Status Codes And Faults; Troubleshooting; Information And Service Menus - Bosch Condens 2000F30 Regular boiler Installation, Commissioning And Servicing Instruction Manual

Floor-standing gas-fired condensing appliance
Table of Contents

Advertisement

12
FAULT FINDING AND DIAGNOSTICS
12.1

Status codes and faults

The controller monitors all safety, regulation and control components.
Each operating state of the device is supported by a unique status code,
each fault by a fault code.
Detailed troubleshooting is possible using the following tables.
The operation and fault displays are shown as follows:
• Status codes, these show operating states during normal operation
– Status codes can be read during operation using the info menu
(service function i01)
• Blocking faults cause a temporary shutdown of the appliance. The
appliance restarts as soon as the blocking fault has been removed or
rectified.
– Display of blocking faults are with error code and status code
appears on the screen.
• Locking faults are system errors which cause the appliance to
shutdown. The appliance will only restart after a manual intervention
or a reset.
– Locking errors are with error codes and status code flash on the
display.
Fig. 74
[1]
Alphanumeric fault code
[2]
Service menu function
[3]
Status/cause code
12.2

Troubleshooting

DANGER: Explosion!
▶ Turn the gas supply off before working on gas related
components.
▶ After replacing gas components, seals and gaskets
check for gas tightness using a gas sniffer/analyser.
DANGER: Poisoning!
▶ Check for gas tightness using a gas sniffer/analyser
on gas and flue components.
DANGER: Electric shock!
▶ Before working on the electrical components
disconnect the electrical mains (230 V ac) and
secure against unintentional re-connection.
Product Name
1
2
3
6 720 619 605-33.1O
FAULT FINDING AND DIAGNOSTICS | 51
WARNING: Scalding!
Hot water can cause serious burns.
▶ Drain the appliance before working on water-
carrying parts.
NOTICE: Water leaks
Water can damage the controller.
▶ Protect from water leaks by covering the controller.
12.3

INFORMATION AND SERVICE MENUS

STATUS CODES
During normal boiler operation various Status codes can be displayed by
pressing the
button.
The first screen of the Information menu displays the current Status
code, this will change as the boiler runs through the various modes and
sequences.
These are not always faults, but just provide information concerning the
current status of the boiler.
Status
Fault
codes
codes
200
CH System is being heated
201
DHW system is being heated
202
Anti rapid cycle mode
203
System stand by
204
System waiting, primary flow temperature above
setpoint
205
Waiting for airflow
207
CE
System pressure too low
208
Test mode active due chimney switch
210
E9
Flue-gas thermostat activated
211
TTB opened (thermal kickback device)
212
Safety or flow temperature rises too fast
213
D4
Temperature difference between supply and return
exceeding limit
214
C7
Fan not running
215
C6
Fan running too fast
216
C6
Fan running too slow
217
C7
No airflow after defined period of time
218
E5
Flow temperature too high
219
E9
Safety sensor temperature too high
220
E9
Safety sensor shorted
221
E9
Safety sensor disconnected
222
E2
Flow sensor shorted
223
E2
Flow sensor disconnected
224
E9
MAX thermostat activated
225
Difference between flow and safety exceeding limit
(bi-sensor only)
227
EA
No ionisation detected after ignition
228
F7
Ionisation current detected before burner-start
229
EA
Loss of ionisation signal during operation
230
EA
Ionisation signal out of bounds
231
FD
Mains power error - electrical power interruption
232
D3
external cut-off switch activated
233
9U
HCM problem
234
EA
Gas valve coil disconnected
237
C4
Airflow present during last 24 hours - fan running
continuously
238
F0
Gas valve error
6 720 ... ... (YYYY/MM)