Beko METPOINT Installation And Operating Manual page 37

Thermal flow meter
Table of Contents

Advertisement

EN
6.8. 4 ... 20 mA
Setup → 4 - 20 mA
Setup → 4 - 20 mA → Channel 1
37
On this screen, you can adjust the settings for the 4 ... 20 mA analog output.
The following measurements can be configured:
Flow
Velocity
Temperature
unused = deactivate channel
The screenshot to the left shows the available units for flow. Press the "<<" button
to call up the next screen.
The scaling of the 4 ... 20 mA analog output can be set to automatic ("AutoRange
= on") or manual ("AutoRange = off").
With "AutoRange = on", the sensor automatically calculates the valid measuring
range and associated reference conditions, based on the set pipe diameter.
Select "Scale 4mA" and "Scale 20mA" to manually configure the scaling of the
output (precondition: "AutoRange = off").
Installation and operating manual
Enter the scale for 4 mA and 20 mA
respectively.