exit the calibration mode. Display 3/07 UDC3500 Universal Digital Controller Product Manual...
Tag and disconnect the field wiring, at the rear of the controller, from terminals 24 (+) and 25 (–). See Figure 6-2. Connect a milliammeter across these terminals. Milliammeter Curre nt Output 2 Figure 6-2 Wiring Connections for Calibrating the Second Current Output UDC3500 Universal Digital Controller Product Manual 3/07...
100 % output is read on the milliammeter. Normally, this will be the setting that produces 20 mA. Exit the Func The controller stores the span value. Loop 1/2 Calibration Mode Lower To exit the calibration mode. Display 3/07 UDC3500 Universal Digital Controller Product Manual...
Tag and disconnect the field wiring, at the rear of the controller, from terminals 7 (+) and 9 (–). See Figure 6-3. Connect a milliammeter across these terminals. Milliammeter L2/N Curre nt Output 3 Figure 6-3 Wiring Connections for Calibrating Third Current Output UDC3500 Universal Digital Controller Product Manual 3/07...
100 % output is read on the milliammeter. Normally, this will be the setting that produces 20 mA. Exit the Func The controller stores the span value. Loop 1/2 Calibration Mode Lower To exit the calibration mode. Display 3/07 UDC3500 Universal Digital Controller Product Manual...
Proportional Control, the Output algorithm must also be configured for “POSPROP”. The Motor Time must be entered in the Output Algorithm Group for both Position Proportional or for Three Position Step control. See Section 3.14 for details. UDC3500 Universal Digital Controller Product Manual 3/07...
Set 0 % value Loop 1/2 Upper Display = (counts of slidewire feedback 0-3000) Lower Display = ZERO VAL When the motor stops, the display should stop counting. When that happens, go to Step 7. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 320
For manual calibration, the motor does not move from its position prior to the start of Position Proportional calibration. Exit the Calibration Mode The controller will store the 100 % value. Func Loop 1/2 To exit the calibration mode Lower Display Setup UDC3500 Universal Digital Controller Product Manual 3/07...
Scroll through Func returns to: Loop 1/2 Functions Upper Display = the new selection Lower Display = CO RANGE 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 322
Normal operating mode. Return to Normal Lower Display Operation The factory calibration will be restored. If the problem is not corrected, contact the Honeywell Technical Assistance Center at 1- 800-423-9883 USA and Canada UDC3500 Universal Digital Controller Product Manual 3/07...
An error message can occur: • At power-up. See Subsection 7.3. • When the Status Tests are requested. See Subsection 7.4. • During continuous background tests while in normal operation. See Subsection 7.5. UDC3500 Universal Digital Controller Product Manual 3/07...
If it is determined that a hardware problem exists, a replacement controller or part will be shipped with instructions for returning the defective unit. Do not return your controller without authorization from Honeywell’s Technical Assistance Center or until the replacement has been received.
Lower Display = TEST Cycle through all Func Continue through the rest of the prompts until you see: STATUS Set Up Loop 1/2 Group prompts Upper Display = READ Lower Display = STATUS UDC3500 Universal Digital Controller Product Manual 3/07...
EEPROM. 4) Run through the STATUS check a second time to see if the error cleared. If error did not clear, then power cycle the instrument. If the message reappears, replace the instrument. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 328
Same as INP1RNG above. INP4 RNG INP4FAIL Two consecutive failures of input 4 Same as INP1FAIL above. integration; i.e., cannot make analog to digital conversion. INP5 RNG Input 5 out of range. Same as INP1RNG above. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 329
This message will also be generated if the resistance of the wires used to connect the thermocouple to the instrument is above 180 ohms (90 ohms per leg). 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 330
Same as ALRM1SP1. ALRM1SP2 Alarm 2 Setpoint 1 is active. Same as ALRM1SP1. ALRM2SP1 Alarm 2 Setpoint 2 is active. Same as ALRM1SP1. ALRM2SP2 Alarm 3 Setpoint 1 is active. Same as ALRM1SP1. ALRM3SP1 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 331
How to Correct the Problem Display Alarm 3 Setpoint 2 is active. Same as ALRM1SP1. ALRM3SP2 Alarm 4 Setpoint 1 is active. Same as ALRM1SP1. ALRM4SP1 Alarm 4 Setpoint 2 is active. Same as ALRM1SP1. ALRM4SP2 3/07 UDC3500 Universal Digital Controller Product Manual...
Output Output Displayed Controller Third Current 7.7.2 Output Output Output disagrees with disagrees with Third Current Displayed Third Output Current Output Display does not change when a key is pressed Keyboard 7.7.7 Malfunction UDC3500 Universal Digital Controller Product Manual 3/07...
Equipment needed You will need the following equipment in order to troubleshoot the symptoms listed: • Multimeter – Capable of measuring millivolts, volts, milliamps and resistance. • Calibration sources – T/C, mV, Volt, etc. 3/07 UDC3500 Universal Digital Controller Product Manual...
Second Current Output: Test for Change Options Set Up group function prompt operation. CUR2 OUT = OUTPUT Make the Current #2 Options Set up group function prompt CO RANGE = 4–20 Go to Step 4 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 335
Field Calibrate the output. Refer to Section 1 – Output Calibration for details. Output works correctly: Finished Output does not work correctly: Go to Step 7. Change Current Output board. Installation instructions provided with new board. 3/07 UDC3500 Universal Digital Controller Product Manual...
Output value moves in the wrong direction: This means that the motor or the slidewire or both are incorrectly wired. Check the motor manufacturer’s wiring diagram and then refer to Section 2 – Installation to rewire the controller. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 337
W1 position and recalibrate the instrument per Section 1 – Output Calibration. If the Jumper is in the W1 position, then replace the Input 3 board. Installation instructions supplied with the new board. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 338
“OUT 2” indicator changes state. Relays measure correctly: Check motor. Refer to manufacturer’s instructions. Relays do not measure correctly: Go to Step Replace the Dual Relay Board. Installation instructions supplied with the new board. UDC3500 Universal Digital Controller Product Manual 3/07...
Contact should change state. 0 % open, 100 % closed. Listen for a click from the relay when the OUT1 or OUT3 indicator changes state. Check relay. Change relay. Change relay board. Installation instructions supplied with the new board. 3/07 UDC3500 Universal Digital Controller Product Manual...
Use a DC milliammeter at the rear terminals to verify the output. Recalibrate the controller. Refer to Section 1 – Output Calibration for details. Change Current Output or Relay Installation instructions supplied with new board. board. UDC3500 Universal Digital Controller Product Manual 3/07...
Make sure the NO or NC contact wiring is correct. Refer to Section 2 – Installation for relay contact information. Change the relay and/or the Installation instructions supplied with the relay output board. new relay or board. 3/07 UDC3500 Universal Digital Controller Product Manual...
After fifteen seconds, the unit returns to normal operation. Replace the Display/Keyboard Refer to “Parts Replacement Assembly if any keys do not Procedures” in this section. function. UDC3500 Universal Digital Controller Product Manual 3/07...
Section 5.2. Change the Input Type in order See Section 5.6. to restore Factory Calibration. Replace Input Board. Installation instructions provided with new board. Replace Controller. 3/07 UDC3500 Universal Digital Controller Product Manual...
If you see FAIL, go to Step 4. If you see PASS, then the problem is most likely not in the instrument, but somewhere else in the network. Reconnect the communications cable and then go to Step 7. UDC3500 Universal Digital Controller Product Manual 3/07...
Page 345
See Section 2.7 for wiring diagrams. termination resistor. There should be a reading equivalent to the value of the termination resistors. If not, replace termination resistors. Check the rest of the Network. 3/07 UDC3500 Universal Digital Controller Product Manual...
MAC address shown on the label on your instrument’s case to be the same as the MAC address shown on your new board. Change Controller UDC3500 Universal Digital Controller Product Manual 3/07...
MAC address shown on the label on your instrument’s case to be the same as the MAC address shown on your new board. Change Controller 3/07 UDC3500 Universal Digital Controller Product Manual...
The instrument configuration will now be the same as it was when the instrument left the factory and all user- entered configurations since that time have been overwritten. UDC3500 Universal Digital Controller Product Manual 3/07...
Func-Loop 1/2 “XXXX” “ENTER2”. Write this number down. Press the key. The instrument will now display Func-Loop 1/2 “XXXX” “ENTER3”. Write this number down. Write down the Model and Serial Numbers of your instrument. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 350
5. Purchase order number. With this information, a new code number set will be generated for your instrument(s). When you have the new code number set provided by Honeywell, repeat steps 1 to 6. Press the key. The instrument will now display Func-Loop 1/2 “XXXX”...
Exploded View Introduction Figure 8-1 is an exploded view of the UDC3500 Controller. Each part is labeled with a key number. The part numbers are listed by key number in Table 8-1. Parts not shown are listed in Table 8-2.
Pry just enough to release it, otherwise you’ll bend or break the tab . If you break or bend the tab and can’t reattach the front snugly, you’ll need to reattach the front using the 4 NEMA4 screws provided. See Section 2.5 Mounting. 3/07 UDC3500 Universal Digital Controller Product Manual...
Function codes 20 and 21 use the RS422/485 tag IDs for accessing configuration and process-related data. These tags are fully explained in Section 10. The tag IDs represent the register addresses used in the Request Message. UDC3500 Universal Digital Controller Product Manual 3/07...
Integer data is represented in sixteen bits and is transferred high byte first. Floating point data is transferred in IEEE 32-bit format. The register count definitions are: 0001 = Integer Data 0002 = Floating Point Data 3/07 UDC3500 Universal Digital Controller Product Manual...
The Data Byte Count is the number of data bytes of the sub response including the Reference Type but not including itself. A floating point sub response has four bytes of data and one byte representing the reference type making the data byte count equal to five. UDC3500 Universal Digital Controller Product Manual 3/07...
Address(es) (Decimal) (Hex) 001 to 127 0001 to 007F analog formatted data (2 registers – IEEE 32-bit floating point) 128 to 255 0080 to 00FF integer formatted data (1 register – 16-bit integer) 3/07 UDC3500 Universal Digital Controller Product Manual...
For Infrared Transactions, add three BOFs (C0hex) at the beginning of each message and one EOF (Ffhex) at the end of each message. Reference Type Definitions The Reference Type definition is always 06. See examples in Subsection 9.4.1 UDC3500 Universal Digital Controller Product Manual 3/07...
These registers do not have restrictions on the number of writes. ID Tag Register Number UDC Usage (7Dh) Computer Setpoint Restrictions on Parameter Numbers in One Message The maximum number of writeable parameters per write request is 1. 3/07 UDC3500 Universal Digital Controller Product Manual...
This is the response to the above request. Response Message (The response is an echo of the request) 02 15 0B 06 00 01 00 02 00 02 3F C0 00 00 (CRC16) UDC3500 Universal Digital Controller Product Manual 3/07...
10,000 times. In order not to exceed this number, it is strongly recommended that configurations that change rapidly such as Computer Setpoint use the Override feature, which does not affect non-volatile memory. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 364
WRITE communications transaction initiated by the Host Computer until the operator completes accessing the EEROM. This only affects WRITE commands, READ commands will still be processed normally. Also, if the operator changes a setpoint value via the keyboard but does not save this UDC3500 Universal Digital Controller Product Manual 3/07...
Page 365
MODBUS READ communication transactions are not affected, the controller will respond with a normal message to any READ command during the 15 second period. 3/07 UDC3500 Universal Digital Controller Product Manual...
PV Range High 0037 –999.0 to +9999 Loop1 in Engineering Units PV Range Low 0136 –999.0 to +9999 Loop2 in Engineering Units PV Range High 0137 –999.0 to +9999 Loop2 in Engineering Units UDC3500 Universal Digital Controller Product Manual 3/07...
Local Setpoint #2 0135 Value within the setpoint Loop2 range limits Local Setpoint #3 0174 Value within the setpoint Loop2 range limits Local Setpoint #4 0170 Value within the setpoint Loop2 range limits 3/07 UDC3500 Universal Digital Controller Product Manual...
21. Any data value can be written because it is ignored. When SP is overridden, the upper display becomes “C” momentarily, and the lower display shows the CSP value as CSP XXXX. 3/07 UDC3500 Universal Digital Controller Product Manual...
4002 16386 0.00 to 10.00 Note 1 Reset #3 4003 16387 0.02 to 50.00 Note 1 Gain #4 or PB #4 4004 16388 0.001 to 1000 Gain Note 1 0.1 to 9999 PB UDC3500 Universal Digital Controller Product Manual 3/07...
Page 375
Run/Hold Key 00EE 0 = Disabled Lockout 1 = Enabled Setpoint Key 00ED 0 = Disabled Lockout 1 = Enabled NOTE 1: Writes to these locations are not available when Accutune is enabled. 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 404
Engineering Units PV Range High 0037 –999.0 to +9999 in Engineering Units PV Range Low 0136 –999.0 to +9999 Loop2 in Engineering Units PV Range High 0137 –999.0 to +9999 Loop2 in Engineering Units UDC3500 Universal Digital Controller Product Manual 3/07...
Page 405
0 = Manual Monoxide 1 = On Line (via Input 3 only) Percent Carbon 002E 0.02 to 0.350 Monoxide Value Atmospheric 0018 590 to 760 Pressure Percent 0022 1 to 99 (% H2) Hydrogen 3/07 UDC3500 Universal Digital Controller Product Manual...
13 = Gate Out 5 14 = FIX ON 15 = FIX OFF 16 = MA MODE 17 = LR SPL1 18 = ADAPT1 19 = MA MODE2 20 = LR SPL2 21 = ADAPT2 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 412
8 = Loop 2 PV 9 = Loop 2 SP Logic Gate1 K 4064 16484 –999.0 to +9999 Constant Gate 2 InputA 409C 16540 Same as ID 152 (OR, NOR, AND, NAND, X OR, X NOR) UDC3500 Universal Digital Controller Product Manual 3/07...
Page 413
Same as ID 172 LT A or B GT A) Logic Gate4 K 4067 16487 –999.0 to +9999 Constant Gate 5 InputA 40A8 16552 Same as ID 152 (OR, NOR, AND, NAND, X OR, X NOR) 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 414
409E 16542 Same as ID 154 Gate 3 Out 40A2 16546 Same as ID 154 Gate 4 Out 40A6 16550 Same as ID 154 Gate 5 Out 40AA 16554 Same as ID 154 UDC3500 Universal Digital Controller Product Manual 3/07...
Action Loop2 1 = 1 ON 2 OFF 2 = 1 OFF 2 ON 3 = 1 ON 2 ON Current 0199 0 = 100% Range for 1 = 50% Current Duplex Loop2 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 416
Range Current 1 0064 Within the range of the Low Scaling selected variable in ID 242 Factor Current 1 0065 Within the range of the High Scaling selected variable in ID 242 Factor UDC3500 Universal Digital Controller Product Manual 3/07...
PID3 to PID4 (used with ID 172 ) Local Setpoint 00AD 0 = One Local Setpoint Source (Number of 1 = Two Local Setpoints LSPs) 2 = Three Local Setpoints 3 = Four LSP 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 428
0.00 to 9999% per minute High Output Limit 000E –5 to 105% of output Low Output Limit 000F –5 to 105% of output High Integral Limit 0010 –5 to 105% Low Integral Limit 0011 –5 to 105% UDC3500 Universal Digital Controller Product Manual 3/07...
Page 429
(100%) Manual Output 0071 0 to 100% Automatic Output 0072 0 to 100% Proportional Band 0094 0 = Gain Units 1 = Proportional band Reset Units 0095 0 = Minutes 1 = RPM 3/07 UDC3500 Universal Digital Controller Product Manual...
Within the PV Range in Switchover Value engineering units PID2 to PID3 (used with ID 172 ) Automatic Loop2 010B Within the PV Range in Switchover Value engineering units PID3 to PID4 (used with ID 172 ) UDC3500 Universal Digital Controller Product Manual 3/07...
Page 431
0.00 to 9999% per minute Output Rate Down 016F –5 to 105% of output High Output Limit 010E –5 to 105% of output Low Output Limit 010F –5 to 105% High Integral Limit 0110 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 432
–5 to +25.0% Output Deadband for 0102 Time Duplex –5 to 105% Output Drop Off 0114 Limit 0 = Latching Failsafe Mode 019F 1 = Non latching 0 to 100% Failsafe Output 0128 Level UDC3500 Universal Digital Controller Product Manual 3/07...
ID 134 Factor Current Output 2 0032 Within the range of the High Scaling selected variable in ID 134 Factor Current Output 2 00EB 0 = 4-20 mA Range 1 = 0-20 mA 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 434
ID 246 Factor Current Output 3 0057 Within the range of the High Scaling selected variable in ID 134 Factor Current Output 3 00F7 0 = 4-20 mA Range 1 = 0-20 mA UDC3500 Universal Digital Controller Product Manual 3/07...
Page 435
37 = Reset T2 38 = Reset T3 39 = R All Timers 40 = Counter 1 41 = Counter 2 42 = Counter 3 43 = Reset all Counters 44 = Reset all Timers 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 436
1 = DI 2 Loop 2 2 = DI 2,3 3 = DI 2,3,4 Digital Inputs Loop 01BD 0 = None 2 Assign 1 = DI 2 2 = DI 2,3 3 = DI 2,3,4 UDC3500 Universal Digital Controller Product Manual 3/07...
Alarm 4 Setpoint 1 0077 Within the range of selected Value parameter or PV span for deviation alarm Alarm 4 Setpoint 2 0073 Within the range of selected Value parameter or PV span for deviation alarm 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 440
Same as 140 Setpoint 2 Type Alarm 2 0090 Same as 140 Setpoint 1 Type Alarm 2 0092 Same as 140 Setpoint 2 Type Alarm 3 408C 16524 Same as 140 Setpoint 1 Type UDC3500 Universal Digital Controller Product Manual 3/07...
Page 441
400D 16397 0.0 to 100% of output or span Hysteresis Alarm 4 400E 16398 0.0 to 100% of output or span Hysteresis Alarm 1 00C8 0 = Non Latching Latching 1 = Latching 3/07 UDC3500 Universal Digital Controller Product Manual...
13 = DI 1 Closed 14 = DI 2 Closed 15 = DI 3 Closed 16 = DI 4 Closed 17 = Man Loop 2 Timer 2 00DC Same as 219 Same as 219 Timer 3 00DD 3/07 UDC3500 Universal Digital Controller Product Manual...
Page 444
6 = Counter 2 7 = Counter 3 8 = All Counters 9 = All Timers and Counters Shows elapsed time of HWM Days 1 406E 16494 Timer 1 in Days. (0 – 9999) UDC3500 Universal Digital Controller Product Manual 3/07...
Page 445
2. 0-9999 ( 1 = 1000 counts for output relays 1 to 5) Shows the value of Counter HWM Counter 3 4076 16502 3. 0-9999 ( 1 = 1000 counts for output relays 1 to 5) 3/07 UDC3500 Universal Digital Controller Product Manual...
5 = May 6 = June 7 = July 8 = August 9 = September 10 = October 11 = November 12 = December Time Event 1 4063 16483 1 to 31 Days UDC3500 Universal Digital Controller Product Manual 3/07...
Page 447
4 = April 5 = May 6 = June 7 = July 8 = August 9 = September 10 = October 11 = November 12 = December Time Event Days 406C 16492 1 to 31 3/07 UDC3500 Universal Digital Controller Product Manual...
4 = Italian TC Diagnostics 009F 0 = Enable 1 = Disable Unit ID Number* 0029 0 to 255 * The Unit ID Number parameter can be used to uniquely identify a particular instrument. UDC3500 Universal Digital Controller Product Manual 3/07...
2005 to 2099 Time Zone (GMT) 4015 16405 -1200 to +1300 (hours and minutes away from GMT) Note: The Time Zone setting is used only for Email purposes, it has no other function. 3/07 UDC3500 Universal Digital Controller Product Manual...
In a normal response, the slave may return data or statistics in the data field. In an exception response, the slave returns an exception code in the data field. This defines the slave condition that caused the exception. UDC3500 Universal Digital Controller Product Manual 3/07...
Issue a PROGRAM POLL to obtain device- dependent error data. Buffer Overflow The data to be returned for the requested number of registers is greater than the available buffer space. Function Code 20 only. 3/07 UDC3500 Universal Digital Controller Product Manual...
Refer to Honeywell document 51-52-25-121 MODBUS Messaging on Ethernet TCP/IP Implementation Guide. 11.3 How to Apply Digital Instrumentation in Severe Electrical Noise Environments Refer to Honeywell document 51-52-05-01 How to Apply Digital Instrumentation in Severe Electrical Noise Environments. UDC3500 Universal Digital Controller Product Manual 3/07...
Pune 411013 FAX: (662) 693-3089 Abu Dhabi U A E Germany Email: kittinan.viriyasavetkul India. Middle East Headquarters Honeywell AG Phone: (91) 20-6603-9400 @honeywell.com Honeywell Middle East Ltd. Phone: +49 (69)8064336 Fax: (91) 20 6603-9600 UDC3500 Universal Digital Controller Product Manual 3/07...
Page 459
3/07 UDC3500 Universal Digital Controller Product Manual...
Page 460
Honeywell Process Solutions Industrial Measurement and Control 512 Virginia Drive Fort Washington, PA 19034 www.honeywell.com/ps 51-52-25-120 Rev. 3 03/07 Printed in USA...
Need help?
Do you have a question about the UDC3500 and is the answer not in the manual?
Questions and answers